DeltaUPSv5-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
1
Rows
1
Columns
46

dupsPMTable

table mandatory
.1.3.6.1.4.1.2254.2.5.10.6 · 1 row entry · 46 columns
A list of power module table entries.
dupsPMEntry entry .1.3.6.1.4.1.2254.2.5.10.6.1
An entry containing information applicable to a particular
power module.
Indexes
dupsPMID
Column Syntax OID
dupsPMID mandatory
The power module identifier.
Integer32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.1
dupsPMPFCTemp mandatory
The power module PFC temperature.
1 Degree CelsiusInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.2
dupsPMINVTemp mandatory
The power module inverter temperature.
1 Degree CelsiusInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.3
dupsPMINVTempR mandatory
The power module inverter-R temperature.
1 Degree CelsiusInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.4
dupsPMINVTempS mandatory
The power module inverter-S temperature.
1 Degree CelsiusInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.5
dupsPMINVTempT mandatory
The power module inverter-T temperature.
1 Degree CelsiusInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.6
dupsPMINVVolt1 mandatory
The inverter line 1 voltage of the power module in 1/10 V.
0.1 VoltInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.7
dupsPMINVVolt2 mandatory
The inverter line 2 voltage of the power module in 1/10 V.
0.1 VoltInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.8
dupsPMINVVolt3 mandatory
The inverter line 3 voltage of the power module in 1/10 V.
0.1 VoltInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.9
dupsPMStsNotExist mandatory
Indicates the power module is existed or not?
Enumeration
Enumerated Values:
1notExist
2existed
.1.3.6.1.4.1.2254.2.5.10.6.1.10
dupsPMStsOff mandatory
Indicates the power module is on or off?
Enumeration
Enumerated Values:
1pmOff
2pmOn
.1.3.6.1.4.1.2254.2.5.10.6.1.11
dupsPMStsRepair mandatory
Indicates the power module is in repair mode or not?
Enumeration
Enumerated Values:
1repair
2notRepair
.1.3.6.1.4.1.2254.2.5.10.6.1.12
dupsPMStsFaultShutdown mandatory
Indicates the power module status of fault shutdown.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.13
dupsPMStsPFCFuseFail mandatory
Indicates the power module PFC fuse open or close?
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.14
dupsPMStsPFCOverTempWarning mandatory
Indicates the power module PFC over temperature warning.
Enumeration
Enumerated Values:
1warning
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.15
dupsPMStsPFCOverTempShutdown mandatory
Indicates the power module PFC over temperature shutdown.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.16
dupsPMStsPFCOverVoltWarning mandatory
Indicates the power module PFC over voltage warning.
Enumeration
Enumerated Values:
1warning
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.17
dupsPMStsPFCOverVoltShutdown mandatory
Indicates the power module PFC over voltage shutdown.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.18
dupsPMStsPFCUnderVoltWarning mandatory
Indicates the power module PFC under voltage warning.
Enumeration
Enumerated Values:
1warning
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.19
dupsPMStsPFCUnderVoltShutdown mandatory
Indicates the power module PFC under voltage shutdown.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.20
dupsPMStsPFCGeneralFault mandatory
Indicates the power module PFC genreal fault.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.21
dupsPMStsPFCFanFail mandatory
Indicates the power module PFC fan fail.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.22
dupsPMStsPFCCurrentLimit mandatory
Indicates the power module PFC output current limit.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.23
dupsPMStsPFCOff mandatory
Indicates the power module PFC off.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.24
dupsPMStsPFCInnerCommFail mandatory
Indicates the power module PFC inner communication fail.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.25
dupsPMStsPFCNotCalibrated mandatory
Indicates the power module PFC is not calibrated.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.26
dupsPMStsINVFuseFail mandatory
Indicates the power module Inverter fuse open or close?
Enumeration
Enumerated Values:
1open
2close
.1.3.6.1.4.1.2254.2.5.10.6.1.27
dupsPMStsINVOverTempWarning mandatory
Indicates the power module Inverter over temperature warning.
Enumeration
Enumerated Values:
1warning
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.28
dupsPMStsINVOverTempShutdown mandatory
Indicates the power module Inverter over temperature shutdown.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.29
dupsPMStsINVFanFail mandatory
Indicates the power module Inverter fan fail.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.30
dupsPMStsINVShortCircuit mandatory
Indicates the power module Inverter short circuit.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.31
dupsPMStsINVSTSFail mandatory
Indicates the power module Inverter STS fail.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.32
dupsPMStsINVCircuitFail mandatory
Indicates the power module Inverter circuit fail shutdown.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.33
dupsPMStsINVOverVolt mandatory
Indicates the power module Inverter over voltage shutdown.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.34
dupsPMStsINVOverload mandatory
Indicates the power module Inverter overload.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.35
dupsPMStsINVInnerCommFail mandatory
Indicates the power module Inverter inner communication fail.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.36
dupsPMStsINVEPO mandatory
Indicates the power module Inverter EPO shutdown.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.37
dupsPMStsINVParallelCommFail mandatory
Indicates the power module Inverter parallel communication fail.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.38
dupsPMStsINVParallelFail mandatory
Indicates the power module Inverter parallel fail.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.39
dupsPMStsINVSTSOn mandatory
Indicates the status of power module Inverter state.
Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.5.10.6.1.40
dupsPMStsINVNotCalibrated mandatory
Indicates the power module Inverter is not calibrated.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.41
dupsPMStsChargerFail mandatory
Indicates the power module Charger fail.
Enumeration
Enumerated Values:
1alarm
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.42
dupsPMSummaryStatus mandatory
The power module summary status.
Enumeration
Enumerated Values:
1abnormal
2normal
.1.3.6.1.4.1.2254.2.5.10.6.1.43
dupsPMPFCTempR mandatory
The power module pfc-R temperature.
1 Degree CelsiusInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.44
dupsPMPFCTempS mandatory
The power module pfc-S temperature.
1 Degree CelsiusInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.45
dupsPMPFCTempT mandatory
The power module pfc-T temperature.
1 Degree CelsiusInteger32
Textual Convention: COPS-PR-SPPIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.5.10.6.1.46