EATON-PDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
8
Rows
8
Columns
38
.1.3.6.1.4.1.534.6.6.4.1.1.2.8 · 1 row entry · 4 columns
A list of input table entries.  The number of entries
is given by the value of pduInputNumPhases.
pduInputEntry entry .1.3.6.1.4.1.534.6.6.4.1.1.2.8.1
An entry containing information applicable to a
particular input phase.
Indexes
pduInputPhaseIndex
Column Syntax OID
pduInputPhaseIndex
The input line identifier.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1
pduInputPhaseVoltage
The present input voltage for this phase.
Volts RMSNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2
pduInputPhaseCurrent
The present input current for this phase.
0.1 Amps RMSNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3
pduInputPhasePercentLoad
The percentage of the pdu power capacity presently
being used on this line, normally based on the
ratio of pduInputPhaseCurrent to the rated input current.
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4
.1.3.6.1.4.1.534.6.6.4.1.1.3.9 · 1 row entry · 4 columns
A list of output table entries.  The number of
entries is given by the value of pduOutputNumPhases.
pduOutputEntry entry .1.3.6.1.4.1.534.6.6.4.1.1.3.9.1
An entry containing information applicable to a
particular output phase.
Indexes
pduOutputPhaseIndex
Column Syntax OID
pduOutputPhaseIndex
The output line identifier.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1
pduOutputPhaseVoltage
The present output voltage for this phase.
Volts RMSNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2
pduOutputPhaseCurrent
The present output current for this phase.
0.1 Amps RMSNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3
pduOutputPhasePercentLoad
The percentage of the pdu power capacity presently
being used on this line, normally based on the
ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent.
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4
.1.3.6.1.4.1.534.6.6.4.1.2.1 · 1 row entry · 6 columns
A sparsely populated (ie, not sequentially numbered) 
table of ratings for each panel.  The number of
entries is given by the value of pduNumPanels.
panelRatingsEntry entry .1.3.6.1.4.1.534.6.6.4.1.2.1.1
An entry containing information applicable to a
particular output phase.
Indexes
panelNumber
Column Syntax OID
panelNumber
Index for the Panel Ratings and Meters tables.
Corresponds to the physical panel number in the
PDU system.
There must be a #1. The maximum value is 16.
Panels are not required to be numbered sequentially.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.1
panelRatedVoltage
The nominal Voltage of this panel (as distributed
to the breakers or subfeeds).
This is either Line-to-Line or Line-to-Neutral,
as indicated in panelVoltageUnits.
Volts RMSPositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.2
panelRatedBreakerCurrent
The rated current value for one panel (input) phase
at full load (100%). This is set by the panel's
input breaker; if there is no input breaker for this
panel, then this object is not accessible.
0.1 Amps RMSPositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.3
panelNumPhases
The number of lines (phases) for this panel.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.4
panelNumBreakers
The number of breakers contained in this panel.
This determines the number of rows found in the breaker tables.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.5
panelVoltageUnits
Indicates whether the panelPhaseVoltage readings are
'Vrms Line-Line' or 'Vrms Line-Neutral'.
OctetString
Constraints:
range: 0-31
.1.3.6.1.4.1.534.6.6.4.1.2.1.1.6
.1.3.6.1.4.1.534.6.6.4.1.2.2 · 1 row entry · 7 columns
A sparsely populated (ie, not sequentially numbered) 
table of ratings for each panel.  The number of
entries is given by the value of pduNumPanels.
panelMetersEntry entry .1.3.6.1.4.1.534.6.6.4.1.2.2.1
An entry containing meter readings applicable to a
particular panel.
Indexes
panelNumber
Column Syntax OID
panelTotalKilowattHours
The accumulated kilowatt-hours for this panel
since it was commissioned and put into service,
or since the last reset of the system KHW measures.
KWHNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.1
panelMonthlyKilowattHours
The accumulated kilowatt-hours for this panel
since the beginning of this calendar month,
or since the last reset of the system KHW measures.
KWHNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.2
panelYtdKilowattHours
The accumulated kilowatt-hours for this panel
since the beginning of this calendar year (YTD),
or since the last reset of the system KHW measures.
KWHNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.3
panelVA
The present VA (input) demand of this panel.
VANonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.4
panelPower
The present power (input) demand of this panel.
WattsNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.5
panelPowerFactor
The input power factor for this panel.
Varies from -1.00 to 1.00, multiplied by 100.
If negative values are used, they indicate lagging pf.
pf * 100Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.6
panelNeutralCurrent
The present neutral phase current for this panel.
0.1 Amps RMSNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.2.1.7
.1.3.6.1.4.1.534.6.6.4.1.2.3 · 1 row entry · 4 columns
A sparsely populated (ie, not sequentially panel numbered) 
table of ratings for each panel.  The number of
entries is given by the sum of panelNumPhases for pduNumPanels.
panelPhaseMetersEntry entry .1.3.6.1.4.1.534.6.6.4.1.2.3.1
An entry containing meter readings applicable to a
particular phase of a particular panel.
Indexes
panelNumber panelPhaseIndex
Column Syntax OID
panelPhaseIndex
The line or phase identifier.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.1
panelPhaseVoltage
The present voltage for this phase.
Volts RMSNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.2
panelPhaseCurrent
The present current for this phase.
0.1 Amps RMSNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.3
panelPhasePercentLoad
The percentage of the panel power capacity presently
being used on this line, normally based on the
ratio of panelPhaseCurrent to the rated phase current.
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.534.6.6.4.1.2.3.1.4
.1.3.6.1.4.1.534.6.6.4.1.3.1 · 1 row entry · 4 columns
A sparsely populated (ie, not sequentially numbered) 
table of ratings and fixed values for each breaker.  
The number of entries is given by the value of 
panelNumBreakers for this panel.
breakerRatingsEntry entry .1.3.6.1.4.1.534.6.6.4.1.3.1.1
An entry containing information applicable to a
particular output phase.
Indexes
panelNumber breakerNumber
Column Syntax OID
breakerNumber
Index for the Breaker Ratings and Meters tables.
Corresponds to the physical breaker number in the
PDU system.
Breakers are not required to be numbered sequentially.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.1
breakerName
Name given by the administrator to identify this breaker.
OctetString
Constraints:
range: 0-31
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.2
breakerRatedCurrent
The rated current value of this breaker (for one phase)
at full load (100%).
0.1 Amps RMSPositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.3
breakerNumPhases
The number of lines (phases) for this breaker.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.1.1.4
.1.3.6.1.4.1.534.6.6.4.1.3.2 · 1 row entry · 3 columns
A sparsely populated (ie, not sequentially numbered) 
table of ratings for each breaker.  The number of
entries is given by the value of panelNumBreakers
for this panel.
breakerMetersEntry entry .1.3.6.1.4.1.534.6.6.4.1.3.2.1
An entry containing meter readings applicable to a
particular breaker.
Indexes
panelNumber breakerNumber
Column Syntax OID
breakerTotalKilowattHours
The accumulated kilowatt-hours for this breaker
since it was commissioned and put into service,
or since the last reset of the panel KHW measures.
KWHNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.1
breakerMonthlyKilowattHours
The accumulated kilowatt-hours for this breaker
since the beginning of this calendar month,
or since the last reset of the panel KHW measures.
KWHNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.2
breakerYtdKilowattHours
The accumulated kilowatt-hours for this breaker
since the beginning of this calendar year (YTD),
or since the last reset of the panel KHW measures.
KWHNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.2.1.3
.1.3.6.1.4.1.534.6.6.4.1.3.3 · 1 row entry · 6 columns
A sparsely populated (ie, not sequentially breaker numbered) 
table of ratings for each breaker.  The number of
entries is given by the sum of breakerNumPhases for 
panelNumBreakers for all panels (pduNumPanels).
breakerPhaseMetersEntry entry .1.3.6.1.4.1.534.6.6.4.1.3.3.1
An entry containing meter readings applicable to a particular
phase of a particular breaker on a particular panel.
Indexes
panelNumber breakerNumber breakerPhaseIndex
Column Syntax OID
breakerPhaseIndex
The line or phase identifier.
PositiveInteger
Textual Convention: PositiveInteger Integer32
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.1
breakerPhaseVA
The present VA (input) demand of this phase on
this breaker.
VANonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.2
breakerPhasePower
The present power (input) demand of phase on
this breaker.
WattsNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.3
breakerPhasePowerFactor
The input power factor for this phase on this breaker.
Varies from -1.00 to 1.00, multiplied by 100.
If negative values are used, they indicate lagging pf.
pf * 100Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.4
breakerPhaseCurrent
The present current for this phase of this breaker.
0.1 Amps RMSNonNegativeInteger
Textual Convention: NonNegativeInteger Integer32
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.5
breakerPhasePercentLoad
The percentage of the breaker power capacity presently
being used on this line, normally based on the
ratio of breakerPhaseCurrent to the breakerRatedCurrent.
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.534.6.6.4.1.3.3.1.6