EATON-PDU-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
8
Rows
8
Columns
38
pduInputTable
table.1.3.6.1.4.1.534.6.6.4.1.1.2.8
·
1 row entry
·
4 columns
A list of input table entries. The number of entries is given by the value of pduInputNumPhases.
An entry containing information applicable to a
particular input phase.
particular input phase.
Indexes
pduInputPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
pduInputPhaseIndex
The input line identifier.
|
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1 |
|
pduInputPhaseVoltage
The present input voltage for this phase.
|
Volts RMSNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2 |
|
pduInputPhaseCurrent
The present input current for this phase.
|
0.1 Amps RMSNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3 |
|
pduInputPhasePercentLoad
The percentage of the pdu power capacity presently
being used on this line, normally based on the ratio of pduInputPhaseCurrent to the rated input current. |
percentInteger32 Constraints: range: 0-200 |
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4 |
pduOutputTable
table.1.3.6.1.4.1.534.6.6.4.1.1.3.9
·
1 row entry
·
4 columns
A list of output table entries. The number of entries is given by the value of pduOutputNumPhases.
An entry containing information applicable to a
particular output phase.
particular output phase.
Indexes
pduOutputPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
pduOutputPhaseIndex
The output line identifier.
|
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1 |
|
pduOutputPhaseVoltage
The present output voltage for this phase.
|
Volts RMSNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2 |
|
pduOutputPhaseCurrent
The present output current for this phase.
|
0.1 Amps RMSNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3 |
|
pduOutputPhasePercentLoad
The percentage of the pdu power capacity presently
being used on this line, normally based on the ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent. |
percentInteger32 Constraints: range: 0-200 |
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4 |
panelRatingsTable
table.1.3.6.1.4.1.534.6.6.4.1.2.1
·
1 row entry
·
6 columns
A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
An entry containing information applicable to a
particular output phase.
particular output phase.
Indexes
panelNumber
| Column | Syntax | OID |
|---|---|---|
|
panelNumber
Index for the Panel Ratings and Meters tables.
Corresponds to the physical panel number in the PDU system. There must be a #1. The maximum value is 16. Panels are not required to be numbered sequentially. |
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.1 |
|
panelRatedVoltage
The nominal Voltage of this panel (as distributed
to the breakers or subfeeds). This is either Line-to-Line or Line-to-Neutral, as indicated in panelVoltageUnits. |
Volts RMSPositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.2 |
|
panelRatedBreakerCurrent
The rated current value for one panel (input) phase
at full load (100%). This is set by the panel's input breaker; if there is no input breaker for this panel, then this object is not accessible. |
0.1 Amps RMSPositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.3 |
|
panelNumPhases
The number of lines (phases) for this panel.
|
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.4 |
|
panelNumBreakers
The number of breakers contained in this panel.
This determines the number of rows found in the breaker tables. |
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.5 |
|
panelVoltageUnits
Indicates whether the panelPhaseVoltage readings are
'Vrms Line-Line' or 'Vrms Line-Neutral'. |
OctetString Constraints: range: 0-31 |
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.6 |
panelMetersTable
table.1.3.6.1.4.1.534.6.6.4.1.2.2
·
1 row entry
·
7 columns
A sparsely populated (ie, not sequentially numbered) table of ratings for each panel. The number of entries is given by the value of pduNumPanels.
An entry containing meter readings applicable to a
particular panel.
particular panel.
Indexes
panelNumber
| Column | Syntax | OID |
|---|---|---|
|
panelTotalKilowattHours
The accumulated kilowatt-hours for this panel
since it was commissioned and put into service, or since the last reset of the system KHW measures. |
KWHNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.1 |
|
panelMonthlyKilowattHours
The accumulated kilowatt-hours for this panel
since the beginning of this calendar month, or since the last reset of the system KHW measures. |
KWHNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.2 |
|
panelYtdKilowattHours
The accumulated kilowatt-hours for this panel
since the beginning of this calendar year (YTD), or since the last reset of the system KHW measures. |
KWHNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.3 |
|
panelVA
The present VA (input) demand of this panel.
|
VANonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.4 |
|
panelPower
The present power (input) demand of this panel.
|
WattsNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.5 |
|
panelPowerFactor
The input power factor for this panel.
Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf. |
pf * 100Integer32 Constraints: range: -100-100 |
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.6 |
|
panelNeutralCurrent
The present neutral phase current for this panel.
|
0.1 Amps RMSNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.7 |
panelPhaseMetersTable
table.1.3.6.1.4.1.534.6.6.4.1.2.3
·
1 row entry
·
4 columns
A sparsely populated (ie, not sequentially panel numbered) table of ratings for each panel. The number of entries is given by the sum of panelNumPhases for pduNumPanels.
An entry containing meter readings applicable to a
particular phase of a particular panel.
particular phase of a particular panel.
Indexes
panelNumber panelPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
panelPhaseIndex
The line or phase identifier.
|
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.1 |
|
panelPhaseVoltage
The present voltage for this phase.
|
Volts RMSNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.2 |
|
panelPhaseCurrent
The present current for this phase.
|
0.1 Amps RMSNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.3 |
|
panelPhasePercentLoad
The percentage of the panel power capacity presently
being used on this line, normally based on the ratio of panelPhaseCurrent to the rated phase current. |
percentInteger32 Constraints: range: 0-200 |
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.4 |
breakerRatingsTable
table.1.3.6.1.4.1.534.6.6.4.1.3.1
·
1 row entry
·
4 columns
A sparsely populated (ie, not sequentially numbered) table of ratings and fixed values for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
An entry containing information applicable to a
particular output phase.
particular output phase.
Indexes
panelNumber breakerNumber
| Column | Syntax | OID |
|---|---|---|
|
breakerNumber
Index for the Breaker Ratings and Meters tables.
Corresponds to the physical breaker number in the PDU system. Breakers are not required to be numbered sequentially. |
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.1 |
|
breakerName
Name given by the administrator to identify this breaker.
|
OctetString Constraints: range: 0-31 |
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.2 |
|
breakerRatedCurrent
The rated current value of this breaker (for one phase)
at full load (100%). |
0.1 Amps RMSPositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.3 |
|
breakerNumPhases
The number of lines (phases) for this breaker.
|
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.4 |
breakerMetersTable
table.1.3.6.1.4.1.534.6.6.4.1.3.2
·
1 row entry
·
3 columns
A sparsely populated (ie, not sequentially numbered) table of ratings for each breaker. The number of entries is given by the value of panelNumBreakers for this panel.
An entry containing meter readings applicable to a
particular breaker.
particular breaker.
Indexes
panelNumber breakerNumber
| Column | Syntax | OID |
|---|---|---|
|
breakerTotalKilowattHours
The accumulated kilowatt-hours for this breaker
since it was commissioned and put into service, or since the last reset of the panel KHW measures. |
KWHNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.1 |
|
breakerMonthlyKilowattHours
The accumulated kilowatt-hours for this breaker
since the beginning of this calendar month, or since the last reset of the panel KHW measures. |
KWHNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.2 |
|
breakerYtdKilowattHours
The accumulated kilowatt-hours for this breaker
since the beginning of this calendar year (YTD), or since the last reset of the panel KHW measures. |
KWHNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.3 |
breakerPhaseMetersTable
table.1.3.6.1.4.1.534.6.6.4.1.3.3
·
1 row entry
·
6 columns
A sparsely populated (ie, not sequentially breaker numbered) table of ratings for each breaker. The number of entries is given by the sum of breakerNumPhases for panelNumBreakers for all panels (pduNumPanels).
An entry containing meter readings applicable to a particular
phase of a particular breaker on a particular panel.
phase of a particular breaker on a particular panel.
Indexes
panelNumber breakerNumber breakerPhaseIndex
| Column | Syntax | OID |
|---|---|---|
|
breakerPhaseIndex
The line or phase identifier.
|
PositiveInteger Textual Convention: PositiveInteger Integer32Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.1 |
|
breakerPhaseVA
The present VA (input) demand of this phase on
this breaker. |
VANonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.2 |
|
breakerPhasePower
The present power (input) demand of phase on
this breaker. |
WattsNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.3 |
|
breakerPhasePowerFactor
The input power factor for this phase on this breaker.
Varies from -1.00 to 1.00, multiplied by 100. If negative values are used, they indicate lagging pf. |
pf * 100Integer32 Constraints: range: -100-100 |
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.4 |
|
breakerPhaseCurrent
The present current for this phase of this breaker.
|
0.1 Amps RMSNonNegativeInteger Textual Convention: NonNegativeInteger Integer32Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.5 |
|
breakerPhasePercentLoad
The percentage of the breaker power capacity presently
being used on this line, normally based on the ratio of breakerPhaseCurrent to the breakerRatedCurrent. |
percentInteger32 Constraints: range: 0-200 |
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.6 |