.1.3.6.1.4.1.705.1.2.2
·
1 row entry
·
9 columns
The table of managers.
The description of a manager entry in the managers table.
Indexes
mgmanagerIndex
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
mgmanagerIndex
mandatory
A unique value for each manager. Its value ranges between 1
and the value of upsmgManagersNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.2.2.1.1 |
||||||||||||||||||||
|
mgmanagerDeviceNumber
mandatory
This object is the number of the manager device in the
DevicesTable of the Config group. This means that the manager is powered by the UPS. If not the default value is 0. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.2.2.1.2 |
||||||||||||||||||||
|
mgmanagerNMSType
mandatory
The type of manager according to the NMS platform. We
include in the manager class all systems which will be notified by the agent via receiving traps (e.g. basic to complex NMS software). |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.2.2.1.3 |
||||||||||||||||||||
|
mgmanagerCommType
mandatory
The level of communication protocol for that manager.
Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgManagersTable. It is an implementation-specific matter as … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.2.2.1.4 |
||||||||||||||||||||
|
mgmanagerDescr
mandatory
A textual string containing information about the manager.
(manufacturer and version description). |
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.2.2.1.5 |
||||||||||||||||||||
|
mgmanagerAddress
mandatory
The IP address of the manager station receiving traps. The
value of this object is meaningful if and only if the value of the relevant mgmanagerCommType object is snmp type. |
RFC1155-SMIIpAddressr/w Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.705.1.2.2.1.6 |
||||||||||||||||||||
|
mgmanagerCommunity
mandatory
The manager community string.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.2.2.1.7 |
||||||||||||||||||||
|
mgmanagerSeverityLevel
mandatory
The severity level of traps to be received by this manager.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.2.2.1.8 |
||||||||||||||||||||
|
mgmanagerTrapAck
mandatory
The manager Trap Acknowledgement status. Setting
this object to mgnoack(2) or stdnomg(3) or cpqnoack(5) disables the trap acknowledgement from the related manager. The MG enterprise specific trap should then be sent onl… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.2.2.1.9 |
.1.3.6.1.4.1.705.1.3.2
·
1 row entry
·
9 columns
The table of receptacles that are controlled by the UPS.
The description of a receptacle in the table.
Indexes
mgreceptacleIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
mgreceptacleIndex
mandatory
A unique value for each receptacle. Its value ranges between
1 and the value of upsmgReceptaclesNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.3.2.1.1 |
||||||||||||||||
|
mgreceptacleLevel
mandatory
The level of receptacle.
Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgReceptaclesTable. It is an implementation-specific matter as to wether t… |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.2 |
||||||||||||||||
|
mgreceptacleType
mandatory
A textual string for the receptacle type.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.3.2.1.3 |
||||||||||||||||
|
mgreceptacleIdent
mandatory
A textual string identification for the user.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.3.2.1.4 |
||||||||||||||||
|
mgreceptacleState
mandatory
The ON/OFF status of the receptacle.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.3.2.1.5 |
||||||||||||||||
|
mgreceptacleReceptacle
mandatory
The receptacle number of the second level receptacle father.
The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle cl… |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.6 |
||||||||||||||||
|
mgreceptaclePowerCons
mandatory
The volt-ampere rating of the receptacle.
The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the … |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.7 |
||||||||||||||||
|
mgreceptacleOverload
mandatory
The overload status of the receptacle.
The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the def… |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.8 |
||||||||||||||||
|
mgreceptacleAutonomy
mandatory
The receptacle autonomy.
The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is … |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.9 |
.1.3.6.1.4.1.705.1.4.22
·
1 row entry
·
8 columns
The table of devices that are powered by the UPS.
The description of a device entry in the devices table.
Indexes
mgdeviceIndex
| Column | Syntax | OID |
|---|---|---|
|
mgdeviceIndex
mandatory
A unique value for each device. Its value ranges between 1
and the value of upsmgDevicesNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.4.22.1.1 |
|
mgdeviceReceptacleNum
mandatory
The receptacle number of the device plugged into the UPS.
This value gives index entry in the ReceptaclesTable object of the Receptacle group. A value of 0 invalidates the entry in the DevicesTable. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.2 |
|
mgdeviceIdent
mandatory
A textual string for device user identification.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.4.22.1.3 |
|
mgdeviceVaRating
mandatory
The volt-ampere rating of the device plugged into the UPS.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.4 |
|
mgdeviceSequenceOff
mandatory
To set the device position in the remote shutdown sequence.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.5 |
|
mgdeviceSequenceOn
mandatory
To set the device position in the remote reboot sequence.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.6 |
|
mgdeviceShutdownDuration
mandatory
To set the duration from start of computer shut-down
to complete. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.7 |
|
mgdeviceBootUpDuration
mandatory
To set the duration from start of computer boot-up
to complete. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.8 |
.1.3.6.1.4.1.705.1.4.23
·
1 row entry
·
10 columns
The table of receptacles.
The description of a receptacle entry in the table.
Indexes
mgreceptacleIndexb
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
mgreceptacleIndexb
mandatory
A unique value for each receptacle. Its value ranges between 1
and the value of upsmgReceptaclesNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.4.23.1.1 |
||||||||
|
mgreceptacleStateTurnOn
mandatory
Default return state at turn on.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.4.23.1.2 |
||||||||
|
mgreceptacleStateMainReturn
mandatory
Default return state on main return.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.4.23.1.3 |
||||||||
|
mgreceptacleStateDischarge
mandatory
Default return state on main return from battery discharge.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.4.23.1.4 |
||||||||
|
mgreceptacleShutoffLevel
mandatory
Battery level for starting shutoff sequence.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.5 |
||||||||
|
mgreceptacleShutoffTimer
mandatory
Time delay from on battery for starting shutoff sequence.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.6 |
||||||||
|
mgreceptacleRestartLevel
mandatory
Battery level for starting restart sequence.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.7 |
||||||||
|
mgreceptacleRestartDelay
mandatory
Time delay for starting restart sequence.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.8 |
||||||||
|
mgreceptacleShutdownDuration
mandatory
Maximum Shutdown Duration for systems powered by this plug.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.9 |
||||||||
|
mgreceptacleBootUpDuration
mandatory
Maximum Reboot Duration for systems powered by this plug.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.10 |
.1.3.6.1.4.1.705.1.4.25
·
1 row entry
·
2 columns
The table of environmental external alarms.
The description of an external alarm in the table.
Indexes
mgextAlarmIndex
| Column | Syntax | OID |
|---|---|---|
|
mgextAlarmIndex
mandatory
A unique value for each external alarm. Its value ranges
between 1 and the value of upsmgConfigExtAlarmNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.4.25.1.1 |
|
mgextAlarmUID
mandatory
A textual string for alarm state user identification.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.4.25.1.2 |
.1.3.6.1.4.1.705.1.4.29
·
1 row entry
·
3 columns
The table of daily on/off time.
The description of a daily on/off time schedule in the table.
Indexes
mgcontrolDayIndex
| Column | Syntax | OID |
|---|---|---|
|
mgcontrolDayIndex
mandatory
The day index. It is a number between 1 and 7, 1 for
Sunday, 2 for Monday, ... |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.4.29.1.1 |
|
mgcontrolDayOn
mandatory
To set daily power on time. Any value greater than 86400
is to disable the Day On. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.29.1.2 |
|
mgcontrolDayOff
mandatory
To set daily power off time. Any value greater than 86400
is to disable the Day Off. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.29.1.3 |
.1.3.6.1.4.1.705.1.4.34
·
1 row entry
·
14 columns
The table containing the configuration of the environment sensor.
The description of an entry in the table.
Indexes
upsmgConfigSensorIndex
| Column | Syntax | OID |
|---|---|---|
|
upsmgConfigSensorIndex
mandatory
The sensor index, ranging from 1 to upsmgEnvironmentNum.
|
Integer32 Constraints: range: 0-50 |
.1.3.6.1.4.1.705.1.4.34.1.1 |
|
upsmgConfigSensorName
mandatory
The sensor user-friendly name.
|
OctetStringr/w Constraints: range: 0-42 |
.1.3.6.1.4.1.705.1.4.34.1.2 |
|
upsmgConfigTemperatureLow
mandatory
The low temperature threshold in unit 0.1 Cel.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.3 |
|
upsmgConfigTemperatureHigh
mandatory
The high temperature threshold in unit 0.1 Cel.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.4 |
|
upsmgConfigTemperatureHysteresis
mandatory
The temperature hysteresys used for threshold test in unit 0.1 Cel.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.5 |
|
upsmgConfigHumidityLow
mandatory
The low humidity threshold in unit 1 %.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.6 |
|
upsmgConfigHumidityHigh
mandatory
The high humidity threshold in unit 1 %.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.7 |
|
upsmgConfigHumidityHysteresis
mandatory
The humidity hysteresys used for threshold test in unit 1 %.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.8 |
|
upsmgConfigInput1Name
mandatory
The Input #1 user-friendly name.
|
OctetStringr/w Constraints: range: 0-22 |
.1.3.6.1.4.1.705.1.4.34.1.9 |
|
upsmgConfigInput1ClosedLabel
mandatory
The Input #1 label for closed position.
|
OctetStringr/w Constraints: range: 0-18 |
.1.3.6.1.4.1.705.1.4.34.1.10 |
|
upsmgConfigInput1OpenLabel
mandatory
The Input #1 label for open position.
|
OctetStringr/w Constraints: range: 0-18 |
.1.3.6.1.4.1.705.1.4.34.1.11 |
|
upsmgConfigInput2Name
mandatory
The Input #2 user-friendly name.
|
OctetStringr/w Constraints: range: 0-22 |
.1.3.6.1.4.1.705.1.4.34.1.12 |
|
upsmgConfigInput2ClosedLabel
mandatory
The Input #2 label for closed position.
|
OctetStringr/w Constraints: range: 0-18 |
.1.3.6.1.4.1.705.1.4.34.1.13 |
|
upsmgConfigInput2OpenLabel
mandatory
The Input #2 label for open position.
|
OctetStringr/w Constraints: range: 0-18 |
.1.3.6.1.4.1.705.1.4.34.1.14 |
.1.3.6.1.4.1.705.1.6.2
·
1 row entry
·
6 columns
The table of input phases.
The description of an input phase.
Indexes
mginputIndex
| Column | Syntax | OID |
|---|---|---|
|
mginputIndex
mandatory
The input phase voltage index. It is a number between 1
and upsmgInputPhaseNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.6.2.1.1 |
|
mginputVoltage
mandatory
The input phase voltage.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.2 |
|
mginputFrequency
mandatory
The input phase frequency.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.3 |
|
mginputMinimumVoltage
mandatory
The input phase minimum voltage over the last minute.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.4 |
|
mginputMaximumVoltage
mandatory
The input phase maximum voltage over the last minute.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.5 |
|
mginputCurrent
mandatory
The input phase current.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.6 |
.1.3.6.1.4.1.705.1.7.2
·
1 row entry
·
5 columns
The table of output phases.
The description of an output phase.
Indexes
mgoutputPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
mgoutputPhaseIndex
mandatory
The output phase voltage index. It is a number between 1
and upsmgOutputPhaseNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.7.2.1.1 |
|
mgoutputVoltage
mandatory
The output phase voltage.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.7.2.1.2 |
|
mgoutputFrequency
mandatory
The output phase frequency.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.7.2.1.3 |
|
mgoutputLoadPerPhase
mandatory
The output load per phase.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.7.2.1.4 |
|
mgoutputCurrent
mandatory
The output phase current.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.7.2.1.5 |
.1.3.6.1.4.1.705.1.8.3
·
1 row entry
·
2 columns
The table of external alarms.
The description of an external alarm.
Indexes
mgalarmNum
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
mgalarmNum
mandatory
The external alarm number. A number between 1 and
upsmgConfigExtAlarmNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.8.3.1.1 |
||||
|
mgalarmState
mandatory
The external alarm state (active or inactive).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.3.1.2 |
.1.3.6.1.4.1.705.1.8.5
·
1 row entry
·
3 columns
The table of sensor units.
The description of a sensor unit.
Indexes
mgsensorNum
| Column | Syntax | OID |
|---|---|---|
|
mgsensorNum
mandatory
The unit number. A number between 1 and 4.
|
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.8.5.1.1 |
|
mgsensorTemp
mandatory
The measured temperature of the unit.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.8.5.1.2 |
|
mgsensorHumidity
mandatory
The measured humidity of the unit.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.8.5.1.3 |
.1.3.6.1.4.1.705.1.8.7
·
1 row entry
·
10 columns
The table containing the measurements and alarms made by Environment sensor units.
The description of an entry in the measurement table.
Indexes
upsmgEnvironmentIndex
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
upsmgEnvironmentIndex
mandatory
The sensor index, ranging from 1 to upsmgEnvironmentNum.
|
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.8.7.1.1 |
||||
|
upsmgEnvironmentComFailure
mandatory
The sensor communication failure : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.2 |
||||
|
upsmgEnvironmentTemperature
mandatory
The temperature measurement in unit 0.1 Cel.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.8.7.1.3 |
||||
|
upsmgEnvironmentTemperatureLow
mandatory
Temperature is below low theshold : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.4 |
||||
|
upsmgEnvironmentTemperatureHigh
mandatory
Temperature is above high threshold : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.5 |
||||
|
upsmgEnvironmentHumidity
mandatory
The humidity measurement in unit 0.1 %.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.8.7.1.6 |
||||
|
upsmgEnvironmentHumidityLow
mandatory
Humidity is below low threshold : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.7 |
||||
|
upsmgEnvironmentHumidityHigh
mandatory
Humidity is above high threshold : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.8 |
||||
|
upsmgEnvironmentInput1State
mandatory
State of Input#1 : closed(1), open(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.9 |
||||
|
upsmgEnvironmentInput2State
mandatory
State of Input#2 : closed(1), open(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.10 |
.1.3.6.1.4.1.705.1.9.1
·
1 row entry
·
11 columns
The table of receptacles.
The description of a receptacle entry in the table.
Indexes
mgreceptacleIndexc
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
mgreceptacleIndexc
mandatory
A unique value for each receptacle. Its value ranges between 1
and the value of upsmgReceptaclesNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.9.1.1.1 |
||||||||
|
mgreceptacleOnDelay
mandatory
Turn on UPS receptacle w/delay=?.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.9.1.1.2 |
||||||||
|
mgreceptacleOnCtrl
mandatory
The receptacle control on action.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.3 |
||||||||
|
mgreceptacleOnStatus
mandatory
The receptacle control on status.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.4 |
||||||||
|
mgreceptacleOffDelay
mandatory
Turn off UPS receptacle w/delay=?.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.9.1.1.5 |
||||||||
|
mgreceptacleOffCtrl
mandatory
The receptacle control off action.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.6 |
||||||||
|
mgreceptacleOffStatus
mandatory
The receptacle control off status.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.7 |
||||||||
|
mgreceptacleToggleDelay
mandatory
Turn off then on UPS receptacle w/delay=?.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.9.1.1.8 |
||||||||
|
mgreceptacleToggleCtrl
mandatory
The receptacle control toggle action.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.9 |
||||||||
|
mgreceptacleToggleStatus
mandatory
The receptacle control toggle status.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.10 |
||||||||
|
mgreceptacleToggleDuration
mandatory
Turn off then on UPS receptacle w/duration=?.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.9.1.1.11 |