EPPC-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
11
Rows
11
Columns
77

upsESystemInputTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.2.16 · 1 row entry · 5 columns
A list of input table entries. The number of entries is given by the 
value of upsESystemInputNumPhase.
upsESystemInputEntry entry .1.3.6.1.4.1.935.10.1.1.2.16.1
An entry containing information applicable to a particular input line.
Indexes
upsESystemInputPhase
Column Syntax OID
upsESystemInputPhase mandatory
The number of the phase. Serves as index for input table
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.935.10.1.1.2.16.1.1
upsESystemInputFrequency mandatory
The measured input frquency from the UPS meters in 0.1Hz.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.16.1.2
upsESystemInputVoltage mandatory
The measured input voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.16.1.3
upsESystemInputCurrent mandatory
The measured input mandatory from the UPS meters in 0.1 amps.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.16.1.4
upsESystemInputWatts mandatory
The measured input real power in watts.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.16.1.5

upsESystemOutputTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.2.18 · 1 row entry · 7 columns
A list of output table entries. The number of entries is given 
by the value of upsESystemOutputNumPhase.
upsESystemOutputEntry entry .1.3.6.1.4.1.935.10.1.1.2.18.1
An entry containing information applicable to a particular line.
Indexes
upsESystemOutputPhase
Column Syntax OID
upsESystemOutputPhase mandatory
The number of the phase. Serves as index for output table
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.935.10.1.1.2.18.1.1
upsESystemOutputFrequency mandatory
The measured output frequency from the UPS meters in 0.1Hz.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.2
upsESystemOutputVoltage mandatory
The measured output voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.3
upsESystemOutputCurrent mandatory
The measured output mandatory from the UPS meters in 0.1 amps.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.4
upsESystemOutputWatts mandatory
The measured output real power in watts.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.5
upsESystemOutputVA mandatory
The measured output real complex power in VA.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.6
upsESystemOutputLoad mandatory
The UPS output load in percent of rated capacity.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.7

upsESystemBypassTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.2.20 · 1 row entry · 5 columns
A list of bypass table entries. The number of entries is given by the
value of upsESystemBypassNumPhase.
upsESystemBypassEntry entry .1.3.6.1.4.1.935.10.1.1.2.20.1
An entry containing information applicable to a particular line.
Indexes
upsESystemBypassPhase
Column Syntax OID
upsESystemBypassPhase mandatory
The number of the phase. Serves as index for bypass table
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.935.10.1.1.2.20.1.1
upsESystemBypassFrequency mandatory
The measured bypass frequency from the UPS meters in 0.1 Hz.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.20.1.2
upsESystemBypassVoltage mandatory
The measured bypass voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.20.1.3
upsESystemBypassCurrent mandatory
The measured bypass mandatory from the UPS meters in 0.1 amps
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.20.1.4
upsESystemBypassWatts mandatory
The measured bypass input real power in watts.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.20.1.5
.1.3.6.1.4.1.935.10.1.1.3.12 · 1 row entry · 8 columns
A list of charger modules entries. The number of entries is given 
by the value of upsEchargerModulesNum.
upsEChargerModulesEntry entry .1.3.6.1.4.1.935.10.1.1.3.12.1
An entry containing information applicable to a particular charger module.
Indexes
chargerModulesNum
Column Syntax OID
chargerModulesNum mandatory
The number of charger modules. Serves as index for charger module table
Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.935.10.1.1.3.12.1.1
chargerModulesAddress mandatory
Charger Modules' address.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.2
positiveChargeVotlage mandatory
The measured positive charger voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.3
negativeChargeVoltage mandatory
The measured nepositive charger voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.4
positiveChargeCurrent mandatory
The measured positive charger mandatory from the UPS meters in in 0.1 amps.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.5
negativeChargeCurrent mandatory
The measured nepositive charger mandatory from the UPS meters in 0.1 amps.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.6
chargerModulesTemperature mandatory
The measured charger temperature from the UPS meters in 0.1 degree.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.7
chargerModulesMode mandatory
The working mode of charger modules.
Enumeration
Enumerated Values:
1powerOn
2standyby
3fault
4shutdown
5running
6suicide
7unknown
.1.3.6.1.4.1.935.10.1.1.3.12.1.8

upsEModulesTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.4.2 · 1 row entry · 22 columns
A list of UPS modules entries. The number of entries is 
given by the value of upsEModulesNum.
upsEModulesEntry entry .1.3.6.1.4.1.935.10.1.1.4.2.1
An entry containing information applicable to a particular upsE module.
Indexes
upsEModulesNum
Column Syntax OID
upsEModulesNum mandatory
The number of UPS modules. Serves as index for UPS module table
Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.935.10.1.1.4.2.1.1
upsEModuleAddress mandatory
the address of UPS modules.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.2
upsEModulePositiveBusVolt mandatory
The measured positive upsE module voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.3
upsEModuleNegativeBusVolt mandatory
The measured nepositive upsE module voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.4
upsEModuleTemperature mandatory
The measured upsE module temperature from the UPS meters in 0.1 degree.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.5
upsEModuleWorkingMode mandatory
The working mode of UPS modules.
Enumeration
Enumerated Values:
1power-on
2stand-by
3by-pass
4line
5battery
6battery-test
7fault
8converter
9eco
10shutdown
11on-booster
12on-reducer
13other
.1.3.6.1.4.1.935.10.1.1.4.2.1.6
upsEModuleOutputCurrentR mandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.7
upsEModuleOutputWattR mandatory
The measured upsE module output watts from the UPS meters in watts.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.8
upsEModuleOutputLoadR mandatory
The output load of UPS modules in %.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.9
upsEModuleWarningCode mandatory
The warning code of ups modules.Please refer the warning table of 'QU,XX' for details.
OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.935.10.1.1.4.2.1.10
upsEModuleFaultCode mandatory
The fault code of ups modules.Please refer command 'QU,XX' for details.
OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.935.10.1.1.4.2.1.11
upsEModuleTrapState mandatory
the values indicate the unrestored traps.
For example, after AC fail, so the value of upsETrapState should be '1'.
And then the AC restore, the value of upsEModuleTrapState
should change to empty.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.935.10.1.1.4.2.1.12
upsEModuleConfigOutputVA mandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.13
upsEModuleOutputCurrentS mandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.14
upsEModuleOutputCurrentT mandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.15
upsEModuleOutputWattS mandatory
The measured upsE module output watts from the UPS meters in watts.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.16
upsEModuleOutputWattT mandatory
The measured upsE module output watts from the UPS meters in watts.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.17
upsEModuleOutputLoadS mandatory
The output load of UPS modules in %.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.18
upsEModuleOutputLoadT mandatory
The output load of UPS modules in %.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.19
upsEModuleOutputVAR mandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.20
upsEModuleOutputVAS mandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.21
upsEModuleOutputVAT mandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
UPS-MIBNonNegativeInteger
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.22
.1.3.6.1.4.1.935.10.1.1.6.4 · 1 row entry · 4 columns
A list of contacts table entries. The number of entries is given by the
value of upsEEnvironmentContactsNum
upsEEnvironmentContactEntry entry .1.3.6.1.4.1.935.10.1.1.6.4.1
An entry containing information applicable to a particular contact
Indexes
upsEEnvironmentContactIndex
Column Syntax OID
upsEEnvironmentContactIndex mandatory
The number of environment contacts. Serves as index for environment contact table
UPS-MIBPositiveInteger
Textual Convention: UPS-MIBPositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.6.4.1.1
upsEEnvironmentContactType mandatory
operation type
Enumerationr/w
Enumerated Values:
1normallyOpen
2normallyClosed
3notUsed
.1.3.6.1.4.1.935.10.1.1.6.4.1.2
upsEEnvironmentContactState mandatory
The mandatory status.
Enumeration
Enumerated Values:
1open
2closed
3openWithNotice
4closedWithNotice
.1.3.6.1.4.1.935.10.1.1.6.4.1.3
upsEEnvironmentContactDescription mandatory
Description of environment contact.
OctetStringr/w
Constraints:
range: 0-31
.1.3.6.1.4.1.935.10.1.1.6.4.1.4
.1.3.6.1.4.1.935.10.1.1.7.6 · 1 row entry · 6 columns
This table describes the schedule for automatically battery
test.
upsEBatteryTestScheduleEntry entry .1.3.6.1.4.1.935.10.1.1.7.6.1
An entry containing information applicable to schedule test.
Indexes
upsEBatteryTestScheduleIndex
Column Syntax OID
upsEBatteryTestScheduleIndex mandatory
The index of battery test scheduled.
UPS-MIBPositiveInteger
Textual Convention: UPS-MIBPositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.7.6.1.1
upsEBatteryTestScheduleDay mandatory
The weekday or specaial day on which the UPS should start battery test.
Enumerationr/w
Enumerated Values:
1monday
2tuesday
3wednsday
4thusday
5friday
6saturday
7sunday
8specialday
9none
.1.3.6.1.4.1.935.10.1.1.7.6.1.2
upsEBatteryTestScheduleTime mandatory
The time that the battery test will be initiated in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.7.6.1.3
upsEBatteryTestScheduleType mandatory
The type of battery test.
Enumerationr/w
Enumerated Values:
1none
2batteryTest10sec
3batteryTestUntilLow
4batteryTestWithTime
.1.3.6.1.4.1.935.10.1.1.7.6.1.5
upsEBatteryTestScheduleTestWithTime mandatory
The battery time of setting time test in seconds.
UPS-MIBNonNegativeIntegerr/w
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.7.6.1.6
upsEBatteryTestScheduleSpecialDay mandatory
The special day that the battery test will be initiated in dd/mm/yyyy format.
OctetStringr/w
Constraints:
range: 10-10
.1.3.6.1.4.1.935.10.1.1.7.6.1.7
.1.3.6.1.4.1.935.10.1.1.8.4 · 1 row entry · 4 columns
This table describes the parametes for shutdown process
when shutdown event occurs
upsEShutdownEventsEntry entry .1.3.6.1.4.1.935.10.1.1.8.4.1
An entry containing information applicable to a particular shutdown
event line
Indexes
upsEShutdownEvent
Column Syntax OID
upsEShutdownEvent mandatory
The shutdown event identification
Enumeration
Enumerated Values:
1acFail
2batteryLow
3upsEOverLoad
4upsEOverTemperature
5upsEWeeklySchedule
6upsESpecialSchedule
7environmentTemperatureOverThreshold
8environmentHumidityOverThreshold
9environmentContact1Alarm
10environmentContact2Alarm
11belowCapacityLimit
12belowRemainTimeLimit
.1.3.6.1.4.1.935.10.1.1.8.4.1.1
upsEShutdownEventAction mandatory
Status of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when
corresponding event occured.
Enumerationr/w
Enumerated Values:
1disable
2warning
3shutdownClient
4shutdownUPS
.1.3.6.1.4.1.935.10.1.1.8.4.1.2
upsEShutdownwarningPeriodTime mandatory
The Delay in seconds after the occurance of the curresponding shutdown
event, and warning message should be popped in this period.
UPS-MIBNonNegativeIntegerr/w
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.8.4.1.3
upsEShutdownWarningPeriodInterval mandatory
The frequency of sending warning messages to the connected
clients when the curresponding shutdown event occurs.
The value is in units of seconds.
UPS-MIBNonNegativeIntegerr/w
Textual Convention: UPS-MIBNonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.8.4.1.4
.1.3.6.1.4.1.935.10.1.1.8.5 · 1 row entry · 5 columns
The table to schedule shutting down the ups by weekly
upsEControlWeeklyScheduleEntry entry .1.3.6.1.4.1.935.10.1.1.8.5.1
An entry containing information applicable to a particular line
Indexes
upsEControlWeeklyScheduleIndex
Column Syntax OID
upsEControlWeeklyScheduleIndex mandatory
the index of schedule events.
UPS-MIBPositiveInteger
Textual Convention: UPS-MIBPositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.8.5.1.1
upsEWeeklyScheduleShutdownDay mandatory
the weekday on which upsE shoud shutdown
Enumerationr/w
Enumerated Values:
1monday
2tuesday
3wednesday
4thursday
5friday
6saturday
7sunday
8none
.1.3.6.1.4.1.935.10.1.1.8.5.1.2
upsEWeeklyScheduleShutdownTime mandatory
The time that the process of shutting down the UPS will be initiated
in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.8.5.1.3
upsEWeeklyScheduleRestartDay mandatory
the weekday on which the UPS should restart.
Enumerationr/w
Enumerated Values:
1monday
2tuesday
3wednesday
4thursday
5friday
6saturday
7sunday
8none
.1.3.6.1.4.1.935.10.1.1.8.5.1.4
upsEWeeklyScheduleRestartTime mandatory
The time the UPS will restart in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.8.5.1.5
.1.3.6.1.4.1.935.10.1.1.8.6 · 1 row entry · 5 columns
The table to schedule shutting down the ups.
upsEControlSpecialDayScheduleEntry entry .1.3.6.1.4.1.935.10.1.1.8.6.1
An entry containing information applicable to a particular line.
Indexes
upsEControlSpecialDayScheduleIndex
Column Syntax OID
upsEControlSpecialDayScheduleIndex mandatory
The index of special day schedule.
UPS-MIBPositiveInteger
Textual Convention: UPS-MIBPositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.8.6.1.1
upsESpecialDayScheduleShutdownDay mandatory
The special day on which UPS should shutdown with the format
of DD/MM/YYYY.
OctetStringr/w
Constraints:
range: 10-10
.1.3.6.1.4.1.935.10.1.1.8.6.1.2
upsESpecialDayScheduleShutdownTime mandatory
The time that the process of shutting down the UPS will be initiated
in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.8.6.1.3
upsESpecialDayScheduleRestartDay mandatory
The special day on which the UPS should restart with the format
of DD/MM/YYYY.
OctetStringr/w
Constraints:
range: 10-10
.1.3.6.1.4.1.935.10.1.1.8.6.1.4
upsESpecialDayScheduleRestartTime mandatory
The time the UPS will restart in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.8.6.1.5
.1.3.6.1.4.1.935.10.1.1.9.1 · 1 row entry · 6 columns
This table list the managers'IP to send traps to.
upsETrapsReceiversEntry entry .1.3.6.1.4.1.935.10.1.1.9.1.1
An entry containing information applicable to a particular input line.
Indexes
upsETrapsReceiversIndex
Column Syntax OID
upsETrapsReceiversIndex mandatory
The index to a trap receiver entry
UPS-MIBPositiveInteger
Textual Convention: UPS-MIBPositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.9.1.1.1
upsETrapsReceiverAddress mandatory
The IP address of the manager to send a trap to.
OctetStringr/w
Constraints:
range: 0-45
.1.3.6.1.4.1.935.10.1.1.9.1.1.2
upsETrapReceiverCommunityString mandatory
The community name to use in the trap when
sent to the manager.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.935.10.1.1.9.1.1.3
upsETrapType mandatory
The type of trap to be received by the manager.
Enumerationr/w
Enumerated Values:
1none
2rfc1628Trap
3eppcTrap
.1.3.6.1.4.1.935.10.1.1.9.1.1.4
upsETrapsSeverityLevel mandatory
The severity level of traps to be received by this manager.
Enumerationr/w
Enumerated Values:
1informational
2warning
3severe
.1.3.6.1.4.1.935.10.1.1.9.1.1.5
upsETrapReceiverDescription mandatory
Description of trap receivers
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.935.10.1.1.9.1.1.6