EPPC-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
11
Rows
11
Columns
77
.1.3.6.1.4.1.935.10.1.1.2.16
·
1 row entry
·
5 columns
A list of input table entries. The number of entries is given by the value of upsESystemInputNumPhase.
An entry containing information applicable to a particular input line.
Indexes
upsESystemInputPhase
| Column | Syntax | OID |
|---|---|---|
|
upsESystemInputPhase
mandatory
The number of the phase. Serves as index for input table
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.1 |
|
upsESystemInputFrequency
mandatory
The measured input frquency from the UPS meters in 0.1Hz.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.2 |
|
upsESystemInputVoltage
mandatory
The measured input voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.3 |
|
upsESystemInputCurrent
mandatory
The measured input mandatory from the UPS meters in 0.1 amps.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.4 |
|
upsESystemInputWatts
mandatory
The measured input real power in watts.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.5 |
.1.3.6.1.4.1.935.10.1.1.2.18
·
1 row entry
·
7 columns
A list of output table entries. The number of entries is given by the value of upsESystemOutputNumPhase.
An entry containing information applicable to a particular line.
Indexes
upsESystemOutputPhase
| Column | Syntax | OID |
|---|---|---|
|
upsESystemOutputPhase
mandatory
The number of the phase. Serves as index for output table
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.1 |
|
upsESystemOutputFrequency
mandatory
The measured output frequency from the UPS meters in 0.1Hz.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.2 |
|
upsESystemOutputVoltage
mandatory
The measured output voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.3 |
|
upsESystemOutputCurrent
mandatory
The measured output mandatory from the UPS meters in 0.1 amps.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.4 |
|
upsESystemOutputWatts
mandatory
The measured output real power in watts.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.5 |
|
upsESystemOutputVA
mandatory
The measured output real complex power in VA.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.6 |
|
upsESystemOutputLoad
mandatory
The UPS output load in percent of rated capacity.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.7 |
.1.3.6.1.4.1.935.10.1.1.2.20
·
1 row entry
·
5 columns
A list of bypass table entries. The number of entries is given by the value of upsESystemBypassNumPhase.
An entry containing information applicable to a particular line.
Indexes
upsESystemBypassPhase
| Column | Syntax | OID |
|---|---|---|
|
upsESystemBypassPhase
mandatory
The number of the phase. Serves as index for bypass table
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.1 |
|
upsESystemBypassFrequency
mandatory
The measured bypass frequency from the UPS meters in 0.1 Hz.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.2 |
|
upsESystemBypassVoltage
mandatory
The measured bypass voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.3 |
|
upsESystemBypassCurrent
mandatory
The measured bypass mandatory from the UPS meters in 0.1 amps
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.4 |
|
upsESystemBypassWatts
mandatory
The measured bypass input real power in watts.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.5 |
.1.3.6.1.4.1.935.10.1.1.3.12
·
1 row entry
·
8 columns
A list of charger modules entries. The number of entries is given by the value of upsEchargerModulesNum.
An entry containing information applicable to a particular charger module.
Indexes
chargerModulesNum
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
chargerModulesNum
mandatory
The number of charger modules. Serves as index for charger module table
|
Integer32 Constraints: range: 1-32 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.1 |
||||||||||||||
|
chargerModulesAddress
mandatory
Charger Modules' address.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.2 |
||||||||||||||
|
positiveChargeVotlage
mandatory
The measured positive charger voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.3 |
||||||||||||||
|
negativeChargeVoltage
mandatory
The measured nepositive charger voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.4 |
||||||||||||||
|
positiveChargeCurrent
mandatory
The measured positive charger mandatory from the UPS meters in in 0.1 amps.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.5 |
||||||||||||||
|
negativeChargeCurrent
mandatory
The measured nepositive charger mandatory from the UPS meters in 0.1 amps.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.6 |
||||||||||||||
|
chargerModulesTemperature
mandatory
The measured charger temperature from the UPS meters in 0.1 degree.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.7 |
||||||||||||||
|
chargerModulesMode
mandatory
The working mode of charger modules.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.3.12.1.8 |
.1.3.6.1.4.1.935.10.1.1.4.2
·
1 row entry
·
22 columns
A list of UPS modules entries. The number of entries is given by the value of upsEModulesNum.
An entry containing information applicable to a particular upsE module.
Indexes
upsEModulesNum
| Column | Syntax | OID | ||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsEModulesNum
mandatory
The number of UPS modules. Serves as index for UPS module table
|
Integer32 Constraints: range: 1-32 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.1 |
||||||||||||||||||||||||||
|
upsEModuleAddress
mandatory
the address of UPS modules.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.2 |
||||||||||||||||||||||||||
|
upsEModulePositiveBusVolt
mandatory
The measured positive upsE module voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.3 |
||||||||||||||||||||||||||
|
upsEModuleNegativeBusVolt
mandatory
The measured nepositive upsE module voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.4 |
||||||||||||||||||||||||||
|
upsEModuleTemperature
mandatory
The measured upsE module temperature from the UPS meters in 0.1 degree.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.5 |
||||||||||||||||||||||||||
|
upsEModuleWorkingMode
mandatory
The working mode of UPS modules.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.4.2.1.6 |
||||||||||||||||||||||||||
|
upsEModuleOutputCurrentR
mandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.7 |
||||||||||||||||||||||||||
|
upsEModuleOutputWattR
mandatory
The measured upsE module output watts from the UPS meters in watts.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.8 |
||||||||||||||||||||||||||
|
upsEModuleOutputLoadR
mandatory
The output load of UPS modules in %.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.9 |
||||||||||||||||||||||||||
|
upsEModuleWarningCode
mandatory
The warning code of ups modules.Please refer the warning table of 'QU,XX' for details.
|
OctetString Constraints: range: 0-15 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.10 |
||||||||||||||||||||||||||
|
upsEModuleFaultCode
mandatory
The fault code of ups modules.Please refer command 'QU,XX' for details.
|
OctetString Constraints: range: 0-15 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.11 |
||||||||||||||||||||||||||
|
upsEModuleTrapState
mandatory
the values indicate the unrestored traps.
For example, after AC fail, so the value of upsETrapState should be '1'. And then the AC restore, the value of upsEModuleTrapState should change to empty. |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.12 |
||||||||||||||||||||||||||
|
upsEModuleConfigOutputVA
mandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.13 |
||||||||||||||||||||||||||
|
upsEModuleOutputCurrentS
mandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.14 |
||||||||||||||||||||||||||
|
upsEModuleOutputCurrentT
mandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.15 |
||||||||||||||||||||||||||
|
upsEModuleOutputWattS
mandatory
The measured upsE module output watts from the UPS meters in watts.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.16 |
||||||||||||||||||||||||||
|
upsEModuleOutputWattT
mandatory
The measured upsE module output watts from the UPS meters in watts.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.17 |
||||||||||||||||||||||||||
|
upsEModuleOutputLoadS
mandatory
The output load of UPS modules in %.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.18 |
||||||||||||||||||||||||||
|
upsEModuleOutputLoadT
mandatory
The output load of UPS modules in %.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.19 |
||||||||||||||||||||||||||
|
upsEModuleOutputVAR
mandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.20 |
||||||||||||||||||||||||||
|
upsEModuleOutputVAS
mandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.21 |
||||||||||||||||||||||||||
|
upsEModuleOutputVAT
mandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
|
UPS-MIBNonNegativeInteger Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.22 |
.1.3.6.1.4.1.935.10.1.1.6.4
·
1 row entry
·
4 columns
A list of contacts table entries. The number of entries is given by the value of upsEEnvironmentContactsNum
An entry containing information applicable to a particular contact
Indexes
upsEEnvironmentContactIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
upsEEnvironmentContactIndex
mandatory
The number of environment contacts. Serves as index for environment contact table
|
UPS-MIBPositiveInteger Textual Convention: UPS-MIBPositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.6.4.1.1 |
||||||||
|
upsEEnvironmentContactType
mandatory
operation type
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.6.4.1.2 |
||||||||
|
upsEEnvironmentContactState
mandatory
The mandatory status.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.6.4.1.3 |
||||||||
|
upsEEnvironmentContactDescription
mandatory
Description of environment contact.
|
OctetStringr/w Constraints: range: 0-31 |
.1.3.6.1.4.1.935.10.1.1.6.4.1.4 |
.1.3.6.1.4.1.935.10.1.1.7.6
·
1 row entry
·
6 columns
This table describes the schedule for automatically battery test.
An entry containing information applicable to schedule test.
Indexes
upsEBatteryTestScheduleIndex
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsEBatteryTestScheduleIndex
mandatory
The index of battery test scheduled.
|
UPS-MIBPositiveInteger Textual Convention: UPS-MIBPositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.7.6.1.1 |
||||||||||||||||||
|
upsEBatteryTestScheduleDay
mandatory
The weekday or specaial day on which the UPS should start battery test.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.7.6.1.2 |
||||||||||||||||||
|
upsEBatteryTestScheduleTime
mandatory
The time that the battery test will be initiated in hh:mm format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.7.6.1.3 |
||||||||||||||||||
|
upsEBatteryTestScheduleType
mandatory
The type of battery test.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.7.6.1.5 |
||||||||||||||||||
|
upsEBatteryTestScheduleTestWithTime
mandatory
The battery time of setting time test in seconds.
|
UPS-MIBNonNegativeIntegerr/w Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.7.6.1.6 |
||||||||||||||||||
|
upsEBatteryTestScheduleSpecialDay
mandatory
The special day that the battery test will be initiated in dd/mm/yyyy format.
|
OctetStringr/w Constraints: range: 10-10 |
.1.3.6.1.4.1.935.10.1.1.7.6.1.7 |
.1.3.6.1.4.1.935.10.1.1.8.4
·
1 row entry
·
4 columns
This table describes the parametes for shutdown process when shutdown event occurs
An entry containing information applicable to a particular shutdown
event line
event line
Indexes
upsEShutdownEvent
| Column | Syntax | OID | ||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsEShutdownEvent
mandatory
The shutdown event identification
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.8.4.1.1 |
||||||||||||||||||||||||
|
upsEShutdownEventAction
mandatory
Status of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when corresponding event occured. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.8.4.1.2 |
||||||||||||||||||||||||
|
upsEShutdownwarningPeriodTime
mandatory
The Delay in seconds after the occurance of the curresponding shutdown
event, and warning message should be popped in this period. |
UPS-MIBNonNegativeIntegerr/w Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.8.4.1.3 |
||||||||||||||||||||||||
|
upsEShutdownWarningPeriodInterval
mandatory
The frequency of sending warning messages to the connected
clients when the curresponding shutdown event occurs. The value is in units of seconds. |
UPS-MIBNonNegativeIntegerr/w Textual Convention: UPS-MIBNonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.8.4.1.4 |
.1.3.6.1.4.1.935.10.1.1.8.5
·
1 row entry
·
5 columns
The table to schedule shutting down the ups by weekly
An entry containing information applicable to a particular line
Indexes
upsEControlWeeklyScheduleIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsEControlWeeklyScheduleIndex
mandatory
the index of schedule events.
|
UPS-MIBPositiveInteger Textual Convention: UPS-MIBPositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.8.5.1.1 |
||||||||||||||||
|
upsEWeeklyScheduleShutdownDay
mandatory
the weekday on which upsE shoud shutdown
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.8.5.1.2 |
||||||||||||||||
|
upsEWeeklyScheduleShutdownTime
mandatory
The time that the process of shutting down the UPS will be initiated
in hh:mm format. |
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.8.5.1.3 |
||||||||||||||||
|
upsEWeeklyScheduleRestartDay
mandatory
the weekday on which the UPS should restart.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.8.5.1.4 |
||||||||||||||||
|
upsEWeeklyScheduleRestartTime
mandatory
The time the UPS will restart in hh:mm format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.8.5.1.5 |
.1.3.6.1.4.1.935.10.1.1.8.6
·
1 row entry
·
5 columns
The table to schedule shutting down the ups.
An entry containing information applicable to a particular line.
Indexes
upsEControlSpecialDayScheduleIndex
| Column | Syntax | OID |
|---|---|---|
|
upsEControlSpecialDayScheduleIndex
mandatory
The index of special day schedule.
|
UPS-MIBPositiveInteger Textual Convention: UPS-MIBPositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.1 |
|
upsESpecialDayScheduleShutdownDay
mandatory
The special day on which UPS should shutdown with the format
of DD/MM/YYYY. |
OctetStringr/w Constraints: range: 10-10 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.2 |
|
upsESpecialDayScheduleShutdownTime
mandatory
The time that the process of shutting down the UPS will be initiated
in hh:mm format. |
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.3 |
|
upsESpecialDayScheduleRestartDay
mandatory
The special day on which the UPS should restart with the format
of DD/MM/YYYY. |
OctetStringr/w Constraints: range: 10-10 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.4 |
|
upsESpecialDayScheduleRestartTime
mandatory
The time the UPS will restart in hh:mm format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.5 |
.1.3.6.1.4.1.935.10.1.1.9.1
·
1 row entry
·
6 columns
This table list the managers'IP to send traps to.
An entry containing information applicable to a particular input line.
Indexes
upsETrapsReceiversIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
upsETrapsReceiversIndex
mandatory
The index to a trap receiver entry
|
UPS-MIBPositiveInteger Textual Convention: UPS-MIBPositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.9.1.1.1 |
||||||
|
upsETrapsReceiverAddress
mandatory
The IP address of the manager to send a trap to.
|
OctetStringr/w Constraints: range: 0-45 |
.1.3.6.1.4.1.935.10.1.1.9.1.1.2 |
||||||
|
upsETrapReceiverCommunityString
mandatory
The community name to use in the trap when
sent to the manager. |
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.935.10.1.1.9.1.1.3 |
||||||
|
upsETrapType
mandatory
The type of trap to be received by the manager.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.9.1.1.4 |
||||||
|
upsETrapsSeverityLevel
mandatory
The severity level of traps to be received by this manager.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.9.1.1.5 |
||||||
|
upsETrapReceiverDescription
mandatory
Description of trap receivers
|
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.935.10.1.1.9.1.1.6 |