humidityAlarmGracePeriod
EATON-SENSOR-MIB ·
.1.3.6.1.4.1.534.6.8.1.3.2.1.10
Object
column
r/w
Integer32
The grace period the alarm triggers after the acquired value crosses a trigger value (in seconds).
Context
- MIB
- EATON-SENSOR-MIB
- OID
.1.3.6.1.4.1.534.6.8.1.3.2.1.10- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- humidityConfigurationEntry
- Table
- humidityConfigurationTable
- Siblings
- 9
Syntax
Integer32
Values & Constraints
Object Constraints
range: 1-60
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| humidityName The friendly name of the sensor humidity probe. | column | OctetString | .1.3.6.1.4.1.534.6.8.1.3.2.1.1 |
| humidityEnable Configure the humidity acquired or not.
0:disabled, 1:enabled | column | EnableType | .1.3.6.1.4.1.534.6.8.1.3.2.1.2 |
| humidityOffset Configure the offset (Minus or Plus) to be added to the acquired value
in order to correct the probe measurement error. in tenth of % units. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.8.1.3.2.1.3 |
| humidityAlarmEnable Configure the humidity alarm depending on the thresholds evaluated or not.
0:disabled, 1:enabled | column | EnableType | .1.3.6.1.4.1.534.6.8.1.3.2.1.4 |
| humidityThresholdLowWarning Low warning humidity threshold in tenth of % units. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.8.1.3.2.1.5 |
| humidityThresholdLowCritical Low critical humidity threshold in tenth of % units. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.8.1.3.2.1.6 |
| humidityThresholdHighWarning High warning humidity threshold in tenth of % units. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.8.1.3.2.1.7 |
| humidityThresholdHighCritical High critical humidity threshold in tenth of % units. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.8.1.3.2.1.8 |
| humidityThresholdHysteresis humidity threshold hysteresis in tenth of % units. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.8.1.3.2.1.9 |