SP2-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
144
Rows
144
Columns
679
mainsVoltageTable
table.1.3.6.1.4.1.12148.10.3.4
·
1 row entry
·
10 columns
This table contains information about mains voltage monitor
Indexes
mainsVoltageIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsVoltageIndex
Index used for navigating the rows 1..12 of mainsVoltageTable
|
Integer32 Constraints: range: 1-12 |
.1.3.6.1.4.1.12148.10.3.4.1.1 |
|
mainsVoltageStatus
The status of the measured mains voltage.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.4.1.2 |
|
mainsVoltageDescription
A textual description of the mains voltage monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.3.4.1.3 |
|
mainsVoltageTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.3.4.1.4 |
|
mainsVoltageAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.4.1.5 |
|
mainsVoltageValue
The value of the measured mains voltage.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.4.1.6 |
|
mainsVoltageMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.4.1.7 |
|
mainsVoltageMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.4.1.8 |
|
mainsVoltageMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.4.1.9 |
|
mainsVoltageMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.4.1.10 |
mainsMonitorsTable
table.1.3.6.1.4.1.12148.10.3.5.2
·
1 row entry
·
4 columns
This table contains the number of voltage, current and frequency measurements in each AC Mains Monitor
Indexes
mainsMonitorIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorIndex
Index used for navigating the rows of mainsMonitorsTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.3.5.2.1.1 |
|
mainsMonitorNumberOfVoltages
The number of voltage measurements in the AC Mains Monitor
|
Integer32 Constraints: range: 0-3 |
.1.3.6.1.4.1.12148.10.3.5.2.1.2 |
|
mainsMonitorNumberOfCurrents
The number of current measurements in the AC Mains Monitor
|
Integer32 Constraints: range: 0-3 |
.1.3.6.1.4.1.12148.10.3.5.2.1.3 |
|
mainsMonitorNumberOfFrequencies
The number of frequency measurements in the AC Mains Monitor
|
Integer32 Constraints: range: 0-3 |
.1.3.6.1.4.1.12148.10.3.5.2.1.4 |
mainsMonitorVoltageTable
table.1.3.6.1.4.1.12148.10.3.5.3
·
1 row entry
·
10 columns
This table contains information about mains voltage in AC Mains Monitor
Indexes
mainsMonitorIndex mainsMonitorPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorPhaseIndex
Index used for navigating the rows 1..3 of mainsMonitorVolatgeTable
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.12148.10.3.5.3.1.1 |
|
mainsMonitorVoltageStatus
The status of the measured mains voltage in AC Mains Monitor.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.5.3.1.2 |
|
mainsMonitorVoltageDescription
A textual description of the mains voltage in AC Mains Monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.3.5.3.1.3 |
|
mainsMonitorVoltageTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.3.5.3.1.4 |
|
mainsMonitorVoltageAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.5.3.1.5 |
|
mainsMonitorVoltageValue
The value of the measured mains voltage in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.3.1.6 |
|
mainsMonitorVoltageMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.3.1.7 |
|
mainsMonitorVoltageMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.3.1.8 |
|
mainsMonitorVoltageMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.3.1.9 |
|
mainsMonitorVoltageMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.3.1.10 |
mainsMonitorCurrentTable
table.1.3.6.1.4.1.12148.10.3.5.4
·
1 row entry
·
7 columns
This table contains information about mains current in AC Mains Monitor
Indexes
mainsMonitorIndex mainsMonitorPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorCurrentStatus
The status of the measured mains current in AC Mains Monitor.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.5.4.1.1 |
|
mainsMonitorCurrentDescription
A textual description of the mains current in AC Mains Monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.3.5.4.1.2 |
|
mainsMonitorCurrentTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.3.5.4.1.3 |
|
mainsMonitorCurrentAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.5.4.1.4 |
|
mainsMonitorCurrentValue
The value of the measured mains current in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.4.1.5 |
|
mainsMonitorCurrentMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.4.1.6 |
|
mainsMonitorCurrentMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.4.1.7 |
.1.3.6.1.4.1.12148.10.3.5.5
·
1 row entry
·
9 columns
This table contains information about mains frequency in AC Mains Monitor
Indexes
mainsMonitorIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorFrequencyStatus
The status of the measured mains frequency in AC Mains Monitor.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.5.5.1.1 |
|
mainsMonitorFrequencyDescription
A textual description of the mains frequency in AC Mains Monitor. This is stored in the system
controller and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.3.5.5.1.2 |
|
mainsMonitorFrequencyTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.3.5.5.1.3 |
|
mainsMonitorFrequencyAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.5.5.1.4 |
|
mainsMonitorFrequencyValue
The value of the measured mains frequency in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.5.1.5 |
|
mainsMonitorFrequencyMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.5.1.6 |
|
mainsMonitorFrequencyMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.5.1.7 |
|
mainsMonitorFrequencyMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.5.1.8 |
|
mainsMonitorFrequencyMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.5.1.9 |
.1.3.6.1.4.1.12148.10.3.5.6
·
1 row entry
·
1 columns
This table contains the accumulated energy consumption measured in AC Mains Monitor
Indexes
mainsMonitorIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorEnergyLogAccumulated
The accumulated energy consumption value
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.6.1.1 |
.1.3.6.1.4.1.12148.10.3.5.8
·
1 row entry
·
2 columns
This table contains energy consumption values logged every hour in AC Mains Monitor.
Indexes
mainsMonitorIndex mainsMonitorEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.5.8.1.1 |
|
mainsMonitorEnergyLogLastHoursValue
Energy consumption value logged every hour in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.8.1.2 |
.1.3.6.1.4.1.12148.10.3.5.10
·
1 row entry
·
2 columns
This table contains energy consumption values logged every day in AC Mains Monitor.
Indexes
mainsMonitorIndex mainsMonitorEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.5.10.1.1 |
|
mainsMonitorEnergyLogLastDaysValue
Energy consumption value logged every day in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.10.1.2 |
.1.3.6.1.4.1.12148.10.3.5.12
·
1 row entry
·
2 columns
This table contains energy consumption values logged every week in AC Mains Monitor.
Indexes
mainsMonitorIndex mainsMonitorEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.5.12.1.1 |
|
mainsMonitorEnergyLogLastWeeksValue
Energy consumption value logged every week in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.12.1.2 |
.1.3.6.1.4.1.12148.10.3.5.13
·
1 row entry
·
7 columns
This table contains information about mains active power in AC Mains Monitor
Indexes
mainsMonitorIndex mainsMonitorPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorActivePowerStatus
The status of the measured mains active power in AC Mains Monitor.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.5.13.1.1 |
|
mainsMonitorActivePowerDescription
A textual description of the mains active power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.3.5.13.1.2 |
|
mainsMonitorActivePowerTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.3.5.13.1.3 |
|
mainsMonitorActivePowerAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.5.13.1.4 |
|
mainsMonitorActivePowerValue
The value of the measured mains active power in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.13.1.5 |
|
mainsMonitorActivePowerMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.13.1.6 |
|
mainsMonitorActivePowerMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.13.1.7 |
.1.3.6.1.4.1.12148.10.3.5.14
·
1 row entry
·
7 columns
This table contains information about mains reactive power in AC Mains Monitor
Indexes
mainsMonitorIndex mainsMonitorPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorReactivePowerStatus
The status of the measured mains reactive power in AC Mains Monitor.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.5.14.1.1 |
|
mainsMonitorReactivePowerDescription
A textual description of the mains reactive power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.3.5.14.1.2 |
|
mainsMonitorReactivePowerTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.3.5.14.1.3 |
|
mainsMonitorReactivePowerAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.5.14.1.4 |
|
mainsMonitorReactivePowerValue
The value of the measured mains reactive power in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.14.1.5 |
|
mainsMonitorReactivePowerMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.14.1.6 |
|
mainsMonitorReactivePowerMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.14.1.7 |
.1.3.6.1.4.1.12148.10.3.5.15
·
1 row entry
·
7 columns
This table contains information about mains apparent power in AC Mains Monitor
Indexes
mainsMonitorIndex mainsMonitorPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsMonitorApparentPowerStatus
The status of the measured mains apparent power in AC Mains Monitor.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.5.15.1.1 |
|
mainsMonitorApparentPowerDescription
A textual description of the mains apparent power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.3.5.15.1.2 |
|
mainsMonitorApparentPowerTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.3.5.15.1.3 |
|
mainsMonitorApparentPowerAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.5.15.1.4 |
|
mainsMonitorApparentPowerValue
The value of the measured mains apparent power in AC Mains Monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.15.1.5 |
|
mainsMonitorApparentPowerMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.15.1.6 |
|
mainsMonitorApparentPowerMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.5.15.1.7 |
mainsOutageLogDaysTable
table.1.3.6.1.4.1.12148.10.3.6.3
·
1 row entry
·
2 columns
This table contains daily mains outage or running time log depending on the log mode.
Indexes
mainsOutageLogDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsOutageLogDaysIndex
Index used for navigating the rows 1..52 of mainsOutageLogDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.6.3.1.1 |
|
mainsOutageLogDaysValue
Mains outage or running time value in minutes, logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.6.3.1.2 |
mainsOutageLogWeeksTable
table.1.3.6.1.4.1.12148.10.3.6.5
·
1 row entry
·
2 columns
This table contains weekly mains outage or running time log depending on the log mode.
Indexes
mainsOutageLogWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsOutageLogWeeksIndex
Index used for navigating the rows 1..52 of mainsOutageLogWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.6.5.1.1 |
|
mainsOutageLogWeeksValue
Mains outage or running time value in hours, logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.6.5.1.2 |
.1.3.6.1.4.1.12148.10.3.6.7
·
1 row entry
·
2 columns
This table contains monthly mains outage or running time log depending on the log mode.
Indexes
mainsOutageLogMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsOutageLogMonthsIndex
Index used for navigating the rows 1..52 of mainsOutageLogMonthsTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.6.7.1.1 |
|
mainsOutageLogMonthsValue
Mains outage or running time value in hours, logged every month.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.6.7.1.2 |
mainsGroupsTable
table.1.3.6.1.4.1.12148.10.3.8
·
1 row entry
·
3 columns
This table contains the status of mains group and number of phases in each group.
Indexes
mainsGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsGroupIndex
Index used for navigating the rows 1..10 of mainsGroupTable
|
Integer32 Constraints: range: 1-10 |
.1.3.6.1.4.1.12148.10.3.8.1.1 |
|
mainsGroupStatus
The status of mains group.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.8.1.2 |
|
mainsGroupNumberOfPhases
This value showing the number of phases of the mains group subsystem.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.8.1.3 |
.1.3.6.1.4.1.12148.10.3.9
·
1 row entry
·
7 columns
This table contains information about mains failure monitor of mains group
Indexes
mainsGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsGroupMainsFailureStatus
This status value shows if the number of failed phases is higher than the defined alarm level for the mains group
|
Enumeration | .1.3.6.1.4.1.12148.10.3.9.1.1 |
|
mainsGroupMainsFailureDescription
A textual description of the mains group phase failure monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.3.9.1.2 |
|
mainsGroupMainsFailureTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.9.1.3 |
|
mainsGroupMainsFailureAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.9.1.4 |
|
mainsGroupMainsFailureValue
The detected number of failed phases in the mains group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.9.1.5 |
|
mainsGroupMainsFailureMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.9.1.6 |
|
mainsGroupMainsFailureMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.9.1.7 |
mainsGroupVoltageTable
table.1.3.6.1.4.1.12148.10.3.10
·
1 row entry
·
10 columns
This table contains information about mains voltage monitors for mains group
Indexes
mainsGroupIndex mainsGroupVoltageIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsGroupVoltageIndex
Index used for navigating the rows 1..12 of mainsGroupVoltageTable
|
Integer32 Constraints: range: 1-12 |
.1.3.6.1.4.1.12148.10.3.10.1.1 |
|
mainsGroupVoltageStatus
The status of the measured mains voltage of the mains group.
|
Enumeration | .1.3.6.1.4.1.12148.10.3.10.1.2 |
|
mainsGroupVoltageDescription
A textual description of the mains voltage monitor of the mains group. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.3.10.1.3 |
|
mainsGroupVoltageTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.10.1.4 |
|
mainsGroupVoltageAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.3.10.1.5 |
|
mainsGroupVoltageValue
The value of the measured mains voltage in the mains group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.10.1.6 |
|
mainsGroupVoltageMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.10.1.7 |
|
mainsGroupVoltageMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.10.1.8 |
|
mainsGroupVoltageMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.10.1.9 |
|
mainsGroupVoltageMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.10.1.10 |
mainsGroupOutageLogTable
table.1.3.6.1.4.1.12148.10.3.11
·
1 row entry
·
4 columns
This table contains total mains outage of the mains group and number of entries in each log table.
Indexes
mainsGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsGroupOutageTotal
This is the total mains outage time measured in hours in the mains group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.11.1.1 |
|
mainsGroupOutageLogDaysNumberOfEntries
This is the maximal number of entries stored in daily mains outage log.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.11.1.2 |
|
mainsGroupOutageLogWeeksNumberOfEntries
This is the maximal number of entries stored in weekly mains outage time log.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.11.1.3 |
|
mainsGroupOutageLogMonthsNumberOfEntries
This is the maximal number of entries stored in monthly mains outage time log.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.11.1.4 |
.1.3.6.1.4.1.12148.10.3.12
·
1 row entry
·
2 columns
This table contains daily mains outage time log of mains group.
Indexes
mainsGroupIndex mainsGroupOutageLogDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsGroupOutageLogDaysIndex
Index used for navigating the rows 1..52 of mainsGroupOutageLogDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.12.1.1 |
|
mainsGroupOutageLogDaysValue
Mains outage time value in minutes of each mains group, logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.12.1.2 |
.1.3.6.1.4.1.12148.10.3.13
·
1 row entry
·
2 columns
This table contains weekly mains outage time log of mains group.
Indexes
mainsGroupIndex mainsGroupOutageLogWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsGroupOutageLogWeeksIndex
Index used for navigating the rows 1..52 of mainsGroupOutageLogWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.13.1.1 |
|
mainsGroupOutageLogWeeksValue
Mains outage time value in hours of each mains group, logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.13.1.2 |
.1.3.6.1.4.1.12148.10.3.14
·
1 row entry
·
2 columns
This table contains monthly mains outage time log of mains group.
Indexes
mainsGroupIndex mainsGroupOutageLogMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
mainsGroupOutageLogMonthsIndex
Index used for navigating the rows 1..52 of mainsGroupOutageLogMonthsTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.3.14.1.1 |
|
mainsGroupOutageLogMonthsValue
Mains outage time value in hours of each mains group, logged every month.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.3.14.1.2 |
.1.3.6.1.4.1.12148.10.4.16
·
1 row entry
·
3 columns
This table contains configurations of generator daily run.
Indexes
generatorDailyRunDayIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorDailyRunDayIndex
Index used for navigating the rows 1..7 of generatorDailyRunSetupTable
|
Enumeration | .1.3.6.1.4.1.12148.10.4.16.1.1 |
|
generatorDailyRunStartHour
Generator daily starting time.
|
Integer32r/w Constraints: range: 0-23 |
.1.3.6.1.4.1.12148.10.4.16.1.2 |
|
generatorDailyRunStopHour
Generator daily stopping time.
|
Integer32r/w Constraints: range: 0-23 |
.1.3.6.1.4.1.12148.10.4.16.1.3 |
generatorTankTable
table.1.3.6.1.4.1.12148.10.4.22
·
1 row entry
·
10 columns
This table contains information about generator fuel tanks.
Indexes
generatorTankIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorTankIndex
Index used for navigating the rows 1..2 of generatorTankTable
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.12148.10.4.22.1.1 |
|
generatorTankStatus
The status of the measured fuel level in tank.
|
Enumeration | .1.3.6.1.4.1.12148.10.4.22.1.2 |
|
generatorTankDescription
A textual description of the fuel level monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.4.22.1.3 |
|
generatorTankTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.4.22.1.4 |
|
generatorTankEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.4.22.1.5 |
|
generatorTankValue
The value of the measured fuel level.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.22.1.6 |
|
generatorTankMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.22.1.7 |
|
generatorTankMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.22.1.8 |
|
generatorTankMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.22.1.9 |
|
generatorTankMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.22.1.10 |
.1.3.6.1.4.1.12148.10.4.23.3
·
1 row entry
·
2 columns
This table contains hourly energy log of generator.
Indexes
generatorEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of generatorEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.23.3.1.1 |
|
generatorEnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.23.3.1.2 |
.1.3.6.1.4.1.12148.10.4.23.5
·
1 row entry
·
2 columns
This table contains daily energy log of generator.
Indexes
generatorEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of generatorEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.23.5.1.1 |
|
generatorEnergyLogLastDaysValue
Energy value logged every day
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.23.5.1.2 |
.1.3.6.1.4.1.12148.10.4.23.7
·
1 row entry
·
2 columns
This table contains weekly energy log of generator.
Indexes
generatorEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of generatorEnergyLogLastWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.23.7.1.1 |
|
generatorEnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.23.7.1.2 |
.1.3.6.1.4.1.12148.10.4.24.3
·
1 row entry
·
2 columns
generator running time in minutes
Indexes
generatorRunHoursLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorRunHoursLogLastDaysIndex
Index used for navigating the rows 1..52 of generatorRunHoursLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.24.3.1.1 |
|
generatorRunHoursLogLastDaysValue
Generator running time in minutes, logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.24.3.1.2 |
.1.3.6.1.4.1.12148.10.4.24.5
·
1 row entry
·
2 columns
generator running time in hours
Indexes
generatorRunHoursLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorRunHoursLogLastWeeksIndex
Index used for navigating the rows 1..52 of generatorRunHoursLogLastWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.24.5.1.1 |
|
generatorRunHoursLogLastWeeksValue
Generator running time in hours, logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.24.5.1.2 |
.1.3.6.1.4.1.12148.10.4.24.7
·
1 row entry
·
2 columns
generator running time in hours
Indexes
generatorRunHoursLogLastMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorRunHoursLogLastMonthsIndex
Index used for navigating the rows 1..52 of generatorRunHoursLogLastMonthsTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.24.7.1.1 |
|
generatorRunHoursLogLastMonthsValue
Generator running time in hours, logged every month.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.24.7.1.2 |
.1.3.6.1.4.1.12148.10.4.25.1
·
1 row entry
·
1 columns
This table contains total fuel consumption for each tank.
Indexes
generatorTankIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorFuelConsumptionTotalUsed
Total fuel consumption value.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.25.1.1.1 |
.1.3.6.1.4.1.12148.10.4.25.3
·
1 row entry
·
2 columns
This table contains generator daily fuel consumption log.
Indexes
generatorTankIndex generatorFuelConsumptionLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorFuelConsumptionLogLastDaysIndex
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.25.3.1.1 |
|
generatorFuelConsumptionLogLastDaysValue
Generator fuel consumption value, logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.25.3.1.2 |
.1.3.6.1.4.1.12148.10.4.25.5
·
1 row entry
·
2 columns
This table contains generator weekly fuel consumption log.
Indexes
generatorTankIndex generatorFuelConsumptionLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorFuelConsumptionLogLastWeeksIndex
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.25.5.1.1 |
|
generatorFuelConsumptionLogLastWeeksValue
Generator fuel consumption value, logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.25.5.1.2 |
.1.3.6.1.4.1.12148.10.4.25.7
·
1 row entry
·
2 columns
This table contains generator hourly fuel consumption log.
Indexes
generatorTankIndex generatorFuelConsumptionLogLastMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
generatorFuelConsumptionLogLastMonthsIndex
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.4.25.7.1.1 |
|
generatorFuelConsumptionLogLastMonthsValue
Generator fuel consumption value, logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.4.25.7.1.2 |
rectifierTable
table.1.3.6.1.4.1.12148.10.5.6
·
1 row entry
·
10 columns
This table shows the information of each rectifier installed in the system.
Indexes
rectifierIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierIndex
Index used for navigating the rows 1..100 of rectifierTable
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.12148.10.5.6.1.1 |
|
rectifierStatus
The overall status of rectifier.
|
Enumeration | .1.3.6.1.4.1.12148.10.5.6.1.2 |
|
rectifierOutputCurrentValue
The output current value of rectifier.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.6.1.3 |
|
rectifierInputVoltageValue
The input voltage value of rectifier.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.6.1.4 |
|
rectifierType
Type of rectifier
|
OctetString Constraints: range: 0-27 |
.1.3.6.1.4.1.12148.10.5.6.1.5 |
|
rectifierHwPartNumber
Hardware part number of rectifier
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.5.6.1.6 |
|
rectifierHwVersion
Hardware version number of rectifier
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.5.6.1.7 |
|
rectifierSwPartNumber
Part number of secondary software in rectifier
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.5.6.1.8 |
|
rectifierSwVersion
Version number of secondary software in rectifier
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.5.6.1.9 |
|
rectifierSerialNumber
Serial number of rectifier
|
OctetString Constraints: range: 1-12 |
.1.3.6.1.4.1.12148.10.5.6.1.10 |
.1.3.6.1.4.1.12148.10.5.7.3
·
1 row entry
·
2 columns
This table contains hourly energy log of rectifiers.
Indexes
rectifiersEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifiersEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.5.7.3.1.1 |
|
rectifiersEnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.7.3.1.2 |
.1.3.6.1.4.1.12148.10.5.7.5
·
1 row entry
·
2 columns
This table contains daily energy log of rectifiers.
Indexes
rectifiersEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifiersEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.5.7.5.1.1 |
|
rectifiersEnergyLogLastDaysValue
Energy value logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.7.5.1.2 |
.1.3.6.1.4.1.12148.10.5.7.7
·
1 row entry
·
2 columns
This table contains weekly energy log of rectifiers.
Indexes
rectifiersEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifiersEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastWeekTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.5.7.7.1.1 |
|
rectifiersEnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.7.7.1.2 |
rectifierGroupsTable
table.1.3.6.1.4.1.12148.10.5.9
·
1 row entry
·
3 columns
This table contains status and the number of installed rectifiers of each rectifier groups.
Indexes
rectifierGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupIndex
Index used for navigating the rows 1..10 of rectifierGroupsTable
|
Integer32 Constraints: range: 1-10 |
.1.3.6.1.4.1.12148.10.5.9.1.1 |
|
rectifierGroupStatus
The status of each rectifier group.
|
Enumeration | .1.3.6.1.4.1.12148.10.5.9.1.2 |
|
rectifierGroupNumberOfRectifiers
Number of installed rectifiers in each rectifier groups
|
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.12148.10.5.9.1.3 |
.1.3.6.1.4.1.12148.10.5.10
·
1 row entry
·
7 columns
This table contains information about the total rectifier current of each rectifier groups, which is calculated by summing up current from each rectifier in a rectifier group.
Indexes
rectifierGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupCurrentStatus
The status of the measured total rectifier current of the rectifier group
|
Enumeration | .1.3.6.1.4.1.12148.10.5.10.1.1 |
|
rectifierGroupCurrentDescription
A textual description of the total rectifier current monitor of a rectifier group. This is stored in the system controller
and can be changed by the user |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.5.10.1.2 |
|
rectifierGroupCurrentTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.10.1.3 |
|
rectifierGroupCurrentAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.5.10.1.4 |
|
rectifierGroupCurrentValue
The value of the measured total rectifier current of each rectifier group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.10.1.5 |
|
rectifierGroupCurrentMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.10.1.6 |
|
rectifierGroupCurrentMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.10.1.7 |
.1.3.6.1.4.1.12148.10.5.11
·
1 row entry
·
7 columns
This table contains information about the used rectifier capacity of each rectifier group.
Indexes
rectifierGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupCapacityStatus
The status of the measured used rectifier capacity of each rectifier group
|
Enumeration | .1.3.6.1.4.1.12148.10.5.11.1.1 |
|
rectifierGroupCapacityDescription
A textual description of the used rectifier capacity monitor of each rectifier group. This is stored in the system controller
and can be changed by the user |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.5.11.1.2 |
|
rectifierGroupCapacityTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.11.1.3 |
|
rectifierGroupCapacityAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.5.11.1.4 |
|
rectifierGroupCapacityValue
The used rectifier capacity value presented in percentage of the total installed rectifier capacity of each rectifier group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.11.1.5 |
|
rectifierGroupCapacityMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.11.1.6 |
|
rectifierGroupCapacityMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.11.1.7 |
rectifierGroupErrorTable
table.1.3.6.1.4.1.12148.10.5.12
·
1 row entry
·
7 columns
This table contains information about the rectifier error monitor of each rectifier group.
Indexes
rectifierGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupErrorStatus
This status value shows if the number of failed units is higher than the defined alarm level.
|
Enumeration | .1.3.6.1.4.1.12148.10.5.12.1.1 |
|
rectifierGroupErrorDescription
A textual description of the rectifier error monitor of each rectifier group. This is stored in the system controller
and can be changed by the user |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.5.12.1.2 |
|
rectifierGroupErrorTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.12.1.3 |
|
rectifierGroupErrorAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.5.12.1.4 |
|
rectifierGroupErrorValue
The number of failed rectifiers of each rectifier group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.12.1.5 |
|
rectifierGroupErrorMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.12.1.6 |
|
rectifierGroupErrorMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.12.1.7 |
.1.3.6.1.4.1.12148.10.5.13
·
1 row entry
·
9 columns
This table shows the information of each rectifier installed in each of the rectifier group in the system.
Indexes
rectifierGroupIndex rectifierGroupRectifierIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupRectifierIndex
Index used for navigating the rows 1..100 of rectifierGroupRectifierTable
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.12148.10.5.13.1.1 |
|
rectifierGroupRectifierStatus
The overall status of rectifier.
|
Enumeration | .1.3.6.1.4.1.12148.10.5.13.1.2 |
|
rectifierGroupRectifierOutputCurrentValue
The output current value of rectifier.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.13.1.3 |
|
rectifierGroupRectifierInputVoltageValue
The input voltage value of rectifier.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.13.1.4 |
|
rectifierGroupRectifierType
Type of rectifier
|
OctetString Constraints: range: 0-27 |
.1.3.6.1.4.1.12148.10.5.13.1.5 |
|
rectifierGroupRectifierHwPartNumber
Hardware part number of rectifier
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.5.13.1.6 |
|
rectifierGroupRectifierHwVersion
Hardware version number of rectifier
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.5.13.1.7 |
|
rectifierGroupRectifierSwPartNumber
Part number of secondary software in rectifier
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.5.13.1.8 |
|
rectifierGroupRectifierSwVersion
Version number of secondary software in rectifier
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.5.13.1.9 |
.1.3.6.1.4.1.12148.10.5.14
·
1 row entry
·
4 columns
This branch contains information about rectifiers' energy logs of each rectifier group.
Indexes
rectifierGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupEnergyLogAccumulated
This is the accumulated energy delivered from rectifiers of each rectifier group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.14.1.1 |
|
rectifierGroupEnergyLogLastHoursNumberOfEntries
This is the maximal number of entries stored in rectifier group hourly energy log.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.14.1.2 |
|
rectifierGroupEnergyLogLastDaysNumberOfEntries
This is the maximal number of entries stored in rectifier group daily energy log.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.14.1.3 |
|
rectifierGroupEnergyLogLastWeeksNumberOfEntries
This is the maximal number of entries stored in rectifier group weekly energy log.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.14.1.4 |
.1.3.6.1.4.1.12148.10.5.15
·
1 row entry
·
2 columns
This table contains hourly energy log of each rectifier group
Indexes
rectifierGroupIndex rectifierGroupEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.5.15.1.1 |
|
rectifierGroupEnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.15.1.2 |
.1.3.6.1.4.1.12148.10.5.16
·
1 row entry
·
2 columns
This table contains daily energy log of each rectifier group
Indexes
rectifierGroupIndex rectifierGroupEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLasDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.5.16.1.1 |
|
rectifierGroupEnergyLogLastDaysValue
Energy value logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.16.1.2 |
.1.3.6.1.4.1.12148.10.5.17
·
1 row entry
·
2 columns
This table contains weekly energy log of each rectifier group
Indexes
rectifierGroupIndex rectifierGroupEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLastWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.5.17.1.1 |
|
rectifierGroupEnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.17.1.2 |
.1.3.6.1.4.1.12148.10.5.19
·
1 row entry
·
9 columns
This table contains information about the highest rectifier temperature of each rectifier groups, which is calculated by summing up current from each rectifier in a rectifier group.
Indexes
rectifierGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
rectifierGroupTemperatureStatus
The status of the measured highest rectifier temperature of the rectifier group
|
Enumeration | .1.3.6.1.4.1.12148.10.5.19.1.1 |
|
rectifierGroupTemperatureDescription
A textual description of the highest rectifier temperature monitor of a rectifier group. This is stored in the system controller
and can be changed by the user |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.5.19.1.2 |
|
rectifierGroupTemperatureTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.19.1.3 |
|
rectifierGroupTemperatureAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.5.19.1.4 |
|
rectifierGroupTemperatureValue
The value of the measured highest rectifier temperature of each rectifier group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.19.1.5 |
|
rectifierGroupTemperatureMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.19.1.6 |
|
rectifierGroupTemperatureMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.19.1.7 |
|
rectifierGroupTemperatureMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.19.1.8 |
|
rectifierGroupTemperatureMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.5.19.1.9 |
dcdcGroupsTable
table.1.3.6.1.4.1.12148.10.6.2
·
1 row entry
·
7 columns
This table contains information about dcdc groups.
Indexes
dcdcGroupIndex
| Column | Syntax | OID |
|---|---|---|
| dcdcGroupIndex | Integer32 Constraints: range: 1-10 |
.1.3.6.1.4.1.12148.10.6.2.1.1 |
|
dcdcGroupStatus
The overall status of dcdc group.
|
Enumeration | .1.3.6.1.4.1.12148.10.6.2.1.2 |
|
dcdcGroupNumberOfDcdcConverters
Number of installed dcdc converters.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.2.1.3 |
|
dcdcGroupOutputVoltage
Output voltage of dcdc converters
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.2.1.4 |
|
dcdcNumberOfCurrents
Number of dcdc currents
|
Integer32 Constraints: range: 0-5 |
.1.3.6.1.4.1.12148.10.6.2.1.5 |
|
dcdcNumberOfCapacities
Number of dcdc capacities
|
Integer32 Constraints: range: 0-5 |
.1.3.6.1.4.1.12148.10.6.2.1.6 |
|
dcdcNumberOfAlarms
Number of dcdc alarms
|
Integer32 Constraints: range: 0-5 |
.1.3.6.1.4.1.12148.10.6.2.1.7 |
dcdcCurrentTable
table.1.3.6.1.4.1.12148.10.6.3
·
1 row entry
·
7 columns
This table contains information about the total dcdc current.
Indexes
dcdcGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
dcdcCurrentStatus
The status of the measured total dcdc current.
|
Enumeration | .1.3.6.1.4.1.12148.10.6.3.1.1 |
|
dcdcCurrentDescription
A textual description of the total dcdc current monitor. This is stored in the system controller
and can be changed by the user |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.6.3.1.2 |
|
dcdcCurrentTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.6.3.1.3 |
|
dcdcCurrentAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.6.3.1.4 |
|
dcdcCurrentValue
The value of the measured total dcdc current.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.3.1.5 |
|
dcdcCurrentMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.3.1.6 |
|
dcdcCurrentMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.3.1.7 |
dcdcCapacityTable
table.1.3.6.1.4.1.12148.10.6.4
·
1 row entry
·
7 columns
This table contains information about the used dcdc capacity.
Indexes
dcdcGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
dcdcCapacityStatus
The status of the measured used dcdc capacity.
|
Enumeration | .1.3.6.1.4.1.12148.10.6.4.1.1 |
|
dcdcCapacityDescription
A textual description of the used dcdc capacity monitor. This is stored in the system controller
and can be changed by the user |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.6.4.1.2 |
|
dcdcCapacityTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.6.4.1.3 |
|
dcdcCapacityAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.6.4.1.4 |
|
dcdcCapacityValue
The used dcdc capacity value presented in percentage of the total installed dcdc capacity.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.4.1.5 |
|
dcdcCapacityMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.4.1.6 |
|
dcdcCapacityMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.4.1.7 |
dcdcTable
table.1.3.6.1.4.1.12148.10.6.5
·
1 row entry
·
9 columns
This table shows the information of each dcdc converter installed in the system.
Indexes
dcdcGroupIndex dcdcIndex
| Column | Syntax | OID |
|---|---|---|
|
dcdcIndex
Index used for navigating the rows 1..100 of dcdcTable
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.12148.10.6.5.1.1 |
|
dcdcStatus
The overall status of dcdc converter
|
Enumeration | .1.3.6.1.4.1.12148.10.6.5.1.2 |
|
dcdcOutputCurrentValue
The output current value of dcdc.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.5.1.3 |
|
dcdcInputVoltageValue
The input voltage value of dcdc.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.5.1.4 |
|
dcdcType
Type of dcdc converter
|
OctetString Constraints: range: 0-27 |
.1.3.6.1.4.1.12148.10.6.5.1.5 |
|
dcdcHwPartNumber
Hardware part number of dcdc converter
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.6.5.1.6 |
|
dcdcHwVersion
Hardware version number of dcdc converter
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.6.5.1.7 |
|
dcdcSwPartNumber
Part number of secondary software in dcdc converter
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.6.5.1.8 |
|
dcdcSwVersion
Version number of secondary software in dcdc converter
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.6.5.1.9 |
dcdcErrorTable
table.1.3.6.1.4.1.12148.10.6.6
·
1 row entry
·
7 columns
This table contains information about the dcdc error monitor.
Indexes
dcdcGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
dcdcErrorStatus
This status value shows if the number of failed units is higher than the defined alarm level.
|
Enumeration | .1.3.6.1.4.1.12148.10.6.6.1.1 |
|
dcdcErrorDescription
A textual description of the dcdc error monitor. This is stored in the system controller
and can be changed by the user |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.6.6.1.2 |
|
dcdcErrorTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.6.6.1.3 |
|
dcdcErrorEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.6.6.1.4 |
|
dcdcErrorValue
The number of failed dcdc converters.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.6.1.5 |
|
dcdcErrorMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.6.1.6 |
|
dcdcErrorMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.6.6.1.7 |
solarChargerTable
table.1.3.6.1.4.1.12148.10.7.6
·
1 row entry
·
9 columns
This table shows the information of each solar charger installed in the system.
Indexes
solarChargerIndex
| Column | Syntax | OID |
|---|---|---|
|
solarChargerIndex
Index used for navigating the rows 1..100 of solarChargerTable
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.12148.10.7.6.1.1 |
|
solarChargerStatus
The overall status of solar charger.
|
Enumeration | .1.3.6.1.4.1.12148.10.7.6.1.2 |
|
solarChargerOutputCurrentValue
The output current value of solar charger.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.7.6.1.3 |
|
solarChargerInputVoltageValue
The input voltage value of solar charger.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.7.6.1.4 |
|
solarChargerType
Type of solar charger
|
OctetString Constraints: range: 0-27 |
.1.3.6.1.4.1.12148.10.7.6.1.5 |
|
solarChargerHwPartNumber
Hardware part number of solar charger
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.7.6.1.6 |
|
solarChargerHwVersion
Hardware version number of solar charger
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.7.6.1.7 |
|
solarChargerSwPartNumber
Part number of secondary software in solar charger
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.7.6.1.8 |
|
solarChargerSwVersion
Version number of secondary software in solar charger
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.7.6.1.9 |
.1.3.6.1.4.1.12148.10.7.7.3
·
1 row entry
·
2 columns
This table contains hourly energy log of solar chargers.
Indexes
solarChargersEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
solarChargersEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.7.7.3.1.1 |
|
solarChargersEnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.7.7.3.1.2 |
.1.3.6.1.4.1.12148.10.7.7.5
·
1 row entry
·
2 columns
This table contains daily energy log of solar chargers.
Indexes
solarChargersEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
solarChargersEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.7.7.5.1.1 |
|
solarChargersEnergyLogLastDaysValue
Energy value logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.7.7.5.1.2 |
.1.3.6.1.4.1.12148.10.7.7.7
·
1 row entry
·
2 columns
This table contains weekly energy log of solar chargers.
Indexes
solarChargersEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
solarChargersEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastWeekTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.7.7.7.1.1 |
|
solarChargersEnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.7.7.7.1.2 |
windChargerTable
table.1.3.6.1.4.1.12148.10.8.6
·
1 row entry
·
9 columns
This table shows the information of each wind charger installed in the system.
Indexes
windChargerIndex
| Column | Syntax | OID |
|---|---|---|
|
windChargerIndex
Index used for navigating the rows 1..100 of windChargerTable
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.12148.10.8.6.1.1 |
|
windChargerStatus
The overall status of wind charger.
|
Enumeration | .1.3.6.1.4.1.12148.10.8.6.1.2 |
|
windChargerOutputCurrentValue
The output current value of wind charger.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.8.6.1.3 |
|
windChargerInputVoltageValue
The input voltage value of wind charger.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.8.6.1.4 |
|
windChargerType
Type of wind charger
|
OctetString Constraints: range: 0-27 |
.1.3.6.1.4.1.12148.10.8.6.1.5 |
|
windChargerHwPartNumber
Hardware part number of wind charger
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.8.6.1.6 |
|
windChargerHwVersion
Hardware version number of wind charger
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.8.6.1.7 |
|
windChargerSwPartNumber
Part number of secondary software in wind charger
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.8.6.1.8 |
|
windChargerSwVersion
Version number of secondary software in wind charger
|
OctetString Constraints: range: 0-6 |
.1.3.6.1.4.1.12148.10.8.6.1.9 |
.1.3.6.1.4.1.12148.10.8.7.3
·
1 row entry
·
2 columns
This table contains hourly energy log of wind chargers.
Indexes
windChargersEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
windChargersEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of windChargersEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.8.7.3.1.1 |
|
windChargersEnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.8.7.3.1.2 |
.1.3.6.1.4.1.12148.10.8.7.5
·
1 row entry
·
2 columns
This table contains daily energy log of wind chargers.
Indexes
windChargersEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
windChargersEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of windChargersEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.8.7.5.1.1 |
|
windChargersEnergyLogLastDaysValue
Energy value logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.8.7.5.1.2 |
.1.3.6.1.4.1.12148.10.8.7.7
·
1 row entry
·
2 columns
This table contains weekly energy log of wind chargers.
Indexes
windChargersEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
windChargersEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of windChargersEnergyLogLastWeekTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.8.7.7.1.1 |
|
windChargersEnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.8.7.7.1.2 |
loadGroupTable
table.1.3.6.1.4.1.12148.10.9.5
·
1 row entry
·
4 columns
This table contains information about load groups.
Indexes
loadGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
loadGroupIndex
Index used for navigating the rows 1..8 of loadGroupTable
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.9.5.1.1 |
|
loadGroupStatus
The status of load group
|
Enumeration | .1.3.6.1.4.1.12148.10.9.5.1.2 |
|
loadNumberOfLVLDs
Number of LVLDs installed in load group
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.9.5.1.3 |
|
loadNumberOfVoltages
Number of voltages in load group
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.9.5.1.4 |
loadLVLDTable
table.1.3.6.1.4.1.12148.10.9.6
·
1 row entry
·
10 columns
This table contains information about LVLDs
Indexes
loadGroupIndex loadLVLDIndex
| Column | Syntax | OID |
|---|---|---|
|
loadLVLDIndex
Index used for navigating the rows 1..8 of loadLVLDTable
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.9.6.1.1 |
|
loadLVLDStatus
The status of LVLD
|
Enumeration | .1.3.6.1.4.1.12148.10.9.6.1.2 |
|
loadLVLDDescription
A textual description of the LVLD. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.9.6.1.3 |
|
loadLVLDTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.9.6.1.4 |
|
loadLVLDEnable
This value once enabled, the alarm condition of the LVLD will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.9.6.1.5 |
|
loadLVLDValue
The measured value of the LVLD.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.6.1.6 |
|
loadLVLDConnectVoltage
The load Contactor's Reconnect Voltage
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.6.1.7 |
|
loadLVLDDisconnectVoltage
The load Contactor's Disconnect Voltage
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.6.1.8 |
|
loadLVLDDisconnectDelayEnable
Enable/disable LVLD disconnect delay.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.9.6.1.9 |
|
loadLVLDDisconnectDelayTime
LVLD disconnect delay time in minutes.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.6.1.10 |
loadFuseTable
table.1.3.6.1.4.1.12148.10.9.7
·
1 row entry
·
5 columns
This table contains information about load fuse
Indexes
loadGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
loadFuseStatus
The status of load fuse
|
Enumeration | .1.3.6.1.4.1.12148.10.9.7.1.1 |
|
loadFuseDescription
A textual description of the load fuse monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.9.7.1.2 |
|
loadFuseTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.9.7.1.3 |
|
loadFuseAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.9.7.1.4 |
|
loadFuseValue
The measured value of the load fuse.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.7.1.5 |
.1.3.6.1.4.1.12148.10.9.8.3
·
1 row entry
·
2 columns
Indexes
loadEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
loadEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of loadEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.9.8.3.1.1 |
|
loadEnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.8.3.1.2 |
.1.3.6.1.4.1.12148.10.9.8.5
·
1 row entry
·
2 columns
Indexes
loadEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
loadEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of loadEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.9.8.5.1.1 |
|
loadEnergyLogLastDaysValue
Energy value logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.8.5.1.2 |
.1.3.6.1.4.1.12148.10.9.8.7
·
1 row entry
·
2 columns
Indexes
loadEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
loadEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of loadEnergyLogLastWeekTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.9.8.7.1.1 |
|
loadEnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.8.7.1.2 |
loadVoltageTable
table.1.3.6.1.4.1.12148.10.9.9
·
1 row entry
·
6 columns
This table contains information about voltages
Indexes
loadGroupIndex loadVoltageIndex
| Column | Syntax | OID |
|---|---|---|
|
loadVoltageIndex
Index used for navigating the rows 1..3 of loadVoltageTable
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.12148.10.9.9.1.1 |
|
loadVoltageStatus
The status of voltage
|
Enumeration | .1.3.6.1.4.1.12148.10.9.9.1.2 |
|
loadVoltageDescription
A textual description of the voltage. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.9.9.1.3 |
|
loadVoltageTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.9.9.1.4 |
|
loadVoltageEnable
This value once enabled, the alarm condition of the LVLD will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.9.9.1.5 |
|
loadVoltageValue
The measured value of the voltage.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.9.9.1.6 |
batteryTestResultTable
table.1.3.6.1.4.1.12148.10.10.16.4
·
1 row entry
·
9 columns
This table contains the battery test results stored in controller.
Indexes
batteryTestResultIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryTestResultIndex
A index pointing to one of ten possible battery test results
|
Integer32 Constraints: range: 1-10 |
.1.3.6.1.4.1.12148.10.10.16.4.1.1 |
|
batteryTestResultStartDateTime
This is the time and date when the test started.
|
SNMPv2-TCDateAndTime Textual Convention: SNMPv2-TCDateAndTime OctetStringType Constraints: range: 8range: 11 |
.1.3.6.1.4.1.12148.10.10.16.4.1.2 |
|
batteryTestResultDuration
This is the test duration in minutes.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.16.4.1.3 |
|
batteryTestResultDischarged
This is the discharged Ah during test.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.16.4.1.4 |
|
batteryTestResultQuality
This is the calculated battery quality (SoH)in percentage.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.16.4.1.5 |
|
batteryTestResultEndVoltage
This is the test end voltage in volt.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.16.4.1.6 |
|
batteryTestResultTestResult
This is the test result.
|
Enumeration | .1.3.6.1.4.1.12148.10.10.16.4.1.7 |
|
batteryTestResultTerminationCriteria
This is the test Termination Criteria.
|
Enumeration | .1.3.6.1.4.1.12148.10.10.16.4.1.8 |
|
batteryTestResultBatteryTemperature
This is the battery temperature
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.16.4.1.9 |
batteryBankTable
table.1.3.6.1.4.1.12148.10.10.18.2
·
1 row entry
·
6 columns
Indexes
batteryBankIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryBankIndex
Index used for navigating the rows 1..8 of batteryBankTable
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.10.18.2.1.1 |
|
batteryBankStatus
The overall status of battery bank
|
Enumeration | .1.3.6.1.4.1.12148.10.10.18.2.1.2 |
|
batteryBankNumberOfTemperatures
Number of temperature measurements in battery bank.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.10.18.2.1.3 |
|
batteryBankNumberOfCurrents
Number of current measurements in battery bank.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.10.18.2.1.4 |
|
batteryBankNumberOfFuses
Number of fuses installed in battery bank.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.10.18.2.1.5 |
|
batteryBankNumberOfSymmetries
Number of symmetry measurements available in battery bank.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.10.18.2.1.6 |
.1.3.6.1.4.1.12148.10.10.18.3
·
1 row entry
·
10 columns
Indexes
batteryBankIndex batteryTemperatureIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryTemperatureIndex
This index denotes which row in the temperature input table.
The size of the table is defined by the batteryBankNumberOfTemp |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.10.18.3.1.1 |
|
batteryTemperatureStatus
The status of battery temperature monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.10.18.3.1.2 |
|
batteryTemperatureDescription
A textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.18.3.1.3 |
|
batteryTemperatureTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.10.18.3.1.4 |
|
batteryTemperatureAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.10.18.3.1.5 |
|
batteryTemperatureValue
The measured battery temperature.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.3.1.6 |
|
batteryTemperatureMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.3.1.7 |
|
batteryTemperatureMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.3.1.8 |
|
batteryTemperatureMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.3.1.9 |
|
batteryTemperatureMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.3.1.10 |
batteryBankCurrentTable
table.1.3.6.1.4.1.12148.10.10.18.4
·
1 row entry
·
10 columns
Indexes
batteryBankIndex batteryCurrentIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryCurrentIndex
This index denotes which row in the current input table.
The size of the table is defined by the system |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.10.18.4.1.1 |
|
batteryCurrentStatus
The status of battery current monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.10.18.4.1.2 |
|
batteryCurrentDescription
A textual description of the battery current monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.18.4.1.3 |
|
batteryCurrentTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.10.18.4.1.4 |
|
batteryCurrentAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.10.18.4.1.5 |
|
batteryCurrentValue
The measured battery current
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.4.1.6 |
|
batteryCurrentMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.4.1.7 |
|
batteryCurrentMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.4.1.8 |
|
batteryCurrentMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.4.1.9 |
|
batteryCurrentMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.4.1.10 |
batteryBankFuseTable
table.1.3.6.1.4.1.12148.10.10.18.5
·
1 row entry
·
6 columns
Indexes
batteryBankIndex batteryFuseIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryFuseIndex
This index denotes which row in the fuse table.
The size of the table is defined by the system |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.10.18.5.1.1 |
|
batteryFuseStatus
The status of battery fuse monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.10.18.5.1.2 |
|
batteryFuseDescription
A textual description of the battery fuse monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.18.5.1.3 |
|
batteryFuseTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.10.18.5.1.4 |
|
batteryFuseAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.10.18.5.1.5 |
|
batteryFuseValue
The measured value of battery fuse input.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.5.1.6 |
batteryBankSymmetryTable
table.1.3.6.1.4.1.12148.10.10.18.6
·
1 row entry
·
9 columns
Indexes
batteryBankIndex batteryBankSymmetryIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryBankSymmetryIndex
This index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries |
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.10.18.6.1.1 |
|
batteryBankSymmetryStatus
The status of battery symmetry monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.10.18.6.1.2 |
|
batteryBankSymmetryDescription
A textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.18.6.1.3 |
|
batteryBankSymmetryTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.10.18.6.1.4 |
|
batteryBankSymmetryAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.10.18.6.1.5 |
|
batteryBankSymmetryMeasureValue
The measured battery symmetry voltage in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.6.1.6 |
|
batteryBankSymmetryDeltaValue
The measured battery symmetry delta voltage in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.6.1.7 |
|
batteryBankSymmetryMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.6.1.8 |
|
batteryBankSymmetryMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.18.6.1.9 |
batteryMonitorsTable
table.1.3.6.1.4.1.12148.10.10.19.2
·
1 row entry
·
5 columns
Indexes
batteryMonitorIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryMonitorIndex
Index used for navigating the rows 1..8 of batteryMonitorsTable
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.10.19.2.1.1 |
|
batteryMonitorNumberOfTemperatures
The number of temperature measurements in battery monitor.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.10.19.2.1.2 |
|
batteryMonitorNumberOfCurrents
The number of current measurements in battery monitor.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.10.19.2.1.3 |
|
batteryMonitorNumberOfFuses
The number of fuse measurements in battery monitor.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.10.19.2.1.4 |
|
batteryMonitorNumberOfSymmetries
The number of symmetry measurements in battery monitor.
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.10.19.2.1.5 |
.1.3.6.1.4.1.12148.10.10.19.3
·
1 row entry
·
10 columns
Indexes
batteryMonitorIndex batteryMonitorTemperatureIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryMonitorTemperatureIndex
This index denotes which row in the temperature input table.
The size of the table is defined by the batteryMonitorNumberOfTemperatures |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.10.19.3.1.1 |
|
batteryMonitorTemperatureStatus
The status of battery temperature monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.10.19.3.1.2 |
|
batteryMonitorTemperatureDescription
A textual description of the battery monitor temperature. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.19.3.1.3 |
|
batteryMonitorTemperatureTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.10.19.3.1.4 |
|
batteryMonitorTemperatureAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.10.19.3.1.5 |
|
batteryMonitorTemperatureValue
The measured battery temperature in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.3.1.6 |
|
batteryMonitorTemperatureMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.3.1.7 |
|
batteryMonitorTemperatureMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.3.1.8 |
|
batteryMonitorTemperatureMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.3.1.9 |
|
batteryMonitorTemperatureMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.3.1.10 |
.1.3.6.1.4.1.12148.10.10.19.4
·
1 row entry
·
10 columns
Indexes
batteryMonitorIndex batteryMonitorCurrentIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryMonitorCurrentIndex
This index denotes which row in the current input table.
The size of the table is defined by the batteryMonitorNumberOfCurrents |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.10.19.4.1.1 |
|
batteryMonitorCurrentStatus
The status of battery current monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.10.19.4.1.2 |
|
batteryMonitorCurrentDescription
A textual description of the battery monitor current. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.19.4.1.3 |
|
batteryMonitorCurrentTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.10.19.4.1.4 |
|
batteryMonitorCurrentAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.10.19.4.1.5 |
|
batteryMonitorCurrentValue
The measured battery current in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.4.1.6 |
|
batteryMonitorCurrentMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.4.1.7 |
|
batteryMonitorCurrentMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.4.1.8 |
|
batteryMonitorCurrentMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.4.1.9 |
|
batteryMonitorCurrentMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.4.1.10 |
batteryMonitorFuseTable
table.1.3.6.1.4.1.12148.10.10.19.5
·
1 row entry
·
6 columns
Indexes
batteryMonitorIndex batteryMonitorFuseIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryMonitorFuseIndex
This index denotes which row in the fuse table.
The size of the table is defined by the batteryMonitorNumberOfFuses |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.10.19.5.1.1 |
|
batteryMonitorFuseStatus
The status of battery fuse monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.10.19.5.1.2 |
|
batteryMonitorFuseDescription
A textual description of the battery monitor fuse. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.19.5.1.3 |
|
batteryMonitorFuseTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.10.19.5.1.4 |
|
batteryMonitorFuseAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.10.19.5.1.5 |
|
batteryMonitorFuseValue
The measured value of battery fuse in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.5.1.6 |
.1.3.6.1.4.1.12148.10.10.19.6
·
1 row entry
·
9 columns
Indexes
batteryMonitorIndex batteryMonitorSymmetryIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryMonitorSymmetryIndex
This index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries |
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.10.19.6.1.1 |
|
batteryMonitorSymmetryStatus
The status of battery symmetry monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.10.19.6.1.2 |
|
batteryMonitorSymmetryDescription
A textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.19.6.1.3 |
|
batteryMonitorSymmetryTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.10.19.6.1.4 |
|
batteryMonitorSymmetryAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.10.19.6.1.5 |
|
batteryMonitorSymmetryMeasureValue
The measured battery symmetry voltage in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.6.1.6 |
|
batteryMonitorSymmetryDeltaValue
The measured battery symmetry delta voltage in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.6.1.7 |
|
batteryMonitorSymmetryMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.6.1.8 |
|
batteryMonitorSymmetryMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.19.6.1.9 |
.1.3.6.1.4.1.12148.10.10.20.3
·
1 row entry
·
2 columns
This table contains hourly energy log of battery.
Indexes
batteryEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.20.3.1.1 |
|
batteryEnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.20.3.1.2 |
.1.3.6.1.4.1.12148.10.10.20.5
·
1 row entry
·
2 columns
This table contains daily energy log of battery.
Indexes
batteryEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.20.5.1.1 |
|
batteryEnergyLogLastDaysValue
Energy value logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.20.5.1.2 |
.1.3.6.1.4.1.12148.10.10.20.7
·
1 row entry
·
2 columns
This table contains weekly energy log of battery.
Indexes
batteryEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.20.7.1.1 |
|
batteryEnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.20.7.1.2 |
batteryCycleLogDaysTable
table.1.3.6.1.4.1.12148.10.10.21.3
·
1 row entry
·
2 columns
This table contains daily battery discharge cycle log.
Indexes
batteryCycleLogDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryCycleLogDaysIndex
Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.21.3.1.1 |
|
batteryCycleLogDaysValue
Number of discharge cycles logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.21.3.1.2 |
.1.3.6.1.4.1.12148.10.10.21.5
·
1 row entry
·
2 columns
This table contains weekly battery discharge cycle log.
Indexes
batteryCycleLogWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryCycleLogWeeksIndex
Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.21.5.1.1 |
|
batteryCycleLogWeeksValue
Number of discharge cycles logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.21.5.1.2 |
.1.3.6.1.4.1.12148.10.10.21.7
·
1 row entry
·
2 columns
This table contains monthly battery discharge cycle log.
Indexes
batteryCycleLogMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryCycleLogMonthsIndex
Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.21.7.1.1 |
|
batteryCycleLogMonthsValue
Number of discharge cycles logged every month.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.21.7.1.2 |
.1.3.6.1.4.1.12148.10.10.25.3
·
1 row entry
·
2 columns
This table contains daily battery run time log.
Indexes
batteryRunTimeLogDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryRunTimeLogDaysIndex
Index used for navigating the rows 1..52 of batteryRunTimeLogDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.25.3.1.1 |
|
batteryRunTimeLogDaysValue
Battery running minutes logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.25.3.1.2 |
.1.3.6.1.4.1.12148.10.10.25.5
·
1 row entry
·
2 columns
This table contains weekly battery run time log.
Indexes
batteryRunTimeLogWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryRunTimeLogWeeksIndex
Index used for navigating the rows 1..52 of batteryRunTimeLogWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.25.5.1.1 |
|
batteryRunTimeLogWeeksValue
Battery running hours logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.25.5.1.2 |
.1.3.6.1.4.1.12148.10.10.25.7
·
1 row entry
·
2 columns
This table contains monthly battery run time log.
Indexes
batteryRunTimeLogMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryRunTimeLogMonthsIndex
Index used for navigating the rows 1..52 of batteryRunTimeLogMonthsTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.10.25.7.1.1 |
|
batteryRunTimeLogMonthsValue
Battery running hours logged every month.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.25.7.1.2 |
batteryModuleTable
table.1.3.6.1.4.1.12148.10.10.26.4
·
1 row entry
·
20 columns
Information of individule battery module
Indexes
batteryModuleIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryModuleIndex
Index used for navigating the rows 1..100 of batteryModuleTable
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.12148.10.10.26.4.1.1 |
|
batteryModuleStatus
The status value for the battery module
|
Enumeration | .1.3.6.1.4.1.12148.10.10.26.4.1.2 |
|
batteryModuleBatteryVoltage
Battery voltage value
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.3 |
|
batteryModuleBatteryCurrent
Battery current value
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.4 |
|
batteryModuleBatteryRemCap
Battery remaining capacity value
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.5 |
|
batteryModuleBatteryTemperature
Battery temperature value
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.6 |
|
batteryModuleBatteryQuality
Battery quality value
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.7 |
|
batteryModuleMaxChargeCurrent
Maximal charging current in Amp
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.8 |
|
batteryModuleMaxDischargeCurrent
Maximal discharge current in Amp
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.9 |
|
batteryModuleBatteryMode
Battery mode
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.12148.10.10.26.4.1.10 |
|
batteryModuleChargeMode
Charge mode
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.12148.10.10.26.4.1.11 |
|
batteryModuleManufacturer
Battery manufaturer
|
OctetString Constraints: range: 0-27 |
.1.3.6.1.4.1.12148.10.10.26.4.1.12 |
|
batteryModulePartNumber
Part number
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.26.4.1.13 |
|
batteryModuleSerialNumber
Serial number
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.26.4.1.14 |
|
batteryModuleSoftwareVersion
Software version
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.10.26.4.1.15 |
|
batteryModuleProductionDate
Date of production
|
OctetString Constraints: range: 8-11 |
.1.3.6.1.4.1.12148.10.10.26.4.1.16 |
|
batteryModuleAccumulatedAhCharged
Accumulated Ah charged
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.17 |
|
batteryModuleAccumulatedAhDischarged
Accumulated Ah discharged
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.18 |
|
batteryModuleNoOfChargeCycles
Number of charge cycles
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.19 |
|
batteryModuleNoOfDischargeCycles
Number of discharge cycles
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.10.26.4.1.20 |
inputControlUnitsTable
table.1.3.6.1.4.1.12148.10.11.1
·
1 row entry
·
2 columns
Indexes
inputControlUnitIndex
| Column | Syntax | OID |
|---|---|---|
|
inputControlUnitIndex
Index used for navigating the rows of inputControlUnitTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.11.1.1.1 |
|
inputControlUnitNumberOfInputs
Number of programmable inputs available in controller.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.12148.10.11.1.1.2 |
.1.3.6.1.4.1.12148.10.11.2
·
1 row entry
·
7 columns
This table contains the status of the programmable inputs for Control Units.
Indexes
inputControlUnitIndex inputControlUnitInputIndex
| Column | Syntax | OID |
|---|---|---|
|
inputControlUnitInputIndex
Index used for navigating the rows of inputControlUnitInputTable
The size of the table is defined by the inputControlUnitNumberOfInputs |
Integer32 Constraints: range: 1-10 |
.1.3.6.1.4.1.12148.10.11.2.1.1 |
|
inputControlUnitInputStatus
Programmable input status.
|
Enumeration | .1.3.6.1.4.1.12148.10.11.2.1.2 |
|
inputControlUnitInputDescription
A textual description of the programmable input. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.11.2.1.3 |
|
inputControlUnitInputTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.11.2.1.4 |
|
inputControlUnitInputAlarmEnable
This will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state |
Enumerationr/w | .1.3.6.1.4.1.12148.10.11.2.1.5 |
|
inputControlUnitInputValue
The inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current or a Boolean value. Note: This value can only be set for virtual input on SP2 master or Smartpack S. Whe… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.11.2.1.6 |
|
inputControlUnitInputConfiguration
Configuration of the input type. Configurations available for different controllers are as follows:
SP2 Basic(normally open, normally closed); SP2 BasicInd(normally open,normally closed, temperature, temp 4-20mA, voltag… |
Enumerationr/w | .1.3.6.1.4.1.12148.10.11.2.1.7 |
inputIoUnitsTable
table.1.3.6.1.4.1.12148.10.11.3
·
1 row entry
·
2 columns
Indexes
inputIoUnitIndex
| Column | Syntax | OID |
|---|---|---|
|
inputIoUnitIndex
Index used for navigating the rows of inputIoUnitsTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.11.3.1.1 |
|
inputIoUnitNumberOfInputs
Number of programmable inputs available in IO unit.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.12148.10.11.3.1.2 |
.1.3.6.1.4.1.12148.10.11.4
·
1 row entry
·
7 columns
This table contains the status of the programmable inputs for I/O monitor units. .
Indexes
inputIoUnitIndex inputIoUnitProgInputIndex
| Column | Syntax | OID |
|---|---|---|
|
inputIoUnitProgInputIndex
The Index to the Input of the selected I/O monitor unit.
Or the input number if you like. |
Integer32 Constraints: range: 1-6 |
.1.3.6.1.4.1.12148.10.11.4.1.1 |
|
inputIoUnitProgInputStatus
Programmable input status.
|
Enumeration | .1.3.6.1.4.1.12148.10.11.4.1.2 |
|
inputIoUnitProgInputDescription
A textual description of the programmable input in IO unit. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.11.4.1.3 |
|
inputIoUnitProgInputTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.11.4.1.4 |
|
inputIoUnitProgInputAlarmEnable
This will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state |
Enumerationr/w | .1.3.6.1.4.1.12148.10.11.4.1.5 |
|
inputIoUnitProgInputValue
The inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current or a Boolean value. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.11.4.1.6 |
|
inputIoUnitProgInputConfiguration
Configuration of the input type. Configurations available for IO unit are normally open,
normally closed, diode matrix, voltage and clock. Note: If an input is set to 'clock', it can not be configurated to 'normally op… |
Enumerationr/w | .1.3.6.1.4.1.12148.10.11.4.1.7 |
outputControlUnitTable
table.1.3.6.1.4.1.12148.10.12.1
·
1 row entry
·
2 columns
Indexes
outputControlUnitIndex
| Column | Syntax | OID |
|---|---|---|
|
outputControlUnitIndex
Index used for navigating the rows of outputControlUnitTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.12.1.1.1 |
|
outputControlUnitNumberOfOutputs
Number of outputs available in controller.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.12148.10.12.1.1.2 |
.1.3.6.1.4.1.12148.10.12.2
·
1 row entry
·
3 columns
This table contains the status of the outputs for Control Units.
Indexes
outputControlUnitIndex outputControlUnitOutputIndex
| Column | Syntax | OID |
|---|---|---|
|
outputControlUnitOutputIndex
Index used for navigating the rows of outputControlUnitoutputTable
The size of the table is defined by the outputControlUnitNumberOfOutputs |
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.12.2.1.1 |
|
outputControlUnitOutputStatus
General output relays may be 'energized' or 'not energized'. 'energized' and
'not energized' correspond to normal and alarm condition respectively for normally activated configuration. Latched contactors may have val… |
Enumeration | .1.3.6.1.4.1.12148.10.12.2.1.2 |
|
outputControlUnitOutputDescription
A textual description of the output. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.12.2.1.3 |
outputIoUnitTable
table.1.3.6.1.4.1.12148.10.12.3
·
1 row entry
·
2 columns
Indexes
outputIoUnitIndex
| Column | Syntax | OID |
|---|---|---|
|
outputIoUnitIndex
Index used for navigating the rows of outputIoUnitTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.12.3.1.1 |
|
outputIoUnitNumberOfOutputs
Number of outputs available in IO unit.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.12148.10.12.3.1.2 |
outputIoUnitOutputTable
table.1.3.6.1.4.1.12148.10.12.4
·
1 row entry
·
3 columns
This table contains the status of the outputs for IO Units.
Indexes
outputIoUnitIndex outputIoUnitOutputIndex
| Column | Syntax | OID |
|---|---|---|
|
outputIoUnitOutputIndex
Index used for navigating the rows of outputIOUnitOutputTable
The size of the table is defined by the outputIOUnitNumberOfOutputs |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.12.4.1.1 |
|
outputIoUnitOutputStatus
General output relays may be 'energized' or 'not energized'.
Latched contactors may have values 'disconnected' or 'connected' |
Enumeration | .1.3.6.1.4.1.12148.10.12.4.1.2 |
|
outputIoUnitOutputDescription
A textual description of the output in IO unit. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.12.4.1.3 |
.1.3.6.1.4.1.12148.10.13.4.6
·
1 row entry
·
4 columns
This table shows the trap target address. Note that it is NOT allowed to change or create SNMP v3 trap target address IPs.
Indexes
snmpTrapsTargetAddressIndex
| Column | Syntax | OID |
|---|---|---|
| snmpTrapsTargetAddressIndex | Integer32 Constraints: range: 1-10 |
.1.3.6.1.4.1.12148.10.13.4.6.1.1 |
|
snmpTrapsTargetAddressIP
Note that it is only allowed
to change or create SNMP v2c trap target address IPs. |
OctetStringr/w Constraints: range: 1-80 |
.1.3.6.1.4.1.12148.10.13.4.6.1.2 |
| snmpTrapsTargetAddressPort | SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.4.6.1.3 |
| snmpTrapsTargetAddressVersion | Enumeration | .1.3.6.1.4.1.12148.10.13.4.6.1.4 |
.1.3.6.1.4.1.12148.10.13.7.2
·
1 row entry
·
3 columns
Indexes
controlSystemIoUnitIndex
| Column | Syntax | OID |
|---|---|---|
|
controlSystemIoUnitIndex
Index used for navigating the rows of controlSystemIoUnitTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.13.7.2.1.1 |
|
controlSystemIoUnitNumberOfTemperatures
Number of temperature measurements available in IO unit
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.13.7.2.1.2 |
|
controlSystemIoUnitNumberOfFans
Number of fan measurements available in IO unit
|
Integer32 Constraints: range: 0-4 |
.1.3.6.1.4.1.12148.10.13.7.2.1.3 |
.1.3.6.1.4.1.12148.10.13.7.3
·
1 row entry
·
10 columns
Indexes
controlSystemIoUnitIndex controlSystemIoUnitTemperatureIndex
| Column | Syntax | OID |
|---|---|---|
|
controlSystemIoUnitTemperatureIndex
Index used for navigating the rows of controlSystemIoUnitTemperatureTable
The size of the table is defined by the controlSystemIoUnitNumberOfTemperatures |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.12148.10.13.7.3.1.1 |
|
controlSystemIoUnitTemperatureStatus
The status of temperature monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.13.7.3.1.2 |
|
controlSystemIoUnitTemperatureDescription
A textual description of the temperature monitor in control system. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.13.7.3.1.3 |
|
controlSystemIoUnitTemperatureTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.13.7.3.1.4 |
|
controlSystemIoUnitTemperatureAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.13.7.3.1.5 |
|
controlSystemIoUnitTemperatureValue
The measured temperature value.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.7.3.1.6 |
|
controlSystemIoUnitTemperatureMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.7.3.1.7 |
|
controlSystemIoUnitTemperatureMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.7.3.1.8 |
|
controlSystemIoUnitTemperatureMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.7.3.1.9 |
|
controlSystemIoUnitTemperatureMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.7.3.1.10 |
.1.3.6.1.4.1.12148.10.13.7.4
·
1 row entry
·
4 columns
Indexes
controlSystemIoUnitIndex controlSystemIoUnitFanIndex
| Column | Syntax | OID |
|---|---|---|
|
controlSystemIoUnitFanIndex
Index used for navigating the rows 1..2 of ioUnitFan Table
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.12148.10.13.7.4.1.1 |
|
controlSystemIoUnitFanSpeedValue
The measured fan speed
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.7.4.1.2 |
|
controlSystemIoUnitFanSpeedDeviation
The measured fan speed deviation
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.7.4.1.3 |
|
controlSystemIoUnitFanControl
Fan speed control value in percentage
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.7.4.1.4 |
controlUnitTable
table.1.3.6.1.4.1.12148.10.13.8.2
·
1 row entry
·
8 columns
A table containing an inventory listing. Each row represent one of the system hardware unit that is connected to the can bus. These units are system controllers, battery monitors, I/O units, AC Mains Monitor boxes and load monitors. Due to the system architechture the tables index are not contiguous. Each unit type har its own address range on the can bus. All unit types except the system controller may contain from 0 to 14 units. The system controlller can never be zero. Then there is no powersystem.
One row in the table containing all hardware units connected to the canbus.
Indexes
controlUnitIndex
| Column | Syntax | OID |
|---|---|---|
|
controlUnitIndex
Index used for navigating the rows of controlUnitTable
The size of the table is defined by the controlUnitNumberOfUnits |
Integer32 Constraints: range: 1-254 |
.1.3.6.1.4.1.12148.10.13.8.2.1.1 |
|
controlUnitDescription
A textual description of the control unit
|
OctetString Constraints: range: 0-32 |
.1.3.6.1.4.1.12148.10.13.8.2.1.2 |
|
controlUnitStatus
The overall status of the control unit.
|
Enumeration | .1.3.6.1.4.1.12148.10.13.8.2.1.3 |
|
controlUnitSerialNumber
Serial number of the control unit.
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.13.8.2.1.4 |
|
controlUnitHwPartNumber
Hardware part number of the control unit.
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.13.8.2.1.5 |
|
controlUnitHwVersion
Hardware version of the control unit.
|
OctetString Constraints: range: 0-20 |
.1.3.6.1.4.1.12148.10.13.8.2.1.6 |
|
controlUnitSwPartNumber
Software part number of the control unit.
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.13.8.2.1.7 |
|
controlUnitSwVersion
Software version of the control unit.
|
OctetString Constraints: range: 0-20 |
.1.3.6.1.4.1.12148.10.13.8.2.1.8 |
currentMonitorsTable
table.1.3.6.1.4.1.12148.10.13.9.2
·
1 row entry
·
5 columns
Indexes
currentMonitorIndex
| Column | Syntax | OID |
|---|---|---|
|
currentMonitorIndex
Index used for navigating the rows of currentMonitorsTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.13.9.2.1.1 |
|
currentMonitorType
This shows if the current monitor is configured as standard load monitor (1), load current
monitor (2), rectifier current monitor (3), dcdc current monitor (4), solar current monitor (5), wind current monitor (6) or fu… |
Enumeration | .1.3.6.1.4.1.12148.10.13.9.2.1.2 |
|
currentMonitorId
This is the unit index for each current monitor type.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.2.1.3 |
|
currentMonitorNumberOfFuses
Number of fuse measurements in current monitor.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.12148.10.13.9.2.1.4 |
|
currentMonitorNumberOfCurrents
Number of current measurements in current monitor.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.12148.10.13.9.2.1.5 |
currentMonitorFuseTable
table.1.3.6.1.4.1.12148.10.13.9.3
·
1 row entry
·
6 columns
Indexes
currentMonitorIndex currentMonitorFuseIndex
| Column | Syntax | OID |
|---|---|---|
|
currentMonitorFuseIndex
Index used for navigating the rows of currentMonitorFuseTable
The size of the table is defined by the currentMonitorNumberOfFuses |
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.13.9.3.1.1 |
|
currentMonitorFuseStatus
The status of fuse in current monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.13.9.3.1.2 |
|
currentMonitorFuseDescription
A textual description of the fuse monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.13.9.3.1.3 |
|
currentMonitorFuseTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.13.9.3.1.4 |
|
currentMonitorFuseAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.13.9.3.1.5 |
|
currentMonitorFuseValue
The measured fuse value.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.3.1.6 |
.1.3.6.1.4.1.12148.10.13.9.4
·
1 row entry
·
8 columns
Indexes
currentMonitorIndex currentMonitorCurrentIndex
| Column | Syntax | OID |
|---|---|---|
|
currentMonitorCurrentIndex
Index used for navigating the rows of currentMonitorCurrentTable
The size of the table is defined by the currentMonitorNumberOfCurrents |
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.13.9.4.1.1 |
|
currentMonitorCurrentStatus
The status of current in current monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.13.9.4.1.2 |
|
currentMonitorCurrentDescription
A textual description of the current monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.13.9.4.1.3 |
|
currentMonitorCurrentTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.13.9.4.1.4 |
|
currentMonitorCurrentAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.13.9.4.1.5 |
|
currentMonitorCurrentValue
The measured current value.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.4.1.6 |
|
currentMonitorCurrentMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.4.1.7 |
|
currentMonitorCurrentMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.4.1.8 |
.1.3.6.1.4.1.12148.10.13.9.5
·
1 row entry
·
1 columns
This table contains the accumulated energy consumption measured in current monitor
Indexes
currentMonitorIndex currentMonitorCurrentIndex
| Column | Syntax | OID |
|---|---|---|
|
currentMonitorEnergyLogAccumulated
The accumulated energy consumption value
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.5.1.1 |
.1.3.6.1.4.1.12148.10.13.9.7
·
1 row entry
·
2 columns
This table contains energy consumption values logged every hour in current monitor.
Indexes
currentMonitorIndex currentMonitorCurrentIndex currentMonitorEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
currentMonitorEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.9.7.1.1 |
|
currentMonitorEnergyLogLastHoursValue
Energy consumption value logged every hour in current monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.7.1.2 |
.1.3.6.1.4.1.12148.10.13.9.9
·
1 row entry
·
2 columns
This table contains energy consumption values logged every day in current monitor.
Indexes
currentMonitorIndex currentMonitorCurrentIndex currentMonitorEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
currentMonitorEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.9.9.1.1 |
|
currentMonitorEnergyLogLastDaysValue
Energy consumption value logged every day in current monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.9.1.2 |
.1.3.6.1.4.1.12148.10.13.9.11
·
1 row entry
·
2 columns
This table contains energy consumption values logged every week in current monitor.
Indexes
currentMonitorIndex currentMonitorCurrentIndex currentMonitorEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
currentMonitorEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastWeekTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.9.11.1.1 |
|
currentMonitorEnergyLogLastWeeksValue
Energy consumption value logged every week in current monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.9.11.1.2 |
flexiMonitorsTable
table.1.3.6.1.4.1.12148.10.13.10.2
·
1 row entry
·
6 columns
Indexes
flexiMonitorIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorIndex
Index used for navigating the rows of flexiMonitorsTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.13.10.2.1.1 |
|
flexiMonitorType
This shows if the fleximonitor is configured as battery monitor (1), load
monitor (2), rectifier monitor (3), controller monitor(4), dcdc monitor (5), solar monitor (6), wind monitor (7) or fuel cell monitor 8). |
Enumeration | .1.3.6.1.4.1.12148.10.13.10.2.1.2 |
|
flexiMonitorId
This is the unit index for each fleximonitor type.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.2.1.3 |
|
flexiMonitorNumberOfInputs
Number of inputs in fleximonitor.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.12148.10.13.10.2.1.4 |
|
flexiMonitorNumberOfOutputs
Number of outputs in fleximonitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.2.1.5 |
|
flexiMonitorNumberOfCurrentInputs
Number of current inputs in fleximonitor.
|
Integer32 Constraints: range: 0-8 |
.1.3.6.1.4.1.12148.10.13.10.2.1.6 |
flexiMonitorInputTable
table.1.3.6.1.4.1.12148.10.13.10.3
·
1 row entry
·
7 columns
Indexes
flexiMonitorIndex flexiMonitorInputIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorInputIndex
Index used for navigating the rows of flexiMonitorInputTable
The size of the table is defined by the flexiMonitorNumberOfInputs |
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.13.10.3.1.1 |
|
flexiMonitorInputStatus
Programmable input status.
|
Enumeration | .1.3.6.1.4.1.12148.10.13.10.3.1.2 |
|
flexiMonitorInputDescription
A textual description of the programmable input. This is stored in the system controller
and can be changed by the user. . |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.13.10.3.1.3 |
|
flexiMonitorInputTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.13.10.3.1.4 |
|
flexiMonitorInputAlarmEnable
This will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state |
Enumerationr/w | .1.3.6.1.4.1.12148.10.13.10.3.1.5 |
|
flexiMonitorInputValue
The inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current, a Speed or a Boolean value. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.3.1.6 |
|
flexiMonitorInputConfiguration
Configuration of the input type. Available configurations are: ProgIn-Normally Open(1), ProgIn-Normally Closed(2),
Voltage(3), Temperature(4),Current(5),Speed(6),Fuse-Normally Open(7),Fuse-Normally Closed(8), Fuse-Diode… |
Enumerationr/w | .1.3.6.1.4.1.12148.10.13.10.3.1.7 |
flexiMonitorOutputTable
table.1.3.6.1.4.1.12148.10.13.10.4
·
1 row entry
·
3 columns
Indexes
flexiMonitorIndex flexiMonitorOutputIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorOutputIndex
Index used for navigating the rows of flexiMonitorOutputTable
The size of the table is defined by the flexiMonitorNumberOfOutputs |
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.13.10.4.1.1 |
|
flexiMonitorOutputStatus
General output relays may be 'energized' or 'not energized'. 'energized' and
'not energized' correspond to normal and alarm condition respectively for normally activated configuration. Latched contactors may have val… |
Enumeration | .1.3.6.1.4.1.12148.10.13.10.4.1.2 |
|
flexiMonitorOutputDescription
A textual description of the output. This is stored in the system controller
and can be changed by the user. |
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.12148.10.13.10.4.1.3 |
.1.3.6.1.4.1.12148.10.13.10.5
·
1 row entry
·
4 columns
Indexes
flexiMonitorIndex flexiMonitorCurrentInputIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorCurrentInputIndex
Index used for navigating the rows of flexiMonitorInputTable
The size of the table is defined by the flexiMonitorNumberOfInputs |
Integer32 Constraints: range: 1-16 |
.1.3.6.1.4.1.12148.10.13.10.5.1.1 |
|
flexiMonitorCurrentInputDescription
A textual description of the programmable input. This is stored in the system controller
and can be changed by the user. . |
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.13.10.5.1.2 |
|
flexiMonitorCurrentInputPricePerKW
Price per kW. To be used together with energy cost logs.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.12148.10.13.10.5.1.3 |
|
flexiMonitorCurrentInputCurrency
The currency used in energy cost logs.
|
OctetStringr/w Constraints: range: 1-6 |
.1.3.6.1.4.1.12148.10.13.10.5.1.4 |
.1.3.6.1.4.1.12148.10.13.10.7
·
1 row entry
·
4 columns
Indexes
flexiMonitorIndex flexiMonitorCurrentInputIndex flexiMonitorEnergyCostLogLastMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorEnergyCostLogLastMonthsIndex
Index used for navigating the rows 1..12
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.7.1.1 |
|
flexiMonitorEnergyCostLogLastMonthsMonth
Index by month
|
Enumeration | .1.3.6.1.4.1.12148.10.13.10.7.1.2 |
|
flexiMonitorEnergyCostLogLastMonthsEnergy
Energy in kWh
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.7.1.3 |
|
flexiMonitorEnergyCostLogLastMonthsCost
Energy cost
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.12148.10.13.10.7.1.4 |
.1.3.6.1.4.1.12148.10.13.10.9
·
1 row entry
·
4 columns
Indexes
flexiMonitorIndex flexiMonitorCurrentInputIndex flexiMonitorEnergyCostLogLastYearsIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorEnergyCostLogLastYearsIndex
Index used for navigating the rows 1..12
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.9.1.1 |
|
flexiMonitorEnergyCostLogLastYearsYear
Index by year
|
OctetString Constraints: range: 4-4 |
.1.3.6.1.4.1.12148.10.13.10.9.1.2 |
|
flexiMonitorEnergyCostLogLastYearsEnergy
Energy in kWh
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.9.1.3 |
|
flexiMonitorEnergyCostLogLastYearsCost
Energy cost
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.12148.10.13.10.9.1.4 |
.1.3.6.1.4.1.12148.10.13.10.10
·
1 row entry
·
1 columns
This table contains the accumulated energy consumption measured in fleximonitor
Indexes
flexiMonitorIndex flexiMonitorCurrentInputIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorEnergyLogAccumulated
The accumulated energy consumption value
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.10.1.1 |
.1.3.6.1.4.1.12148.10.13.10.12
·
1 row entry
·
2 columns
This table contains energy consumption values logged every hour in fleximonitor.
Indexes
flexiMonitorIndex flexiMonitorCurrentInputIndex flexiMonitorEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of flexiMonitorEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.10.12.1.1 |
|
flexiMonitorEnergyLogLastHoursValue
Energy consumption value logged every hour in fleximonitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.12.1.2 |
.1.3.6.1.4.1.12148.10.13.10.14
·
1 row entry
·
2 columns
This table contains energy consumption values logged every day in fleximonitor.
Indexes
flexiMonitorIndex flexiMonitorCurrentInputIndex flexiMonitorEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of flexiMonitorEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.10.14.1.1 |
|
flexiMonitorEnergyLogLastDaysValue
Energy consumption value logged every day in fleximonitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.14.1.2 |
.1.3.6.1.4.1.12148.10.13.10.16
·
1 row entry
·
2 columns
This table contains energy consumption values logged every week in fleximonitor.
Indexes
flexiMonitorIndex flexiMonitorCurrentInputIndex flexiMonitorEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
flexiMonitorEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of flexiMonitorEnergyLogLastWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.10.16.1.1 |
|
flexiMonitorEnergyLogLastWeeksValue
Energy consumption value logged every week in fleximonitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.10.16.1.2 |
mainControlUnitsTable
table.1.3.6.1.4.1.12148.10.13.11.1
·
1 row entry
·
2 columns
Indexes
mainControlUnitIndex
| Column | Syntax | OID |
|---|---|---|
|
mainControlUnitIndex
Index used for navigating the rows of controlUnitTable
The size of the table is defined by the system |
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.13.11.1.1.1 |
|
mainControlUnitNumberOfTemperatures
Total number of temperature measurements in main controller
|
Integer32 Constraints: range: 1-14 |
.1.3.6.1.4.1.12148.10.13.11.1.1.2 |
.1.3.6.1.4.1.12148.10.13.11.2
·
1 row entry
·
10 columns
Indexes
mainControlUnitIndex mainControlUnitTemperatureIndex
| Column | Syntax | OID |
|---|---|---|
|
mainControlUnitTemperatureIndex
This index denotes which row in the temperature input table.
The size of the table is defined by the batteryBankNumberOfTemp |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.13.11.2.1.1 |
|
mainControlUnitTemperatureStatus
The status of battery temperature monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.13.11.2.1.2 |
|
mainControlUnitTemperatureDescription
A textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.13.11.2.1.3 |
|
mainControlUnitTemperatureTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.13.11.2.1.4 |
|
mainControlUnitTemperatureAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.13.11.2.1.5 |
|
mainControlUnitTemperatureValue
The measured battery temperature.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.11.2.1.6 |
|
mainControlUnitTemperatureMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.11.2.1.7 |
|
mainControlUnitTemperatureMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.11.2.1.8 |
|
mainControlUnitTemperatureMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.11.2.1.9 |
|
mainControlUnitTemperatureMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.11.2.1.10 |
.1.3.6.1.4.1.12148.10.13.11.3
·
1 row entry
·
6 columns
Indexes
mainControlUnitIndex
| Column | Syntax | OID |
|---|---|---|
|
mainControlUnitEarthFaultStatus
This status value shows if the earth resistance is lower than the defined alarm level.
|
Enumeration | .1.3.6.1.4.1.12148.10.13.11.3.1.1 |
|
mainControlUnitEarthFaultDescription
A textual description of the earth fault monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.13.11.3.1.2 |
|
mainControlUnitEarthFaultTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.11.3.1.3 |
|
mainControlUnitEarthFaultAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.13.11.3.1.4 |
|
mainControlUnitEarthFaultValue
The measured value of the earth resistance in kOhm.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.11.3.1.5 |
|
mainControlUnitEarthFaultMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.11.3.1.6 |
.1.3.6.1.4.1.12148.10.13.24
·
1 row entry
·
4 columns
Indexes
controlSystemGenericModbusDataIndex
| Column | Syntax | OID |
|---|---|---|
|
controlSystemGenericModbusDataIndex
Index used for navigating the rows of table
The size of the table is defined by the system |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.12148.10.13.24.1.1 |
|
controlSystemGenericModbusDataDescription
description of generic Modbus data
|
OctetString Constraints: range: 0-32 |
.1.3.6.1.4.1.12148.10.13.24.1.2 |
|
controlSystemGenericModbusDataValue
Value of generic Modbus data
|
OctetString Constraints: range: 0-32 |
.1.3.6.1.4.1.12148.10.13.24.1.3 |
|
controlSystemGenericModbusDataUnit
Unit of generic Modbus data
|
OctetString Constraints: range: 0-12 |
.1.3.6.1.4.1.12148.10.13.24.1.4 |
genericAlarmMonitorTable
table.1.3.6.1.4.1.12148.10.13.26
·
1 row entry
·
7 columns
generic alarm monitors to be used with 3rd-party modbus devices
Indexes
genericAlarmMonitorIndex
| Column | Syntax | OID |
|---|---|---|
| genericAlarmMonitorIndex | Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.12148.10.13.26.1.1 |
|
genericAlarmMonitorStatus
The state of the alarm monitor can be either one of the defined enumerated values
|
Enumeration | .1.3.6.1.4.1.12148.10.13.26.1.2 |
|
genericAlarmMonitorDescription
A textual description of the generic alarm monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.13.26.1.3 |
|
genericAlarmMonitorTrapRepeatCounter
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero w… |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.13.26.1.4 |
|
genericAlarmMonitorAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.13.26.1.5 |
|
genericAlarmMonitorValue
The generic alarm monitor value. Scale is dependent on the scale setting of the corresponding generic modbus value.
|
Integer32 Constraints: range: 0-9999 |
.1.3.6.1.4.1.12148.10.13.26.1.6 |
|
genericAlarmMonitorUnit
A textual description of the unit of generic alarm monitor.
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.13.26.1.7 |
genericLogsTable
table.1.3.6.1.4.1.12148.10.13.27
·
1 row entry
·
5 columns
Generic logs connected to the last ten generic alarm monitors (#91-#100)
Indexes
genericLogsIndex
| Column | Syntax | OID |
|---|---|---|
|
genericLogsIndex
generic log index 1...10
|
Integer32 Constraints: range: 1-10 |
.1.3.6.1.4.1.12148.10.13.27.1.1 |
|
genericLogsAccumulated
This is the accumulated trip log value in hours.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.13.27.1.2 |
|
genericLogsDaysNumberOfEntries
This is the maximal number of entries stored in daily log
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.27.1.3 |
|
genericLogsWeeksNumberOfEntries
This is the maximal number of entries stored in weekly log
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.27.1.4 |
|
genericLogsMonthsNumberOfEntries
This is the maximal number of entries stored in monthly log
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.27.1.5 |
genericLogDaysTable
table.1.3.6.1.4.1.12148.10.13.28
·
1 row entry
·
2 columns
This table contains daily generic log.
Indexes
genericLogsIndex genericLogDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
genericLogDaysIndex
Index used for navigating the rows 1..52 of genericLogDaysTable
|
Unsigned32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.28.1.1 |
|
genericLogDaysValue
generic monitor value in minutes logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.28.1.2 |
genericLogWeeksTable
table.1.3.6.1.4.1.12148.10.13.29
·
1 row entry
·
2 columns
This table contains weekly generic log.
Indexes
genericLogsIndex genericLogWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
genericLogWeeksIndex
Index used for navigating the rows 1..52 of genericLogWeeksTable
|
Unsigned32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.29.1.1 |
|
genericLogWeeksValue
generic monitor value in hours logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.29.1.2 |
genericLogMonthsTable
table.1.3.6.1.4.1.12148.10.13.30
·
1 row entry
·
2 columns
This table contains monthly generic log.
Indexes
genericLogsIndex genericLogMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
genericLogMonthsIndex
Index used for navigating the rows 1..52 of genericLogMonthsTable
|
Unsigned32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.13.30.1.1 |
|
genericLogMonthsValue
generic monitor value in hours logged every month.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.13.30.1.2 |
alarmGroupTable
table.1.3.6.1.4.1.12148.10.14.1
·
1 row entry
·
3 columns
Indexes
alarmGroupIndex
| Column | Syntax | OID |
|---|---|---|
|
alarmGroupIndex
Index used for navigating the rows 1..49 of alarmGroupTable
|
Integer32 Constraints: range: 1-49 |
.1.3.6.1.4.1.12148.10.14.1.1.1 |
|
alarmGroupStatus
The status of alarm group
|
Enumeration | .1.3.6.1.4.1.12148.10.14.1.1.2 |
|
alarmGroupDescription
A textual description of the alarm group. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.14.1.1.3 |
.1.3.6.1.4.1.12148.10.15.16.4
·
1 row entry
·
9 columns
This table contains the battery test results stored in controller.
Indexes
batteryGroup2TestResultIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2TestResultIndex
A index pointing to one of ten possible battery test results
|
Integer32 Constraints: range: 1-10 |
.1.3.6.1.4.1.12148.10.15.16.4.1.1 |
|
batteryGroup2TestResultStartDateTime
This is the time and date when the test started.
|
SNMPv2-TCDateAndTime Textual Convention: SNMPv2-TCDateAndTime OctetStringType Constraints: range: 8range: 11 |
.1.3.6.1.4.1.12148.10.15.16.4.1.2 |
|
batteryGroup2TestResultDuration
This is the test duration in minutes.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.16.4.1.3 |
|
batteryGroup2TestResultDischarged
This is the discharged Ah during test.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.16.4.1.4 |
|
batteryGroup2TestResultQuality
This is the calculated battery quality (SoH)in percentage.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.16.4.1.5 |
|
batteryGroup2TestResultEndVoltage
This is the test end voltage in volt.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.16.4.1.6 |
|
batteryGroup2TestResultTestResult
This is the test result.
|
Enumeration | .1.3.6.1.4.1.12148.10.15.16.4.1.7 |
|
batteryGroup2TestResultTerminationCriteria
This is the test Termination Criteria.
|
Enumeration | .1.3.6.1.4.1.12148.10.15.16.4.1.8 |
|
batteryGroup2TestResultBatteryTemperature
This is the battery temperature
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.16.4.1.9 |
.1.3.6.1.4.1.12148.10.15.18.6
·
1 row entry
·
10 columns
Indexes
batteryGroup2TemperatureIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2TemperatureIndex
This index denotes which row in the temperature input table.
The size of the table is defined by the batteryGroup2BankNumberOfTemperatures |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.15.18.6.1.1 |
|
batteryGroup2TemperatureStatus
The status of battery temperature monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.15.18.6.1.2 |
|
batteryGroup2TemperatureDescription
A textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.15.18.6.1.3 |
|
batteryGroup2TemperatureTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.15.18.6.1.4 |
|
batteryGroup2TemperatureAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.15.18.6.1.5 |
|
batteryGroup2TemperatureValue
The measured battery temperature.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.6.1.6 |
|
batteryGroup2TemperatureMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.6.1.7 |
|
batteryGroup2TemperatureMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.6.1.8 |
|
batteryGroup2TemperatureMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.6.1.9 |
|
batteryGroup2TemperatureMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.6.1.10 |
.1.3.6.1.4.1.12148.10.15.18.7
·
1 row entry
·
10 columns
Indexes
batteryGroup2CurrentIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2CurrentIndex
This index denotes which row in the current input table.
The size of the table is defined by the system |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.15.18.7.1.1 |
|
batteryGroup2CurrentStatus
The status of battery current monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.15.18.7.1.2 |
|
batteryGroup2CurrentDescription
A textual description of the battery current monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.15.18.7.1.3 |
|
batteryGroup2CurrentTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.15.18.7.1.4 |
|
batteryGroup2CurrentAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.15.18.7.1.5 |
|
batteryGroup2CurrentValue
The measured battery current
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.7.1.6 |
|
batteryGroup2CurrentMajorHighLevel
The major high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.7.1.7 |
|
batteryGroup2CurrentMinorHighLevel
The minor high alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.7.1.8 |
|
batteryGroup2CurrentMinorLowLevel
The minor low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.7.1.9 |
|
batteryGroup2CurrentMajorLowLevel
The major low alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.7.1.10 |
.1.3.6.1.4.1.12148.10.15.18.8
·
1 row entry
·
6 columns
Indexes
batteryGroup2FuseIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2FuseIndex
This index denotes which row in the fuse table.
The size of the table is defined by the system |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.12148.10.15.18.8.1.1 |
|
batteryGroup2FuseStatus
The status of battery fuse monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.15.18.8.1.2 |
|
batteryGroup2FuseDescription
A textual description of the battery fuse monitor. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.15.18.8.1.3 |
|
batteryGroup2FuseTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.15.18.8.1.4 |
|
batteryGroup2FuseAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.15.18.8.1.5 |
|
batteryGroup2FuseValue
The measured value of battery fuse input.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.8.1.6 |
.1.3.6.1.4.1.12148.10.15.18.9
·
1 row entry
·
9 columns
Indexes
batteryGroup2BankSymmetryIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2BankSymmetryIndex
This index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries |
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.12148.10.15.18.9.1.1 |
|
batteryGroup2BankSymmetryStatus
The status of battery symmetry monitor
|
Enumeration | .1.3.6.1.4.1.12148.10.15.18.9.1.2 |
|
batteryGroup2BankSymmetryDescription
A textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user. |
OctetStringr/w Constraints: range: 0-16 |
.1.3.6.1.4.1.12148.10.15.18.9.1.3 |
|
batteryGroup2BankSymmetryTrapRepeatCounter
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated. The counter is automatically set to zero … |
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.12148.10.15.18.9.1.4 |
|
batteryGroup2BankSymmetryAlarmEnable
This value once enabled, the alarm condition of the monitor will be reported.
|
Enumerationr/w | .1.3.6.1.4.1.12148.10.15.18.9.1.5 |
|
batteryGroup2BankSymmetryMeasureValue
The measured battery symmetry voltage in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.9.1.6 |
|
batteryGroup2BankSymmetryDeltaValue
The measured battery symmetry delta voltage in battery monitor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.9.1.7 |
|
batteryGroup2BankSymmetryMajorAlarmLevel
The major alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.9.1.8 |
|
batteryGroup2BankSymmetryMinorAlarmLevel
The minor alarm limit
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.18.9.1.9 |
.1.3.6.1.4.1.12148.10.15.19.3
·
1 row entry
·
2 columns
This table contains hourly energy log of battery.
Indexes
batteryGroup2EnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2EnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.15.19.3.1.1 |
|
batteryGroup2EnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.19.3.1.2 |
.1.3.6.1.4.1.12148.10.15.19.5
·
1 row entry
·
2 columns
This table contains daily energy log of battery.
Indexes
batteryGroup2EnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2EnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.15.19.5.1.1 |
|
batteryGroup2EnergyLogLastDaysValue
Energy value logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.19.5.1.2 |
.1.3.6.1.4.1.12148.10.15.19.7
·
1 row entry
·
2 columns
This table contains weekly energy log of battery.
Indexes
batteryGroup2EnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2EnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.15.19.7.1.1 |
|
batteryGroup2EnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.19.7.1.2 |
.1.3.6.1.4.1.12148.10.15.20.3
·
1 row entry
·
2 columns
This table contains daily battery discharge cycle log.
Indexes
batteryGroup2CycleLogDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2CycleLogDaysIndex
Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.15.20.3.1.1 |
|
batteryGroup2CycleLogDaysValue
Number of discharge cycles logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.20.3.1.2 |
.1.3.6.1.4.1.12148.10.15.20.5
·
1 row entry
·
2 columns
This table contains weekly battery discharge cycle log.
Indexes
batteryGroup2CycleLogWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2CycleLogWeeksIndex
Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.15.20.5.1.1 |
|
batteryGroup2CycleLogWeeksValue
Number of discharge cycles logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.20.5.1.2 |
.1.3.6.1.4.1.12148.10.15.20.7
·
1 row entry
·
2 columns
This table contains monthly battery discharge cycle log.
Indexes
batteryGroup2CycleLogMonthsIndex
| Column | Syntax | OID |
|---|---|---|
|
batteryGroup2CycleLogMonthsIndex
Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.15.20.7.1.1 |
|
batteryGroup2CycleLogMonthsValue
Number of discharge cycles logged every month.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.15.20.7.1.2 |
fuelCellTable
table.1.3.6.1.4.1.12148.10.19.6
·
1 row entry
·
26 columns
This table shows the information of each fuel cell installed in the system.
Indexes
fuelCellIndex
| Column | Syntax | OID |
|---|---|---|
|
fuelCellIndex
Index used for navigating the rows 1..100 of fuelCellTable
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.12148.10.19.6.1.1 |
|
fuelCellStatus
The overall status of fuel cell.
|
Enumeration | .1.3.6.1.4.1.12148.10.19.6.1.2 |
|
fuelCellMode
The mode value of fuel cell.
|
Enumeration | .1.3.6.1.4.1.12148.10.19.6.1.3 |
|
fuelCellCurrentValue
The output current value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.4 |
|
fuelCellVoltageValue
The input voltage value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.5 |
|
fuelCellPowerValue
The input voltage value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.6 |
|
fuelCellType
Type of fuel cell
|
OctetString Constraints: range: 0-27 |
.1.3.6.1.4.1.12148.10.19.6.1.7 |
|
fuelCellInletTemperature
The inlet temp value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.8 |
|
fuelCellOutletTemperature
The outlet temp value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.9 |
|
fuelCellRoomTemperature
The room temp value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.10 |
|
fuelCellFan
The fan value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.11 |
|
fuelCellH2Storage1
The H2 storage 1 value of fuel cell.
|
Enumeration | .1.3.6.1.4.1.12148.10.19.6.1.12 |
|
fuelCellH2Storage2
The H2 storage 2 value of fuel cell.
|
Enumeration | .1.3.6.1.4.1.12148.10.19.6.1.13 |
|
fuelCellH2Storage3
The H2 storage 3 value of fuel cell.
|
Enumeration | .1.3.6.1.4.1.12148.10.19.6.1.14 |
|
fuelCellDO22
The DO22 value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.15 |
|
fuelCellDO23
The DO23 value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.16 |
|
fuelCellDO24
The DO24 value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.17 |
|
fuelCellDO25
The DO25 value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.18 |
|
fuelCellDO26
The DO26 value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.19 |
|
fuelCellDO27
The DO27 value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.20 |
|
fuelCellDC1current
The DC1 current value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.21 |
|
fuelCellDC2current
The DC2 current value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.22 |
|
fuelCellDC3current
The DC3 current value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.23 |
|
fuelCellDC4current
The DC4 current value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.24 |
|
fuelCellDC5current
The DC5 current value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.25 |
|
fuelCellDC6current
The DC6 current value of fuel cell.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.6.1.26 |
.1.3.6.1.4.1.12148.10.19.7.3
·
1 row entry
·
2 columns
This table contains hourly energy log of fuel cell.
Indexes
fuelCellsEnergyLogLastHoursIndex
| Column | Syntax | OID |
|---|---|---|
|
fuelCellsEnergyLogLastHoursIndex
Index used for navigating the rows 1..52 of fuelCellsEnergyLogLastHoursTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.19.7.3.1.1 |
|
fuelCellsEnergyLogLastHoursValue
Energy value logged every hour.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.7.3.1.2 |
.1.3.6.1.4.1.12148.10.19.7.5
·
1 row entry
·
2 columns
This table contains daily energy log of fuel cell.
Indexes
fuelCellsEnergyLogLastDaysIndex
| Column | Syntax | OID |
|---|---|---|
|
fuelCellsEnergyLogLastDaysIndex
Index used for navigating the rows 1..52 of fuelCellsEnergyLogLastDaysTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.19.7.5.1.1 |
|
fuelCellsEnergyLogLastDaysValue
Energy value logged every day.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.12148.10.19.7.5.1.2 |
.1.3.6.1.4.1.12148.10.19.7.7
·
1 row entry
·
2 columns
This table contains weekly energy log of fuel cell.
Indexes
fuelCellsEnergyLogLastWeeksIndex
| Column | Syntax | OID |
|---|---|---|
|
fuelCellsEnergyLogLastWeeksIndex
Index used for navigating the rows 1..52 of fuelCellsEnergyLogLastWeekTable
|
Integer32 Constraints: range: 1-52 |
.1.3.6.1.4.1.12148.10.19.7.7.1.1 |
|
fuelCellsEnergyLogLastWeeksValue
Energy value logged every week.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |