EATON-SENSOR-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
14
Rows
14
Columns
82
.1.3.6.1.4.1.534.6.8.1.1.2
·
1 row entry
·
10 columns
A list of sensor devices identification data. The number of entries is given by sensorCount.
An entry for a sensor device identification.
Indexes
sensorIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
sensorIndex
A unique value for each sensor device. Its value
ranges from 1 to sensorCount. |
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.534.6.8.1.1.2.1.1 |
||||||||
|
sensorUuid
A unique uuid value for each sensor device.
|
OctetString | .1.3.6.1.4.1.534.6.8.1.1.2.1.2 |
||||||||
|
sensorConnectionType
Sensor connection type with the device that monitors it.
|
ProbeConnectionType Textual Convention: ProbeConnectionType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.1.2.1.3 |
||||||||
|
sensorAddress
Depending of the connection implementation : Modbus Slave Id, BT Mac address, ...
|
OctetString | .1.3.6.1.4.1.534.6.8.1.1.2.1.4 |
||||||||
|
sensorMonitoredBy
Parent oid device where the sensor is connected to and monitored by.
|
ObjectIdentifier | .1.3.6.1.4.1.534.6.8.1.1.2.1.5 |
||||||||
|
sensorManufacturer
The vendor name of the sensor device.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.1.2.1.6 |
||||||||
|
sensorModel
The model name of the sensor device.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.1.2.1.7 |
||||||||
|
sensorPartNumber
The catalog part number of the sensor device.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.1.2.1.8 |
||||||||
|
sensorSerialNumber
The serial number of the sensor device.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.1.2.1.9 |
||||||||
|
sensorFirmwareVersion
The firmware version of the sensor device.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.1.2.1.10 |
sensorConfigurationTable
table.1.3.6.1.4.1.534.6.8.1.1.3
·
1 row entry
·
5 columns
A list of sensor devices configuration data. The number of entries is given by sensorCount.
An entry for a sensor device configuration.
Indexes
sensorIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
sensorName
The friendly name of the sensor device.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.1.3.1.1 |
||||||||||
|
sensorLocation
The location of the sensor device.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.1.3.1.2 |
||||||||||
|
sensorPosition
The Position by reference to the data center aisle.
|
PositionTyper/w Textual Convention: PositionType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.1.3.1.3 |
||||||||||
|
sensorElevation
The Elevation in the rack.
|
ElevationTyper/w Textual Convention: ElevationType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.1.3.1.4 |
||||||||||
|
sensorUElevation
The elevation in the rack in count of U position from the bottom.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.1.3.1.5 |
sensorMonitoringTable
table.1.3.6.1.4.1.534.6.8.1.1.4
·
1 row entry
·
6 columns
A list of sensor devices monitoring data. The number of entries is given by sensorCount.
An entry for a sensor device monitoring.
Indexes
sensorIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
sensorStatus
Indicates how the sensor is communicating or not.
|
CommunicationStatus Textual Convention: CommunicationStatus EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.1.4.1.1 |
||||||
|
sensorStatusSince
UTC time in seconds since 1970/01/01 dating the sensor status last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.1.4.1.2 |
||||||
|
sensorTemperatureCount
Number of temperature probes managed by the sensor device.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.1.4.1.3 |
||||||
|
sensorHumidityCount
Number of humidity probes managed by the sensor device.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.1.4.1.4 |
||||||
|
sensorDigitalInputCount
Number of digital input probes managed by the sensor device.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.1.4.1.5 |
||||||
|
sensorAnalogInputCount
Number of analog input probes managed by the sensor device.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.1.4.1.6 |
.1.3.6.1.4.1.534.6.8.1.2.1
·
1 row entry
·
3 columns
A list of temperature probe measurements. the number of entries is given by the temperature count.
An entry for a temperature probe identification.
Indexes
sensorIndex temperatureIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
temperatureIndex
A unique value for each temperature probe measurement. Its value
ranges from 1 to sensorTemperatureCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.8.1.2.1.1.1 |
||||||||
|
temperatureUuid
A unique uuid value for each temperature.
|
OctetString | .1.3.6.1.4.1.534.6.8.1.2.1.1.2 |
||||||||
|
temperatureConnectionType
Probe connection type with the sensor that monitors it.
|
ProbeConnectionType Textual Convention: ProbeConnectionType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.2.1.1.3 |
.1.3.6.1.4.1.534.6.8.1.2.2
·
1 row entry
·
10 columns
A list of temperature probe configuration. The number of entries is given by sensorTemperatureCount.
An entry for a temperature probe configuration.
Indexes
sensorIndex temperatureIndex
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
temperatureName
The friendly name of the sensor temperature probe.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.2.2.1.1 |
||||
|
temperatureEnable
Configure the temperature acquired or not.
0:disabled, 1:enabled |
EnableTyper/w Textual Convention: EnableType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.2.2.1.2 |
||||
|
temperatureOffset
Configure the offset (Minus or Plus) to be added to the acquired value
in order to correct the probe measurement error. See temperatureUnit data for the units. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.2.1.3 |
||||
|
temperatureAlarmEnable
Configure the temperature alarm depending on the thresholds evaluated or not.
0:disabled, 1:enabled |
EnableTyper/w Textual Convention: EnableType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.2.2.1.4 |
||||
|
temperatureThresholdLowWarning
Low warning temperature threshold.
See temperatureUnit data for the units. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.2.1.5 |
||||
|
temperatureThresholdLowCritical
Low critical temperature threshold.
See temperatureUnit data for the units. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.2.1.6 |
||||
|
temperatureThresholdHighWarning
High warning temperature threshold.
See temperatureUnit data for the units. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.2.1.7 |
||||
|
temperatureThresholdHighCritical
High critical temperature threshold.
See temperatureUnit data for the units. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.2.1.8 |
||||
|
temperatureThresholdHysteresis
Temperature threshold hysteresis.
See temperatureUnit data for the units. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.2.1.9 |
||||
|
temperatureAlarmGracePeriod
The grace period the alarm triggers after the acquired value crosses
a trigger value (in seconds). |
Integer32r/w Constraints: range: 1-60 |
.1.3.6.1.4.1.534.6.8.1.2.2.1.10 |
.1.3.6.1.4.1.534.6.8.1.2.3
·
1 row entry
·
5 columns
A list of temperature probe monitoring. The number of entries is given by sensorTemperatureCount.
An entry for a temperature probe monitoring.
Indexes
sensorIndex temperatureIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
temperatureAlarm
Alarm set according to the realtime measure compared to the thresholds.
|
AlarmType Textual Convention: AlarmType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.2.3.1.1 |
||||||||||
|
temperatureAlarmChangeSince
UTC time in seconds since 1970/01/01 dating the temperature alarm last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.2.3.1.2 |
||||||||||
|
temperatureValue
Realtime measured value after correction with the offset.
See temperatureUnit data for the units. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.3.1.3 |
||||||||||
|
temperatureCommunicationStatus
Indicates how the temperature probe is communicating or not.
|
CommunicationStatus Textual Convention: CommunicationStatus EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.2.3.1.4 |
||||||||||
|
temperatureCommunicationStatusSince
UTC time in seconds since 1970/01/01 dating the temperature communication status last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.2.3.1.5 |
.1.3.6.1.4.1.534.6.8.1.2.4
·
1 row entry
·
5 columns
A list of temperature probe monitoring Min and Max. The number of entries is given by sensorTemperatureCount.
An entry for a temperature probe monitoring Min and Max.
Indexes
sensorIndex temperatureIndex
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
temperatureMinValue
Minimum value registered since the 1st connection of the sensor or the last reset.
See temperatureUnit data for the units. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.4.1.1 |
||||
|
temperatureMinValueSince
UTC time in seconds since 1970/01/01 dating the temperature min value last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.2.4.1.2 |
||||
|
temperatureMaxValue
Maximum value registered since the 1st connection of the sensor or the last reset.
See temperatureUnit data for the units. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.2.4.1.3 |
||||
|
temperatureMaxValueSince
UTC time in seconds since 1970/01/01 dating the temperature max value last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.2.4.1.4 |
||||
|
temperatureResetMinMax
Command that resets the min and max data with the current measure.
0:None, 1:Reset |
ResetCommandTyper/w Textual Convention: ResetCommandType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.2.4.1.5 |
.1.3.6.1.4.1.534.6.8.1.3.1
·
1 row entry
·
3 columns
A list of humidity probe measurements. the number of entries is given by the humidity count.
An entry for a humidity probe identification.
Indexes
sensorIndex humidityIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
humidityIndex
A unique value for each humidity probe measurement. Its value
ranges from 1 to sensorhumidityCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.8.1.3.1.1.1 |
||||||||
|
humidityUuid
A unique uuid value for each humidity.
|
OctetString | .1.3.6.1.4.1.534.6.8.1.3.1.1.2 |
||||||||
|
humidityConnectionType
Probe connection type with the sensor that monitors it.
|
ProbeConnectionType Textual Convention: ProbeConnectionType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.3.1.1.3 |
.1.3.6.1.4.1.534.6.8.1.3.2
·
1 row entry
·
10 columns
A list of humidity probe configuration. The number of entries is given by sensorhumidityCount.
An entry for a humidity probe configuration.
Indexes
sensorIndex humidityIndex
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
humidityName
The friendly name of the sensor humidity probe.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.3.2.1.1 |
||||
|
humidityEnable
Configure the humidity acquired or not.
0:disabled, 1:enabled |
EnableTyper/w Textual Convention: EnableType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.3.2.1.2 |
||||
|
humidityOffset
Configure the offset (Minus or Plus) to be added to the acquired value
in order to correct the probe measurement error. in tenth of % units. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.2.1.3 |
||||
|
humidityAlarmEnable
Configure the humidity alarm depending on the thresholds evaluated or not.
0:disabled, 1:enabled |
EnableTyper/w Textual Convention: EnableType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.3.2.1.4 |
||||
|
humidityThresholdLowWarning
Low warning humidity threshold in tenth of % units.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.2.1.5 |
||||
|
humidityThresholdLowCritical
Low critical humidity threshold in tenth of % units.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.2.1.6 |
||||
|
humidityThresholdHighWarning
High warning humidity threshold in tenth of % units.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.2.1.7 |
||||
|
humidityThresholdHighCritical
High critical humidity threshold in tenth of % units.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.2.1.8 |
||||
|
humidityThresholdHysteresis
humidity threshold hysteresis in tenth of % units.
|
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.2.1.9 |
||||
|
humidityAlarmGracePeriod
The grace period the alarm triggers after the acquired value crosses
a trigger value (in seconds). |
Integer32r/w Constraints: range: 1-60 |
.1.3.6.1.4.1.534.6.8.1.3.2.1.10 |
humidityMonitoringTable
table.1.3.6.1.4.1.534.6.8.1.3.3
·
1 row entry
·
5 columns
A list of humidity probe monitoring. The number of entries is given by sensorhumidityCount.
An entry for a humidity probe monitoring.
Indexes
sensorIndex humidityIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
humidityAlarm
Alarm set according to the realtime measure compared to the thresholds.
|
AlarmType Textual Convention: AlarmType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.3.3.1.1 |
||||||||||
|
humidityAlarmChangeSince
UTC time in seconds since 1970/01/01 dating the humidity alarm last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.3.3.1.2 |
||||||||||
|
humidityValue
Realtime measured value after correction with the offset. in tenth of % units.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.3.1.3 |
||||||||||
|
humidityCommunicationStatus
Indicates how the humidity probe is communicating or not.
|
CommunicationStatus Textual Convention: CommunicationStatus EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.3.3.1.4 |
||||||||||
|
humidityCommunicationStatusSince
UTC time in seconds since 1970/01/01 dating the humidity communication status last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.3.3.1.5 |
.1.3.6.1.4.1.534.6.8.1.3.4
·
1 row entry
·
5 columns
A list of humidity probe monitoring Min and Max. The number of entries is given by sensorhumidityCount.
An entry for a humidity probe monitoring Min and Max.
Indexes
sensorIndex humidityIndex
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
humidityMinValue
Minimum value registered since the 1st connection of the sensor or the last reset.
in tenth of % units. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.4.1.1 |
||||
|
humidityMinValueSince
UTC time in seconds since 1970/01/01 dating the humidity min value last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.3.4.1.2 |
||||
|
humidityMaxValue
Maximum value registered since the 1st connection of the sensor or the last reset.
in tenth of % units. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.8.1.3.4.1.3 |
||||
|
humidityMaxValueSince
UTC time in seconds since 1970/01/01 dating the humidity max value last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.3.4.1.4 |
||||
|
humidityResetMinMax
Command that resets the min and max data with the current measure.
0:None, 1:Reset |
ResetCommandTyper/w Textual Convention: ResetCommandType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.3.4.1.5 |
.1.3.6.1.4.1.534.6.8.1.4.1
·
1 row entry
·
3 columns
A list of digital input probe measurements. The number of entries is given by sensorDigitalInputCount.
An entry for a digital input identification.
Indexes
sensorIndex digitalInputIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
digitalInputIndex
A unique value for each digital input probe measurement. Its value
ranges from 1 to sensorDigitalInputCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.8.1.4.1.1.1 |
||||||||
|
digitalInputUuid
A unique uuid value for each digital Input.
|
OctetString | .1.3.6.1.4.1.534.6.8.1.4.1.1.2 |
||||||||
|
digitalInputConnectionType
Probe connection type with the sensor that monitors it.
|
ProbeConnectionType Textual Convention: ProbeConnectionType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.4.1.1.3 |
.1.3.6.1.4.1.534.6.8.1.4.2
·
1 row entry
·
6 columns
A list of digital input probe configuration. The number of entries is given by sensorDigitalInputCount.
An entry for a digital input probe configuration.
Indexes
sensorIndex digitalInputIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
digitalInputName
The friendly name of the digital input probe.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.8.1.4.2.1.1 |
||||||
|
digitalInputEnable
Configure the digital input acquired or not.
0:disabled, 1:enabled |
EnableTyper/w Textual Convention: EnableType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.4.2.1.2 |
||||||
|
digitalInputPolarity
Configure the digitalInput polarity.
0 : Normally opened, 1 : Normally closed |
PolarityTyper/w Textual Convention: PolarityType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.4.2.1.3 |
||||||
|
digitalInputAlarmEnable
Configure the digitalInput alarm depending on the polarity evaluated or not.
0:disabled, 1:enabled |
EnableTyper/w Textual Convention: EnableType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.4.2.1.4 |
||||||
|
digitalInputAlarmSeverity
Configure the alarm severity.
|
AlarmSeverityTyper/w Textual Convention: AlarmSeverityType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.4.2.1.5 |
||||||
|
digitalInputAlarmGracePeriod
The delay the alarm triggers when the state change event occurs (in seconds).
|
Integer32r/w Constraints: range: 1-60 |
.1.3.6.1.4.1.534.6.8.1.4.2.1.6 |
.1.3.6.1.4.1.534.6.8.1.4.3
·
1 row entry
·
6 columns
A list of digital input probee monitoring. The number of entries is given by sensorDigitalInputCount.
An entry for a digital Input probe.
Indexes
sensorIndex digitalInputIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
digitalInputAlarm
Alarm set according to the polarity and alarm severity configuration.
|
AlarmLevelType Textual Convention: AlarmLevelType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.4.3.1.1 |
||||||||
|
digitalInputAlarmChangeSince
UTC time in seconds since 1970/01/01 dating the digital input alarm last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.4.3.1.2 |
||||||||
|
digitalInputState
Measure of the digital input after applying the polarity configured.
0 : Inactive, 1 : Active |
StateType Textual Convention: StateType EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.4.3.1.3 |
||||||||
|
digitalInputStateSince
UTC time in seconds since 1970/01/01 dating the digital input state last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.4.3.1.4 |
||||||||
|
digitalInputCommunicationStatus
Indicates how the digital input is communicating or not.
|
CommunicationStatus Textual Convention: CommunicationStatus EnumerationType Values:
|
.1.3.6.1.4.1.534.6.8.1.4.3.1.5 |
||||||||
|
digitalInputCommunicationStatusSince
UTC time in seconds since 1970/01/01 dating the digital input communication status last change.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.8.1.4.3.1.6 |