panelMetersEntry
EATON-PDU-MIB ·
.1.3.6.1.4.1.534.6.6.4.1.2.2.1
Object
row
An entry containing meter readings applicable to a particular panel.
Context
- MIB
- EATON-PDU-MIB
- OID
.1.3.6.1.4.1.534.6.6.4.1.2.2.1- Type
- row
- Status
- current
- Parent
- panelMetersTable
- Table
- panelMetersTable
- Children
- 7
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| panelTotalKilowattHours The accumulated kilowatt-hours for this panel
since it was commissioned and put into service,
or since the last reset of the system KHW measures. | column | KWH NonNegativeInteger | .1.3.6.1.4.1.534.6.6.4.1.2.2.1.1 |
| panelMonthlyKilowattHours The accumulated kilowatt-hours for this panel
since the beginning of this calendar month,
or since the last reset of the system KHW measures. | column | KWH NonNegativeInteger | .1.3.6.1.4.1.534.6.6.4.1.2.2.1.2 |
| panelYtdKilowattHours The accumulated kilowatt-hours for this panel
since the beginning of this calendar year (YTD),
or since the last reset of the system KHW measures. | column | KWH NonNegativeInteger | .1.3.6.1.4.1.534.6.6.4.1.2.2.1.3 |
| panelVA The present VA (input) demand of this panel. | column | VA NonNegativeInteger | .1.3.6.1.4.1.534.6.6.4.1.2.2.1.4 |
| panelPower The present power (input) demand of this panel. | column | Watts NonNegativeInteger | .1.3.6.1.4.1.534.6.6.4.1.2.2.1.5 |
| panelPowerFactor The input power factor for this panel.
Varies from -1.00 to 1.00, multiplied by 100.
If negative values are used, they indicate lagging pf. | column | pf * 100 Integer32 | .1.3.6.1.4.1.534.6.6.4.1.2.2.1.6 |
| panelNeutralCurrent The present neutral phase current for this panel. | column | 0.1 Amps RMS NonNegativeInteger | .1.3.6.1.4.1.534.6.6.4.1.2.2.1.7 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| panelNumber Index for the Panel Ratings and Meters tables.
Corresponds to the physical panel number in the
PDU system.
There must be a #1. The maximum value is 16.
Panels are not require… | column | PositiveInteger | .1.3.6.1.4.1.534.6.6.4.1.2.1.1.1 |