NetBotz50-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
28
Rows
28
Columns
243
enclosureTable
table.1.3.6.1.4.1.52674.500.2.1
·
1 row entry
·
7 columns
A list of enclosures (base enclosure and pods).
Enclosure entry.
Indexes
enclosureIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
enclosureId
The id of the physical enclosure.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.2.1.1.1 |
||||||||||||
|
enclosureStatus
The operational status of the enclosure.
|
OperStatus Textual Convention: OperStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.2.1.1.2 |
||||||||||||
|
enclosureErrorStatus
The error status of the enclosure. If there are no error conditions
reported for the enclosure, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.2.1.1.3 |
||||||||||||
|
enclosureLabel
The unique label assigned to the enclosure (or pod).
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.2.1.1.4 |
||||||||||||
|
enclosureParentEncId
The id of the parent enclosure this enclosure is attached to.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.2.1.1.5 |
||||||||||||
|
enclosureSerialNumber
The serial number of this enclosure.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.2.1.1.6 |
||||||||||||
|
enclosureIndex
The index of the physical enclosure.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.2.1.1.7 |
alinkSensorCountTable
table.1.3.6.1.4.1.52674.500.2.2.1
·
1 row entry
·
7 columns
A count of alink-related sensors.
A count-of-sensors entry.
Indexes
alinkSensorCountIndex
| Column | Syntax | OID |
|---|---|---|
|
alinkSensorCountId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.2.2.1.1.1 |
|
alinkSensorCountValue
The number of known connected sensors.
|
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.52674.500.2.2.1.1.2 |
|
alinkSensorCountLabel
The unique label assigned to the sensor count.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.2.2.1.1.3 |
|
alinkSensorCountEncId
The id of the physical enclosure represented by the sensor count.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.2.2.1.1.4 |
|
alinkSensorCountValueStr
The sensor count value shown as a string.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.2.2.1.1.5 |
|
alinkSensorCountValueInt
The sensor count as integer value.
|
Integer32 Constraints: range: 0-6554 |
.1.3.6.1.4.1.52674.500.2.2.1.1.6 |
|
alinkSensorCountIndex
The index of the sensor counter.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.2.2.1.1.7 |
otherPortTable
table.1.3.6.1.4.1.52674.500.3.10
·
1 row entry
·
5 columns
A list of other port entries.
Other port entry.
Indexes
otherPortIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
otherPortId
The unique id of the port.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.3.10.1.1 |
||||||
|
otherPortStatus
The operational status of the port.
|
OperStatus Textual Convention: OperStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.3.10.1.2 |
||||||
|
otherPortLabel
The unique label assigned to the port.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.3.10.1.3 |
||||||
|
otherPortEncId
The id of the physical enclosure containing the port.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.3.10.1.4 |
||||||
|
otherPortIndex
The index of the port.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.3.10.1.5 |
tempSensorTable
table.1.3.6.1.4.1.52674.500.4.1.1
·
1 row entry
·
10 columns
A list of temperature sensor entries.
A temperature sensor entry.
Indexes
tempSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
tempSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.1.1.1 |
||||||||||||
|
tempSensorValue
The temperature measured by the sensor in tenths of a degree Celsius.
|
Integer32 Constraints: range: -500-1000 |
.1.3.6.1.4.1.52674.500.4.1.1.1.2 |
||||||||||||
|
tempSensorErrorStatus
The error status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is n… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.1.1.3 |
||||||||||||
|
tempSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.1.1.4 |
||||||||||||
|
tempSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.1.1.5 |
||||||||||||
|
tempSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.1.1.6 |
||||||||||||
|
tempSensorValueStr
The temperature reading, in degrees celsius, shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.1.1.7 |
||||||||||||
|
tempSensorValueInt
The temperature measured by the sensor in degree Celsius.
|
Integer32 Constraints: range: -50-100 |
.1.3.6.1.4.1.52674.500.4.1.1.1.8 |
||||||||||||
|
tempSensorValueIntF
The temperature measured by the sensor in degree Farenheit.
|
Integer32 Constraints: range: -50-212 |
.1.3.6.1.4.1.52674.500.4.1.1.1.9 |
||||||||||||
|
tempSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.1.1.10 |
humiSensorTable
table.1.3.6.1.4.1.52674.500.4.1.2
·
1 row entry
·
9 columns
A list of humidity sensor entries.
A humidity sensor entry.
Indexes
humiSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
humiSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.2.1.1 |
||||||||||||
|
humiSensorValue
The relative humidity measured by the sensor in tenths of a percent.
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.52674.500.4.1.2.1.2 |
||||||||||||
|
humiSensorErrorStatus
The error status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is n… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.2.1.3 |
||||||||||||
|
humiSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.2.1.4 |
||||||||||||
|
humiSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.2.1.5 |
||||||||||||
|
humiSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.2.1.6 |
||||||||||||
|
humiSensorValueStr
The humidity reading, in percent, shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.2.1.7 |
||||||||||||
|
humiSensorValueInt
The relative humidity measured by the sensor in percent.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.52674.500.4.1.2.1.8 |
||||||||||||
|
humiSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.2.1.9 |
dewPointSensorTable
table.1.3.6.1.4.1.52674.500.4.1.3
·
1 row entry
·
10 columns
A list of dew point sensor entries.
A dew point sensor entry.
Indexes
dewPointSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
dewPointSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.3.1.1 |
||||||||||||
|
dewPointSensorValue
The dew point value measured by the sensor in tenths of a degree Celsius.
|
Integer32 Constraints: range: -500-1000 |
.1.3.6.1.4.1.52674.500.4.1.3.1.2 |
||||||||||||
|
dewPointSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.3.1.3 |
||||||||||||
|
dewPointSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.3.1.4 |
||||||||||||
|
dewPointSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.3.1.5 |
||||||||||||
|
dewPointSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.3.1.6 |
||||||||||||
|
dewPointSensorValueStr
The dew point reading, in degrees celsius, shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.3.1.7 |
||||||||||||
|
dewPointSensorValueInt
The dew point value measured by the sensor in degrees Celsius.
|
Integer32 Constraints: range: -50-100 |
.1.3.6.1.4.1.52674.500.4.1.3.1.8 |
||||||||||||
|
dewPointSensorValueIntF
The dew point reading in degrees Farenheit, measured by the sensor.
|
Integer32 Constraints: range: -40-122 |
.1.3.6.1.4.1.52674.500.4.1.3.1.9 |
||||||||||||
|
dewPointSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.3.1.10 |
airFlowSensorTable
table.1.3.6.1.4.1.52674.500.4.1.5
·
1 row entry
·
9 columns
A list of airflow sensor entries.
An air flow sensor entry.
Indexes
airFlowSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
airFlowSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.5.1.1 |
||||||||||||
|
airFlowSensorValue
The air flow measured by the sensor in tenths of a meter per minute.
|
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.52674.500.4.1.5.1.2 |
||||||||||||
|
airFlowSensorErrorStatus
The error status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is n… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.5.1.3 |
||||||||||||
|
airFlowSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.5.1.4 |
||||||||||||
|
airFlowSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.5.1.5 |
||||||||||||
|
airFlowSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.5.1.6 |
||||||||||||
|
airFlowSensorValueStr
The airflow reading, in meters per minute, shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.5.1.7 |
||||||||||||
|
airFlowSensorValueInt
The air flow measured by the sensor in meters per minute.
|
Integer32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.52674.500.4.1.5.1.8 |
||||||||||||
|
airFlowSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.5.1.9 |
ampDetectSensorTable
table.1.3.6.1.4.1.52674.500.4.1.6
·
1 row entry
·
9 columns
A list of amp detect sensor entries.
An ampere sensor entry.
Indexes
ampDetectSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
ampDetectSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.6.1.1 |
||||||||||||
|
ampDetectSensorValue
The value measured by the sensor in tenths of an ampere.
|
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.52674.500.4.1.6.1.2 |
||||||||||||
|
ampDetectSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.6.1.3 |
||||||||||||
|
ampDetectSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.6.1.4 |
||||||||||||
|
ampDetectSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.6.1.5 |
||||||||||||
|
ampDetectSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.6.1.6 |
||||||||||||
|
ampDetectSensorValueStr
The amp detect reading, in amperes, shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.6.1.7 |
||||||||||||
|
ampDetectSensorValueInt
The value measured by the sensor in amperes.
|
Integer32 Constraints: range: 0-6554 |
.1.3.6.1.4.1.52674.500.4.1.6.1.8 |
||||||||||||
|
ampDetectSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.6.1.9 |
otherNumericSensorTable
table.1.3.6.1.4.1.52674.500.4.1.10
·
1 row entry
·
12 columns
A list of other numeric sensor entries.
Other numeric sensor entry.
Indexes
otherNumericSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
otherNumericSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.10.1.1 |
||||||||||||
|
otherNumericSensorValue
The value measured by the sensor in tenths of the unit of measure.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.10.1.2 |
||||||||||||
|
otherNumericSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.10.1.3 |
||||||||||||
|
otherNumericSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.10.1.4 |
||||||||||||
|
otherNumericSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.10.1.5 |
||||||||||||
|
otherNumericSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.10.1.6 |
||||||||||||
|
otherNumericSensorValueStr
The sensor reading shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.10.1.7 |
||||||||||||
|
otherNumericSensorValueInt
The value measured by the sensor in the unit of measure (1/10 of otherNumericSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.10.1.8 |
||||||||||||
|
otherNumericSensorUnits
The unit of measure for the sensor value.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.10.1.9 |
||||||||||||
|
otherNumericSensorValueIntX1000
The value measured by the sensor in thousandths of the unit of measure (100 times otherNumericSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.10.1.10 |
||||||||||||
|
otherNumericSensorValueIntX1000000
The value measured by the sensor in millionths of the unit of measure (100000 times otherNumericSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.10.1.11 |
||||||||||||
|
otherNumericSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.10.1.12 |
rssiSensorTable
table.1.3.6.1.4.1.52674.500.4.1.11
·
1 row entry
·
10 columns
A list of wireless network RSSI entries.
RSSI sensor entry.
Indexes
rssiSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
rssiSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.11.1.1 |
||||||||||||
|
rssiSensorValue
The value measured by the sensor in tenths of the unit of measure.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.11.1.2 |
||||||||||||
|
rssiSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.11.1.3 |
||||||||||||
|
rssiSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.11.1.4 |
||||||||||||
|
rssiSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.11.1.5 |
||||||||||||
|
rssiSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.11.1.6 |
||||||||||||
|
rssiSensorValueStr
The sensor reading shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.11.1.7 |
||||||||||||
|
rssiSensorValueInt
The value measured by the sensor in the unit of measure (1/10 of rssiSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.11.1.8 |
||||||||||||
|
rssiSensorUnits
The unit of measure for the sensor value.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.11.1.9 |
||||||||||||
|
rssiSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.11.1.10 |
currentInputSensorTable
table.1.3.6.1.4.1.52674.500.4.1.12
·
1 row entry
·
12 columns
A list of current input sensor entries.
Current Input sensor entry.
Indexes
currentInputSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
currentInputSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.12.1.1 |
||||||||||||
|
currentInputSensorValue
The value measured by the sensor in tenths of the unit of measure.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.12.1.2 |
||||||||||||
|
currentInputSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.12.1.3 |
||||||||||||
|
currentInputSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.12.1.4 |
||||||||||||
|
currentInputSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.12.1.5 |
||||||||||||
|
currentInputSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.12.1.6 |
||||||||||||
|
currentInputSensorValueStr
The sensor reading shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.12.1.7 |
||||||||||||
|
currentInputSensorValueInt
The value measured by the sensor in the unit of measure (1/10 of currentInputSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.12.1.8 |
||||||||||||
|
currentInputSensorUnits
The unit of measure for the sensor value.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.12.1.9 |
||||||||||||
|
currentInputSensorValueIntX1000
The value measured by the sensor in thousandths of the unit of measure (100 times currentInputSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.12.1.10 |
||||||||||||
|
currentInputSensorValueIntX1000000
The value measured by the sensor in millionths of the unit of measure (100000 times currentInputSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.12.1.11 |
||||||||||||
|
currentInputSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.12.1.12 |
voltageSensorTable
table.1.3.6.1.4.1.52674.500.4.1.13
·
1 row entry
·
12 columns
A list of current input sensor entries.
Voltage sensor entry.
Indexes
voltageSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
voltageSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.13.1.1 |
||||||||||||
|
voltageSensorValue
The value measured by the sensor in tenths of the unit of measure.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.13.1.2 |
||||||||||||
|
voltageSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.13.1.3 |
||||||||||||
|
voltageSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.13.1.4 |
||||||||||||
|
voltageSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.13.1.5 |
||||||||||||
|
voltageSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.13.1.6 |
||||||||||||
|
voltageSensorValueStr
The sensor reading shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.13.1.7 |
||||||||||||
|
voltageSensorValueInt
The value measured by the sensor in the unit of measure (1/10 of voltageSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.13.1.8 |
||||||||||||
|
voltageSensorUnits
The unit of measure for the sensor value.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.13.1.9 |
||||||||||||
|
voltageSensorValueIntX1000
The value measured by the sensor in thousandths of the unit of measure (100 times voltageSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.13.1.10 |
||||||||||||
|
voltageSensorValueIntX1000000
The value measured by the sensor in millionths of the unit of measure (100000 times voltageSensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.13.1.11 |
||||||||||||
|
voltageSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.13.1.12 |
batterySensorTable
table.1.3.6.1.4.1.52674.500.4.1.14
·
1 row entry
·
12 columns
A list of current input sensor entries.
Battery sensor entry.
Indexes
batterySensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
batterySensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.14.1.1 |
||||||||||||
|
batterySensorValue
The value measured by the sensor in tenths of the unit of measure.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.14.1.2 |
||||||||||||
|
batterySensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.1.14.1.3 |
||||||||||||
|
batterySensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.14.1.4 |
||||||||||||
|
batterySensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.14.1.5 |
||||||||||||
|
batterySensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.1.14.1.6 |
||||||||||||
|
batterySensorValueStr
The sensor reading shown as a string (or empty string
if it is not plugged into a port). |
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.14.1.7 |
||||||||||||
|
batterySensorValueInt
The value measured by the sensor in the unit of measure (1/10 of batterySensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.14.1.8 |
||||||||||||
|
batterySensorUnits
The unit of measure for the sensor value.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.1.14.1.9 |
||||||||||||
|
batterySensorValueIntX1000
The value measured by the sensor in thousandths of the unit of measure (100 times batterySensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.14.1.10 |
||||||||||||
|
batterySensorValueIntX1000000
The value measured by the sensor in millionths of the unit of measure (100000 times batterySensorValue)
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.1.14.1.11 |
||||||||||||
|
batterySensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.1.14.1.12 |
dryContactSensorTable
table.1.3.6.1.4.1.52674.500.4.2.1
·
1 row entry
·
8 columns
A list of dry contact sensor entries.
Dry contact sensor entry.
Indexes
dryContactSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
dryContactSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.1.1.1 |
||||||||||||
|
dryContactSensorValue
Whether the dry sensor contact is open or closed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.1.1.2 |
||||||||||||
|
dryContactSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.1.1.3 |
||||||||||||
|
dryContactSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.1.1.4 |
||||||||||||
|
dryContactSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.1.1.5 |
||||||||||||
|
dryContactSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.1.1.6 |
||||||||||||
|
dryContactSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.1.1.7 |
||||||||||||
|
dryContactSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.1.1.8 |
doorSwitchSensorTable
table.1.3.6.1.4.1.52674.500.4.2.2
·
1 row entry
·
8 columns
A list of door switch sensor entries.
Door switch sensor entry.
Indexes
doorSwitchSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
doorSwitchSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.2.1.1 |
||||||||||||
|
doorSwitchSensorValue
Whether the door is open or closed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.2.1.2 |
||||||||||||
|
doorSwitchSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.2.1.3 |
||||||||||||
|
doorSwitchSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.2.1.4 |
||||||||||||
|
doorSwitchSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.2.1.5 |
||||||||||||
|
doorSwitchSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.2.1.6 |
||||||||||||
|
doorSwitchSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.2.1.7 |
||||||||||||
|
doorSwitchSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.2.1.8 |
cameraMotionSensorTable
table.1.3.6.1.4.1.52674.500.4.2.3
·
1 row entry
·
8 columns
A list of camera motion sensor entries.
Camera motion sensor entry.
Indexes
cameraMotionSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
cameraMotionSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.3.1.1 |
||||||||||||
|
cameraMotionSensorValue
Whether motion is detected by the camera sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.3.1.2 |
||||||||||||
|
cameraMotionSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.3.1.3 |
||||||||||||
|
cameraMotionSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.3.1.4 |
||||||||||||
|
cameraMotionSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.3.1.5 |
||||||||||||
|
cameraMotionSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.3.1.6 |
||||||||||||
|
cameraMotionSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.3.1.7 |
||||||||||||
|
cameraMotionSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.3.1.8 |
otherStateSensorTable
table.1.3.6.1.4.1.52674.500.4.2.10
·
1 row entry
·
8 columns
A list of other state sensor entries.
Other state sensor entry.
Indexes
otherStateSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
otherStateSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.10.1.1 |
||||||||||||
|
otherStateSensorValue
State value reported by the sensor.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52674.500.4.2.10.1.2 |
||||||||||||
|
otherStateSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.10.1.3 |
||||||||||||
|
otherStateSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.10.1.4 |
||||||||||||
|
otherStateSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.10.1.5 |
||||||||||||
|
otherStateSensorPortId
The id of port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.10.1.6 |
||||||||||||
|
otherStateSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.10.1.7 |
||||||||||||
|
otherStateSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.10.1.8 |
vibrationSensorTable
table.1.3.6.1.4.1.52674.500.4.2.11
·
1 row entry
·
8 columns
A list of vibration sensor entries.
Vibration sensor entry.
Indexes
vibrationSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
vibrationSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.11.1.1 |
||||||||||||
|
vibrationSensorValue
Whether vibration is detected.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.11.1.2 |
||||||||||||
|
vibrationSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.11.1.3 |
||||||||||||
|
vibrationSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.11.1.4 |
||||||||||||
|
vibrationSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.11.1.5 |
||||||||||||
|
vibrationSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.11.1.6 |
||||||||||||
|
vibrationSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.11.1.7 |
||||||||||||
|
vibrationSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.11.1.8 |
smokeSensorTable
table.1.3.6.1.4.1.52674.500.4.2.12
·
1 row entry
·
8 columns
A list of smoke sensor entries.
Smoke sensor entry.
Indexes
smokeSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
smokeSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.12.1.1 |
||||||||||||
|
smokeSensorValue
Whether smoke is detected.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.12.1.2 |
||||||||||||
|
smokeSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.12.1.3 |
||||||||||||
|
smokeSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.12.1.4 |
||||||||||||
|
smokeSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.12.1.5 |
||||||||||||
|
smokeSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.12.1.6 |
||||||||||||
|
smokeSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.12.1.7 |
||||||||||||
|
smokeSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.12.1.8 |
leakSensorTable
table.1.3.6.1.4.1.52674.500.4.2.13
·
1 row entry
·
8 columns
A list of leak sensor entries.
Leak sensor entry.
Indexes
leakSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
leakSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.13.1.1 |
||||||||||||
|
leakSensorValue
Whether a leak is detected.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.13.1.2 |
||||||||||||
|
leakSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.13.1.3 |
||||||||||||
|
leakSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.13.1.4 |
||||||||||||
|
leakSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.13.1.5 |
||||||||||||
|
leakSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.13.1.6 |
||||||||||||
|
leakSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.13.1.7 |
||||||||||||
|
leakSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.13.1.8 |
beaconTable
table.1.3.6.1.4.1.52674.500.4.2.14
·
1 row entry
·
8 columns
A list of beacon entries.
Beacon entry.
Indexes
beaconIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
beaconId
The unique id of the beacon.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.14.1.1 |
||||||||||||
|
beaconValue
Whether the beacon is flashing.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.14.1.2 |
||||||||||||
|
beaconErrorStatus
The operational status of the beacon. If there are no error conditions
reported for the beacon, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.14.1.3 |
||||||||||||
|
beaconLabel
The unique label assigned to the beacon.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.14.1.4 |
||||||||||||
|
beaconEncId
The id of the physical enclosure containing the beacon.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.14.1.5 |
||||||||||||
|
beaconPortId
The id of the port the beacon is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.14.1.6 |
||||||||||||
|
beaconValueStr
The enum value label for the state reported by the beacon.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.14.1.7 |
||||||||||||
|
beaconIndex
The index of the beacon.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.14.1.8 |
switchedOutletTable
table.1.3.6.1.4.1.52674.500.4.2.15
·
1 row entry
·
8 columns
A list of switched outlet entries.
Switched outlet entry.
Indexes
switchedOutletIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
switchedOutletId
The unique id of the switched outlet.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.15.1.1 |
||||||||||||
|
switchedOutletValue
Whether the switched outlet is on or off.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.15.1.2 |
||||||||||||
|
switchedOutletErrorStatus
The operational status of the switched outlet. If there are no error conditions
reported for the switched outlet, the status is normal. Otherwise, the status is reported as the severity value of the highest severity e… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.15.1.3 |
||||||||||||
|
switchedOutletLabel
The unique label assigned to the switched outlet.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.15.1.4 |
||||||||||||
|
switchedOutletEncId
The id of the physical enclosure containing the switched outlet.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.15.1.5 |
||||||||||||
|
switchedOutletPortId
The id of the port the switched outlet is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.15.1.6 |
||||||||||||
|
switchedOutletValueStr
The enum value label for the state reported by the switchedOutlet.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.15.1.7 |
||||||||||||
|
switchedOutletIndex
The index of the switched outlet.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.15.1.8 |
doorLockSensorTable
table.1.3.6.1.4.1.52674.500.4.2.16
·
1 row entry
·
8 columns
A list of door lock sensor entries.
Door lock sensor entry.
Indexes
doorLockSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
doorLockSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.16.1.1 |
||||||||||||
|
doorLockSensorValue
When setting this object only unlocked(0) or locked(1) is valid.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.16.1.2 |
||||||||||||
|
doorLockSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.16.1.3 |
||||||||||||
|
doorLockSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.16.1.4 |
||||||||||||
|
doorLockSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.16.1.5 |
||||||||||||
|
doorLockSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.16.1.6 |
||||||||||||
|
doorLockSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.16.1.7 |
||||||||||||
|
doorLockSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.16.1.8 |
rackHandleSensorTable
table.1.3.6.1.4.1.52674.500.4.2.17
·
1 row entry
·
8 columns
A list of rack handle sensor entries.
Rack door handle sensor entry.
Indexes
rackHandleSensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
rackHandleSensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.17.1.1 |
||||||||||||
|
rackHandleSensorValue
Whether the door is open or closed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.17.1.2 |
||||||||||||
|
rackHandleSensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.17.1.3 |
||||||||||||
|
rackHandleSensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.17.1.4 |
||||||||||||
|
rackHandleSensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.17.1.5 |
||||||||||||
|
rackHandleSensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.17.1.6 |
||||||||||||
|
rackHandleSensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.17.1.7 |
||||||||||||
|
rackHandleSensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.17.1.8 |
outputRelaySensorTable
table.1.3.6.1.4.1.52674.500.4.2.18
·
1 row entry
·
8 columns
A list of output relay entries.
Output relay sensor entry.
Indexes
outputRelaySensorIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outputRelaySensorId
The unique id of the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.18.1.1 |
||||||||||||
|
outputRelaySensorValue
Whether the relay is open or closed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52674.500.4.2.18.1.2 |
||||||||||||
|
outputRelaySensorErrorStatus
The operational status of the sensor. If there are no error conditions
reported for the sensor, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition tha… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.4.2.18.1.3 |
||||||||||||
|
outputRelaySensorLabel
The unique label assigned to the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.18.1.4 |
||||||||||||
|
outputRelaySensorEncId
The id of the physical enclosure containing the sensor.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.18.1.5 |
||||||||||||
|
outputRelaySensorPortId
The id of the port the sensor is plugged into (or empty string
if it is not plugged into a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.4.2.18.1.6 |
||||||||||||
|
outputRelaySensorValueStr
The enum value label for the state reported by the sensor.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.4.2.18.1.7 |
||||||||||||
|
outputRelaySensorIndex
The index of the sensor.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.4.2.18.1.8 |
errorCondTable
table.1.3.6.1.4.1.52674.500.5.1
·
1 row entry
·
12 columns
A list of active and resolved error conditions.
Error condition entry.
Indexes
errorCondIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
errorCondId
The unique id of the error condition.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.5.1.1.1 |
||||||||||||
|
errorCondSeverity
The relative severity of the error condition.
|
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.5.1.1.2 |
||||||||||||
|
errorCondTypeId
The error type id reported for the error condition.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.5.1.1.3 |
||||||||||||
|
errorCondStartTime
The start time of the error condition, in msec since 1/1/1970.
|
SNMPv2-TCDateAndTime Textual Convention: SNMPv2-TCDateAndTime OctetStringType Constraints: range: 8range: 11 |
.1.3.6.1.4.1.52674.500.5.1.1.4 |
||||||||||||
|
errorCondStartTimeStr
The start time of the error condition, as ISO date-time formatted string (UTC).
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.5.1.1.5 |
||||||||||||
|
errorCondResolved
Whether the error condition was resolved.
|
BoolValue Textual Convention: BoolValue EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.5.1.1.6 |
||||||||||||
|
errorCondResolvedTime
The time the error condition was resolved (if it was resolved), in msec since 1/1/1970.
|
SNMPv2-TCDateAndTime Textual Convention: SNMPv2-TCDateAndTime OctetStringType Constraints: range: 8range: 11 |
.1.3.6.1.4.1.52674.500.5.1.1.7 |
||||||||||||
|
errorCondResolvedTimeStr
The time the error condition was resolved (if it was resolved), as ISO date-time formatted string (UTC).
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.5.1.1.8 |
||||||||||||
|
errorCondEncId
The id of the physical enclosure associated with the error.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.5.1.1.9 |
||||||||||||
|
errorCondPortId
The id of the port associated with the error (or empty string
if the error is not associated with a port). |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.5.1.1.10 |
||||||||||||
|
errorCondSensorId
The id of the sensor associated with the error (or empty string
if the error is not associated with a sensor.) |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.5.1.1.11 |
||||||||||||
|
errorCondIndex
The index of the error condition.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.5.1.1.12 |
cameraTable
table.1.3.6.1.4.1.52674.500.6.1
·
1 row entry
·
8 columns
A list of configured camera's.
Camera entry.
Indexes
cameraIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
cameraId
The id of the camera.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.6.1.1.1 |
||||||||||||
|
cameraVendor
The vendor of the camera.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.6.1.1.2 |
||||||||||||
|
cameraModel
The model of the camera.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.6.1.1.3 |
||||||||||||
|
cameraConnectionStatus
The operational status of the camera.
|
OperStatus Textual Convention: OperStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.6.1.1.4 |
||||||||||||
|
cameraErrorStatus
The error status of the camera. If there are no error conditions
reported for the camera, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that is n… |
ErrorStatus Textual Convention: ErrorStatus EnumerationType Values:
|
.1.3.6.1.4.1.52674.500.6.1.1.5 |
||||||||||||
|
cameraLabel
The unique label assigned to the camera.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.52674.500.6.1.1.6 |
||||||||||||
|
cameraAddress
The address or host name of the camera.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.6.1.1.7 |
||||||||||||
|
cameraIndex
The index of the physical enclosure.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.6.1.1.8 |
firmwareTable
table.1.3.6.1.4.1.52674.500.7.1
·
1 row entry
·
3 columns
A list of firmware versions contained in the NetBotz distribution.
Firmware entry.
Indexes
firmwareIndex
| Column | Syntax | OID |
|---|---|---|
|
firmwareDescription
Name of of the firmware product.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.7.1.1.1 |
|
firmwareVersion
Version of of the firmware product.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.52674.500.7.1.1.2 |
|
firmwareIndex
The index of the firmware.
|
SNMPv2-SMICounter32 Textual Convention: SNMPv2-SMICounter32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.52674.500.7.1.1.3 |