LHX-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
4
Rows
4
Columns
30
sensorCountTable
table.1.3.6.1.4.1.13742.9.1.2
·
1 row entry
·
1 columns
A list of lhx sensor count extries.
An entry containing the number of lhx sensors of a certain type.
Indexes
portIdx sensorTypeIdx
| Column | Syntax | OID |
|---|---|---|
|
sensorCount
The number of sensors.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.2.1.1 |
lhxConfigurationTable
table.1.3.6.1.4.1.13742.9.1.3.1
·
1 row entry
·
8 columns
A list of lhx controller configuration extries. The number of entries is given by the value of portCount.
An entry containing parameters for an lhx.
Indexes
portIdx
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
operationalState
The operational state of the lhx controller.
To switch LHX power state while controller is connected, set operationalState to 1 (off) or 2 (on). Switching power state while LHX is disconnected or to 0 (disconnected) is… |
OperationalStateEnumerationr/w Textual Convention: OperationalStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.9.1.3.1.1.1 |
||||||
|
setpointVentilators
The setpoint of the ventilators.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.3.1.1.2 |
||||||
|
setpointWaterValve
The setpoint of the water valve.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.3.1.1.3 |
||||||
|
defaultFanSpeed
The 'default' fan speed during normal operation in per mill.
Default is 80% (= 800). |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.3.1.1.4 |
||||||
|
maximumCoolingState
Indicates whether maximum cooling was requested or not.
To request maximum cooling, set maximumCoolingState to 1 (true). Setting maximumCoolingState to 2 (false) is undefined, set alertState to 2 (false) instead. |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.9.1.3.1.1.5 |
||||||
|
alertState
Indicates whether LHX controler is in alert state or not.
To acknowledge alert status, set alertState to 2 (false). Setting alertState to 1 (true) is undefined. |
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.9.1.3.1.1.6 |
||||||
|
model
The model indentifier of an LHX controller.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.9.1.3.1.1.7 |
||||||
|
fwVersion
The firmware version of an LHX controller.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.9.1.3.1.1.8 |
sensorConfigurationTable
table.1.3.6.1.4.1.13742.9.1.4.1
·
1 row entry
·
17 columns
A list of lhx sensor configuration extries. The number of entries is given by the value of portCount.
An entry containing parameters for an lhx.
Indexes
portIdx sensorTypeIdx sensorIdx
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
portIdx
A unique value for each port. Its value
ranges between 1 and the value of portCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.9.1.4.1.1.1 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorTypeIdx
A unique value for the type of sensor.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.13742.9.1.4.1.1.2 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorIdx
A unique value for each sensor. Its value
ranges between 1 and the value of sensorCount. |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.13742.9.1.4.1.1.3 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorLabel
The short ID of the sensor (e.g. F1, M2).
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.9.1.4.1.1.4 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorUnit
The base units.
This parameter does not apply to state sensors. |
SensorUnitsEnumeration Textual Convention: SensorUnitsEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.9.1.4.1.1.5 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorDecimalDigits
The number of digits displayed to the right of the decimal point.
This parameter does not apply to state sensors. |
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.9.1.4.1.1.6 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorMaximum
The largest possible value.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.4.1.1.7 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorMinimum
The smallest possible value.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not apply… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.4.1.1.8 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorHysteresis
The hysteresis used for deassertions.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does … |
SNMPv2-SMIUnsigned32r/w Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.9.1.4.1.1.9 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorLowerCriticalThreshold
The lower critical threshold.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not appl… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.4.1.1.10 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorLowerWarningThreshold
The lower non-critical (warning) threshold.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.4.1.1.11 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorUpperCriticalThreshold
The upper critical threshold.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does not app… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.4.1.1.12 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorUpperWarningThreshold
The upper non-critical (warning) threshold.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.4.1.1.13 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorEnabledThresholds
A bit string which indicates which thresholds are enabled.
This parameter does not apply to state sensors. |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.13742.9.1.4.1.1.14 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorThresholdMaximum
The largest possible threshold value.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does … |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.4.1.1.15 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorThresholdMinimum
The smallest possible threshold value.
The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2, then actual value is 0.01. This parameter does… |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.1.4.1.1.16 |
||||||||||||||||||||||||||||||||||||||||||
|
sensorName
The descriptive ID of the sensor (e.g. Fan Speed 1).
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.13742.9.1.4.1.1.17 |
sensorMeasurementsTable
table.1.3.6.1.4.1.13742.9.2.1
·
1 row entry
·
4 columns
A list of external sensor entries. The number of entries is given by the value of sensorCount for the LHX.
An entry containing measurement objects for an external sensor.
Indexes
portIdx sensorTypeIdx sensorIdx
| Column | Syntax | OID | ||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
measurementsSensorIsAvailable
Is the sensor available?
|
SNMPv2-TCTruthValue Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.13742.9.2.1.1.1 |
||||||||||||||||||||||||||
|
measurementsSensorState
The sensor state.
|
SensorStateEnumeration Textual Convention: SensorStateEnumeration EnumerationType Values:
|
.1.3.6.1.4.1.13742.9.2.1.1.2 |
||||||||||||||||||||||||||
|
measurementsSensorValue
The sensor reading.
This parameter does not apply to state sensors. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.13742.9.2.1.1.3 |
||||||||||||||||||||||||||
|
measurementsSensorTimeStamp
The sensor reading timestamp.
|
SNMPv2-SMIUnsigned32 Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.13742.9.2.1.1.4 |