SOCOMECUPS-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
11
Rows
11
Columns
51
.1.3.6.1.4.1.4555.1.1.1.1.3.3
·
1 row entry
·
5 columns
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
An entry containing information applicable to a
particular input line.
particular input line.
Indexes
upsInputLineIndex
| Column | Syntax | OID |
|---|---|---|
| upsInputLineIndex mandatory | Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1 |
|
upsInputVoltage
mandatory
The input utility line voltage in 0.1 volts.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2 |
|
upsInputCurrent
mandatory
The magnitude of the present input current in 0.1 A.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3 |
|
upsInputVoltageMax
mandatory
The maximum utility line voltage in 0.1 VAC for last 1 minute.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4 |
|
upsInputVoltageMin
mandatory
The minimum utility line voltage in 0.1 VAC for last 1 minute.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5 |
.1.3.6.1.4.1.4555.1.1.1.1.4.4
·
1 row entry
·
5 columns
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.
An entry containing information applicable to a
particular output line.
particular output line.
Indexes
upsOutputLineIndex
| Column | Syntax | OID |
|---|---|---|
|
upsOutputLineIndex
mandatory
The output line identifier.
|
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1 |
|
upsOutputVoltage
mandatory
The output voltage of the UPS system in 0.1 volts.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2 |
|
upsOutputCurrent
mandatory
The output current of the UPS system in 0.1 Amps.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3 |
|
upsOutputPercentLoad
mandatory
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4 |
|
upsOutputKva
mandatory
Output apparent power of the UPS in kVA.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.4.4.1.5 |
.1.3.6.1.4.1.4555.1.1.1.1.5.3
·
1 row entry
·
3 columns
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
An entry containing information applicable to a
particular bypass input.
particular bypass input.
Indexes
upsBypassLineIndex
| Column | Syntax | OID |
|---|---|---|
|
upsBypassLineIndex
mandatory
The bypass line identifier.
|
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1 |
|
upsBypassVoltage
mandatory
The present bypass voltage of the UPS system in 0.1 volts.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2 |
|
upsBypassCurrent
mandatory
The present bypass current of the UPS system in 0.1 Amps.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3 |
.1.3.6.1.4.1.4555.1.1.1.1.6.2
·
1 row entry
·
4 columns
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an OBJECT IDENTIFIER,
upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent.
An entry containing information applicable to a
particular alarm.
particular alarm.
Indexes
upsAlarmId
| Column | Syntax | OID |
|---|---|---|
|
upsAlarmId
mandatory
A unique identifier for an alarm condition. This
value must remain constant. |
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1.1 |
|
upsAlarmDescr
mandatory
A reference to an alarm description object. The
object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. |
SNMPv2-TCAutonomousType Textual Convention: SNMPv2-TCAutonomousType ObjectIdentifier |
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1.2 |
|
upsAlarmTime
mandatory
The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0. |
SNMPv2-TCTimeStamp Textual Convention: SNMPv2-TCTimeStamp Unsigned32 |
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1.3 |
|
upsAlarmExtDes
mandatory
Extra description.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.4555.1.1.1.1.6.2.1.4 |
.1.3.6.1.4.1.4555.1.1.1.1.8.4
·
1 row entry
·
5 columns
Table which describes the parametes for shutdown process when shutdown event occurs
Indexes
upsControlEventDescr
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
upsControlEventDescr
mandatory
The shutdown event identification
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.1 |
||||
|
upsControlEventStatus
mandatory
Status of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when corresponding event occured. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.2 |
||||
|
upsControlDelay
mandatory
The Delay after the occurance of the curresponding shutdown
event that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutdown and SpecialScheduledShutdown, this is the time before the… |
Integer32r/w Constraints: range: 0-32767 |
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.3 |
||||
|
upsControlFirstWarning
mandatory
The delay after the occurance of the curresponding shutdown
event that the Net Vision will start sending the warning message to the connected clients. The value is in units of seconds |
Integer32r/w Constraints: range: 0-32767 |
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.4 |
||||
|
upsControlWarningInterval
mandatory
The frequency of sending warning messages to the connected
clients when the curresponding shutdown event occurs. The value is in units of seconds. |
Integer32r/w Constraints: range: 0-32767 |
.1.3.6.1.4.1.4555.1.1.1.1.8.4.1.5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.5
·
1 row entry
·
5 columns
The table to schedule shutting down the ups by weekly.
The entries for each day.
Indexes
upsControlWeeklyIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsControlWeeklyIndex
mandatory
The index of scheduled events.
|
Integer32 Constraints: range: 1-7 |
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.1 |
||||||||||||||||
|
upsControlWeeklyShutdownDay
mandatory
The weekday on which the UPS should shut down.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.2 |
||||||||||||||||
|
upsControlWeeklyShutdownTime
mandatory
The time that the process of shutting down the UPS will be initiated
in hh:mm:ss format. |
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.3 |
||||||||||||||||
|
upsControlWeeklyRestartDay
mandatory
The weekday on which the UPS should restart
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.4 |
||||||||||||||||
|
upsControlWeeklyRestartTime
mandatory
The time the UPS will restart in hh:mm:ss format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.5.1.5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.6
·
1 row entry
·
5 columns
The table to schedule shutting down the ups.
The entries for each day.
Indexes
upsControlSpecialIndex
| Column | Syntax | OID |
|---|---|---|
|
upsControlSpecialIndex
mandatory
The index of scheduled events.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.1 |
|
upsControlSpecialShutdownDay
mandatory
The date on which the UPS should shut down in dd/mm/yyyy
format. |
OctetStringr/w Constraints: range: 10-10 |
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.2 |
|
upsControlSpecialShutdownTime
mandatory
The time that the process of shutting down the UPS will be initiated
in hh:mm:ss format |
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.3 |
|
upsControlSpecialRestartDay
mandatory
The date on which the UPS should restart in dd/mm/yyyy format
|
OctetStringr/w Constraints: range: 10-10 |
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.4 |
|
upsControlSpecialRestartTime
mandatory
The time the UPS will restart in hh:mm:ss format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.6.1.5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.7
·
1 row entry
·
5 columns
The table to schedule enable/disable ups eco/mode by weekly.
The entries for each day.
Indexes
upsControlEcoModeIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsControlEcoModeIndex
mandatory
The index of scheduled events.
|
Integer32 Constraints: range: 1-7 |
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.1 |
||||||||||||||||
|
upsControlEcoModeStartDay
mandatory
The weekday on which the UPS Eco/Mode should enable.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.2 |
||||||||||||||||
|
upsControlEcoModeStartTime
mandatory
The time that the UPS Eco/Mode will be enabled, in hh:mm:ss format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.3 |
||||||||||||||||
|
upsControlEcoModeEndDay
mandatory
The weekday on which the UPS Eco/Mode should disable
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.4 |
||||||||||||||||
|
upsControlEcoModeEndTime
mandatory
The time the UPS Eco/Mode will disabled, in hh:mm:ss format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.4555.1.1.1.1.8.7.1.5 |
.1.3.6.1.4.1.4555.1.1.1.1.9.5
·
1 row entry
·
6 columns
The devices powered by UPS and registered to Net Vision
The devices protected by Net Vision
Indexes
indexOfDevice
| Column | Syntax | OID |
|---|---|---|
|
indexOfDevice
mandatory
The index of the device that is plugged into the UPS.
|
Integer32 Constraints: range: 1-255 |
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.1 |
|
addrOfDevice
mandatory
The ip address of the device.
|
SNMPv2-SMIIpAddress Textual Convention: SNMPv2-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.2 |
|
nameOfDevice
mandatory
The name/description of the device plugged into the UPS.
|
OctetString Constraints: range: 0-31 |
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.3 |
|
timeOfConnection
mandatory
The that device registered to Net Vision
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.4 |
|
statusOfConnection
mandatory
status
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.5 |
|
severityOfConnection
mandatory
severity
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.9.5.1.6 |
.1.3.6.1.4.1.4555.1.1.1.1.10.21
·
1 row entry
·
4 columns
A list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers
The managers to send traps to.
Indexes
trapsIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
trapsIndex
mandatory
The index to a trap receiver entry.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1.1 |
||||||
|
trapsReceiverAddr
mandatory
The IP address of the manager to send a trap to.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1.2 |
||||||
|
receiverCommunityString
mandatory
The community name to use in the trap when sent to the manager.
|
OctetStringr/w Constraints: range: 0-15 |
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1.3 |
||||||
|
receiverNmstype
mandatory
The trap group that NMS desired.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.4555.1.1.1.1.10.21.1.4 |
.1.3.6.1.4.1.4555.1.1.1.1.10.22
·
1 row entry
·
4 columns
A list of managers which can access Net Vision with private community string.
The managers.
Indexes
trapsIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
accessIndex
mandatory
The index to a access control entry.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1.1 |
||||||
|
accessControlAddr
mandatory
The IP address of the manager to access Net Vision
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1.2 |
||||||
|
accessCommunityString
mandatory
The community name to use in the manager when
access Net Vision |
OctetStringr/w Constraints: range: 0-15 |
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1.3 |
||||||
|
accessControlMode
mandatory
Access type, only read-Write access type can change parameter
of Net Vision |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.4555.1.1.1.1.10.22.1.4 |