.1.3.6.1.4.1.534.6.8.1.1.2 · 1 row entry · 10 columns
A list of sensor devices identification data.
The number of entries is given by sensorCount.
sensorIdentificationEntry entry .1.3.6.1.4.1.534.6.8.1.1.2.1
An entry for a sensor device identification.
Indexes
sensorIndex
Column Syntax OID
sensorIndex
A unique value for each sensor device. Its value
ranges from 1 to sensorCount.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.534.6.8.1.1.2.1.1
sensorUuid
A unique uuid value for each sensor device.
OctetString .1.3.6.1.4.1.534.6.8.1.1.2.1.2
sensorConnectionType
Sensor connection type with the device that monitors it.
ProbeConnectionType
Textual Convention: ProbeConnectionType Enumeration
Type Values:
0undefined
1internal
2wired
3wireless
.1.3.6.1.4.1.534.6.8.1.1.2.1.3
sensorAddress
Depending of the connection implementation : Modbus Slave Id, BT Mac address, ...
OctetString .1.3.6.1.4.1.534.6.8.1.1.2.1.4
sensorMonitoredBy
Parent oid device where the sensor is connected to and monitored by.
ObjectIdentifier .1.3.6.1.4.1.534.6.8.1.1.2.1.5
sensorManufacturer
The vendor name of the sensor device.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.6
sensorModel
The model name of the sensor device.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.7
sensorPartNumber
The catalog part number of the sensor device.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.8
sensorSerialNumber
The serial number of the sensor device.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.9
sensorFirmwareVersion
The firmware version of the sensor device.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.10
.1.3.6.1.4.1.534.6.8.1.1.3 · 1 row entry · 5 columns
A list of sensor devices configuration data.
The number of entries is given by sensorCount.
sensorConfigurationEntry entry .1.3.6.1.4.1.534.6.8.1.1.3.1
An entry for a sensor device configuration.
Indexes
sensorIndex
Column Syntax OID
sensorName
The friendly name of the sensor device.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.3.1.1
sensorLocation
The location of the sensor device.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.3.1.2
sensorPosition
The Position by reference to the data center aisle.
PositionTyper/w
Textual Convention: PositionType Enumeration
Type Values:
0undefined
1other
2rackRear
3rackFront
4batteryRoom
.1.3.6.1.4.1.534.6.8.1.1.3.1.3
sensorElevation
The Elevation in the rack.
ElevationTyper/w
Textual Convention: ElevationType Enumeration
Type Values:
0undefined
1other
2bottom
3middle
4top
.1.3.6.1.4.1.534.6.8.1.1.3.1.4
sensorUElevation
The elevation in the rack in count of U position from the bottom.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.3.1.5
.1.3.6.1.4.1.534.6.8.1.1.4 · 1 row entry · 6 columns
A list of sensor devices monitoring data.
The number of entries is given by sensorCount.
sensorMonitoringEntry entry .1.3.6.1.4.1.534.6.8.1.1.4.1
An entry for a sensor device monitoring.
Indexes
sensorIndex
Column Syntax OID
sensorStatus
Indicates how the sensor is communicating or not.
CommunicationStatus
Textual Convention: CommunicationStatus Enumeration
Type Values:
0unknown
2communicationOK
3communicationLost
.1.3.6.1.4.1.534.6.8.1.1.4.1.1
sensorStatusSince
UTC time in seconds since 1970/01/01 dating the sensor status last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.1.4.1.2
sensorTemperatureCount
Number of temperature probes managed by the sensor device.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.4.1.3
sensorHumidityCount
Number of humidity probes managed by the sensor device.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.4.1.4
sensorDigitalInputCount
Number of digital input probes managed by the sensor device.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.4.1.5
sensorAnalogInputCount
Number of analog input probes managed by the sensor device.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.4.1.6
.1.3.6.1.4.1.534.6.8.1.2.1 · 1 row entry · 3 columns
A list of temperature probe measurements. the number of entries
is given by the temperature count.
temperatureIdentificationEntry entry .1.3.6.1.4.1.534.6.8.1.2.1.1
An entry for a temperature probe identification.
Indexes
sensorIndex temperatureIndex
Column Syntax OID
temperatureIndex
A unique value for each temperature probe measurement. Its value
ranges from 1 to sensorTemperatureCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.8.1.2.1.1.1
temperatureUuid
A unique uuid value for each temperature.
OctetString .1.3.6.1.4.1.534.6.8.1.2.1.1.2
temperatureConnectionType
Probe connection type with the sensor that monitors it.
ProbeConnectionType
Textual Convention: ProbeConnectionType Enumeration
Type Values:
0undefined
1internal
2wired
3wireless
.1.3.6.1.4.1.534.6.8.1.2.1.1.3
.1.3.6.1.4.1.534.6.8.1.2.2 · 1 row entry · 10 columns
A list of temperature probe configuration.  The number of entries is
given by sensorTemperatureCount.
temperatureConfigurationEntry entry .1.3.6.1.4.1.534.6.8.1.2.2.1
An entry for a temperature probe configuration.
Indexes
sensorIndex temperatureIndex
Column Syntax OID
temperatureName
The friendly name of the sensor temperature probe.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.2.2.1.1
temperatureEnable
Configure the temperature acquired or not.
0:disabled, 1:enabled
EnableTyper/w
Textual Convention: EnableType Enumeration
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.2.2.1.2
temperatureOffset
Configure the offset (Minus or Plus) to be added to the acquired value
in order to correct the probe measurement error.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.3
temperatureAlarmEnable
Configure the temperature alarm depending on the thresholds evaluated or not.
0:disabled, 1:enabled
EnableTyper/w
Textual Convention: EnableType Enumeration
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.2.2.1.4
temperatureThresholdLowWarning
Low warning temperature threshold.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.5
temperatureThresholdLowCritical
Low critical temperature threshold.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.6
temperatureThresholdHighWarning
High warning temperature threshold.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.7
temperatureThresholdHighCritical
High critical temperature threshold.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.8
temperatureThresholdHysteresis
Temperature threshold hysteresis.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.9
temperatureAlarmGracePeriod
The grace period the alarm triggers after the acquired value crosses
a trigger value (in seconds).
Integer32r/w
Constraints:
range: 1-60
.1.3.6.1.4.1.534.6.8.1.2.2.1.10
.1.3.6.1.4.1.534.6.8.1.2.3 · 1 row entry · 5 columns
A list of temperature probe monitoring.  The number of entries is
given by sensorTemperatureCount.
temperatureMonitoringEntry entry .1.3.6.1.4.1.534.6.8.1.2.3.1
An entry for a temperature probe monitoring.
Indexes
sensorIndex temperatureIndex
Column Syntax OID
temperatureAlarm
Alarm set according to the realtime measure compared to the thresholds.
AlarmType
Textual Convention: AlarmType Enumeration
Type Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.8.1.2.3.1.1
temperatureAlarmChangeSince
UTC time in seconds since 1970/01/01 dating the temperature alarm last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.2.3.1.2
temperatureValue
Realtime measured value after correction with the offset.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.3.1.3
temperatureCommunicationStatus
Indicates how the temperature probe is communicating or not.
CommunicationStatus
Textual Convention: CommunicationStatus Enumeration
Type Values:
0unknown
2communicationOK
3communicationLost
.1.3.6.1.4.1.534.6.8.1.2.3.1.4
temperatureCommunicationStatusSince
UTC time in seconds since 1970/01/01 dating the temperature communication status last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.2.3.1.5
.1.3.6.1.4.1.534.6.8.1.2.4 · 1 row entry · 5 columns
A list of temperature probe monitoring Min and Max.  The number of entries is
given by sensorTemperatureCount.
temperatureMonitoringMinMaxEntry entry .1.3.6.1.4.1.534.6.8.1.2.4.1
An entry for a temperature probe monitoring Min and Max.
Indexes
sensorIndex temperatureIndex
Column Syntax OID
temperatureMinValue
Minimum value registered since the 1st connection of the sensor or the last reset.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.4.1.1
temperatureMinValueSince
UTC time in seconds since 1970/01/01 dating the temperature min value last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.2.4.1.2
temperatureMaxValue
Maximum value registered since the 1st connection of the sensor or the last reset.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.4.1.3
temperatureMaxValueSince
UTC time in seconds since 1970/01/01 dating the temperature max value last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.2.4.1.4
temperatureResetMinMax
Command that resets the min and max data with the current measure.
0:None, 1:Reset
ResetCommandTyper/w
Textual Convention: ResetCommandType Enumeration
Type Values:
0none
1reset
.1.3.6.1.4.1.534.6.8.1.2.4.1.5
.1.3.6.1.4.1.534.6.8.1.3.1 · 1 row entry · 3 columns
A list of humidity probe measurements. the number of entries
is given by the humidity count.
humidityIdentificationEntry entry .1.3.6.1.4.1.534.6.8.1.3.1.1
An entry for a humidity probe identification.
Indexes
sensorIndex humidityIndex
Column Syntax OID
humidityIndex
A unique value for each humidity probe measurement. Its value
ranges from 1 to sensorhumidityCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.8.1.3.1.1.1
humidityUuid
A unique uuid value for each humidity.
OctetString .1.3.6.1.4.1.534.6.8.1.3.1.1.2
humidityConnectionType
Probe connection type with the sensor that monitors it.
ProbeConnectionType
Textual Convention: ProbeConnectionType Enumeration
Type Values:
0undefined
1internal
2wired
3wireless
.1.3.6.1.4.1.534.6.8.1.3.1.1.3
.1.3.6.1.4.1.534.6.8.1.3.2 · 1 row entry · 10 columns
A list of humidity probe configuration.  The number of entries is
given by sensorhumidityCount.
humidityConfigurationEntry entry .1.3.6.1.4.1.534.6.8.1.3.2.1
An entry for a humidity probe configuration.
Indexes
sensorIndex humidityIndex
Column Syntax OID
humidityName
The friendly name of the sensor humidity probe.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.3.2.1.1
humidityEnable
Configure the humidity acquired or not.
0:disabled, 1:enabled
EnableTyper/w
Textual Convention: EnableType Enumeration
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.3.2.1.2
humidityOffset
Configure the offset (Minus or Plus) to be added to the acquired value
in order to correct the probe measurement error. in tenth of % units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.3
humidityAlarmEnable
Configure the humidity alarm depending on the thresholds evaluated or not.
0:disabled, 1:enabled
EnableTyper/w
Textual Convention: EnableType Enumeration
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.3.2.1.4
humidityThresholdLowWarning
Low warning humidity threshold in tenth of % units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.5
humidityThresholdLowCritical
Low critical humidity threshold in tenth of % units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.6
humidityThresholdHighWarning
High warning humidity threshold in tenth of % units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.7
humidityThresholdHighCritical
High critical humidity threshold in tenth of % units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.8
humidityThresholdHysteresis
humidity threshold hysteresis in tenth of % units.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.9
humidityAlarmGracePeriod
The grace period the alarm triggers after the acquired value crosses
a trigger value (in seconds).
Integer32r/w
Constraints:
range: 1-60
.1.3.6.1.4.1.534.6.8.1.3.2.1.10
.1.3.6.1.4.1.534.6.8.1.3.3 · 1 row entry · 5 columns
A list of humidity probe monitoring.  The number of entries is
given by sensorhumidityCount.
humidityMonitoringEntry entry .1.3.6.1.4.1.534.6.8.1.3.3.1
An entry for a humidity probe monitoring.
Indexes
sensorIndex humidityIndex
Column Syntax OID
humidityAlarm
Alarm set according to the realtime measure compared to the thresholds.
AlarmType
Textual Convention: AlarmType Enumeration
Type Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.8.1.3.3.1.1
humidityAlarmChangeSince
UTC time in seconds since 1970/01/01 dating the humidity alarm last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.3.3.1.2
humidityValue
Realtime measured value after correction with the offset. in tenth of % units.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.3.1.3
humidityCommunicationStatus
Indicates how the humidity probe is communicating or not.
CommunicationStatus
Textual Convention: CommunicationStatus Enumeration
Type Values:
0unknown
2communicationOK
3communicationLost
.1.3.6.1.4.1.534.6.8.1.3.3.1.4
humidityCommunicationStatusSince
UTC time in seconds since 1970/01/01 dating the humidity communication status last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.3.3.1.5
.1.3.6.1.4.1.534.6.8.1.3.4 · 1 row entry · 5 columns
A list of humidity probe monitoring Min and Max.  The number of entries is
given by sensorhumidityCount.
humidityMonitoringMinMaxEntry entry .1.3.6.1.4.1.534.6.8.1.3.4.1
An entry for a humidity probe monitoring Min and Max.
Indexes
sensorIndex humidityIndex
Column Syntax OID
humidityMinValue
Minimum value registered since the 1st connection of the sensor or the last reset.
in tenth of % units.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.4.1.1
humidityMinValueSince
UTC time in seconds since 1970/01/01 dating the humidity min value last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.3.4.1.2
humidityMaxValue
Maximum value registered since the 1st connection of the sensor or the last reset.
in tenth of % units.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.4.1.3
humidityMaxValueSince
UTC time in seconds since 1970/01/01 dating the humidity max value last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.3.4.1.4
humidityResetMinMax
Command that resets the min and max data with the current measure.
0:None, 1:Reset
ResetCommandTyper/w
Textual Convention: ResetCommandType Enumeration
Type Values:
0none
1reset
.1.3.6.1.4.1.534.6.8.1.3.4.1.5
.1.3.6.1.4.1.534.6.8.1.4.1 · 1 row entry · 3 columns
A list of digital input probe measurements.  The number of entries is
given by sensorDigitalInputCount.
digitalInputIdentificationEntry entry .1.3.6.1.4.1.534.6.8.1.4.1.1
An entry for a digital input identification.
Indexes
sensorIndex digitalInputIndex
Column Syntax OID
digitalInputIndex
A unique value for each digital input probe measurement. Its value
ranges from 1 to sensorDigitalInputCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.8.1.4.1.1.1
digitalInputUuid
A unique uuid value for each digital Input.
OctetString .1.3.6.1.4.1.534.6.8.1.4.1.1.2
digitalInputConnectionType
Probe connection type with the sensor that monitors it.
ProbeConnectionType
Textual Convention: ProbeConnectionType Enumeration
Type Values:
0undefined
1internal
2wired
3wireless
.1.3.6.1.4.1.534.6.8.1.4.1.1.3
.1.3.6.1.4.1.534.6.8.1.4.2 · 1 row entry · 6 columns
A list of digital input probe configuration.  The number of entries is
given by sensorDigitalInputCount.
digitalInputConfigurationEntry entry .1.3.6.1.4.1.534.6.8.1.4.2.1
An entry for a digital input probe configuration.
Indexes
sensorIndex digitalInputIndex
Column Syntax OID
digitalInputName
The friendly name of the digital input probe.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.4.2.1.1
digitalInputEnable
Configure the digital input acquired or not.
0:disabled, 1:enabled
EnableTyper/w
Textual Convention: EnableType Enumeration
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.4.2.1.2
digitalInputPolarity
Configure the digitalInput polarity.
0 : Normally opened, 1 : Normally closed
PolarityTyper/w
Textual Convention: PolarityType Enumeration
Type Values:
0normallyOpened
1normallyClosed
.1.3.6.1.4.1.534.6.8.1.4.2.1.3
digitalInputAlarmEnable
Configure the digitalInput alarm depending on the polarity evaluated or not.
0:disabled, 1:enabled
EnableTyper/w
Textual Convention: EnableType Enumeration
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.4.2.1.4
digitalInputAlarmSeverity
Configure the alarm severity.
AlarmSeverityTyper/w
Textual Convention: AlarmSeverityType Enumeration
Type Values:
1informational
2warning
3critical
.1.3.6.1.4.1.534.6.8.1.4.2.1.5
digitalInputAlarmGracePeriod
The delay the alarm triggers when the state change event occurs (in seconds).
Integer32r/w
Constraints:
range: 1-60
.1.3.6.1.4.1.534.6.8.1.4.2.1.6
.1.3.6.1.4.1.534.6.8.1.4.3 · 1 row entry · 6 columns
A list of digital input probee monitoring.  The number of entries is
given by sensorDigitalInputCount.
digitalInputMonitoringEntry entry .1.3.6.1.4.1.534.6.8.1.4.3.1
An entry for a digital Input probe.
Indexes
sensorIndex digitalInputIndex
Column Syntax OID
digitalInputAlarm
Alarm set according to the polarity and alarm severity configuration.
AlarmLevelType
Textual Convention: AlarmLevelType Enumeration
Type Values:
0good
1informational
2warning
3critical
.1.3.6.1.4.1.534.6.8.1.4.3.1.1
digitalInputAlarmChangeSince
UTC time in seconds since 1970/01/01 dating the digital input alarm last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.4.3.1.2
digitalInputState
Measure of the digital input after applying the polarity configured.
0 : Inactive, 1 : Active
StateType
Textual Convention: StateType Enumeration
Type Values:
0inactive
1active
.1.3.6.1.4.1.534.6.8.1.4.3.1.3
digitalInputStateSince
UTC time in seconds since 1970/01/01 dating the digital input state last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.4.3.1.4
digitalInputCommunicationStatus
Indicates how the digital input is communicating or not.
CommunicationStatus
Textual Convention: CommunicationStatus Enumeration
Type Values:
0unknown
2communicationOK
3communicationLost
.1.3.6.1.4.1.534.6.8.1.4.3.1.5
digitalInputCommunicationStatusSince
UTC time in seconds since 1970/01/01 dating the digital input communication status last change.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.8.1.4.3.1.6