DKSF-60-4-X-X-X Table View

Table-centric layout grouping table, row, and column objects.

Tables
6
Rows
6
Columns
38
.1.3.6.1.4.1.25728.5500.5 · 1 row entry · 6 columns
Watchdog and outlet/relay control table
npRelayEntry entry .1.3.6.1.4.1.25728.5500.5.1
Relay/outlet table row
Indexes
npRelayN
Column Syntax OID
npRelayN
The N of output relay
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.25728.5500.5.1.1
npRelayMode
Control of relay:
0 - manual off
1 - manual on
2 - watchdog
3 - schedule
4 - both schedule and watchdog (while switched on by schedule)
5 - logic
Enumerationr/w
Enumerated Values:
0off
1on
2watchdog
3schedule
4scheduleAndWatchdog
5logic
.1.3.6.1.4.1.25728.5500.5.1.2
npRelayStartReset
Write 1 to start reset (switch relay off for some time)
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.25728.5500.5.1.3
npRelayMemo
Relay memo
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.25728.5500.5.1.6
npRelayFlip
Write -1 to flip between manual on and manual off states of relay
Enumerationr/w
Enumerated Values:
-1flip
.1.3.6.1.4.1.25728.5500.5.1.14
npRelayState
Actual relay state at the moment,
regardless of source of control.
0 - relay is off
1 - relay is on
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.25728.5500.5.1.15
.1.3.6.1.4.1.25728.5800.3 · 1 row entry · 8 columns
Watchdog and outlet/relay control table
npPwrEntry entry .1.3.6.1.4.1.25728.5800.3.1
Watchdog and outlet/relay control table row
Indexes
npPwrChannelN
Column Syntax OID
npPwrChannelN
The id of watchdog/power channel
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.25728.5800.3.1.1
npPwrStartReset
Write 1 to start forced reset
On read:
0 - normal operation
1 - reset is active
2 - reboot pause is active or watchdog is inactive
Integer32r/w
Constraints:
range: 0-2
.1.3.6.1.4.1.25728.5800.3.1.2
npPwrManualMode
Mode of power channel
0 - manual off
1 - manual on
2 - watchdog
3 - schedule
4 - schedule and watchdog
5 - controlled by Logic
Enumerationr/w
Enumerated Values:
0off
1on
2watchdog
3schedule
4scheduleAndWatchdog
5logic
.1.3.6.1.4.1.25728.5800.3.1.3
npPwrResetsCounter
Counter of watchdog resets
Write 0 to clear.
Integer32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.25728.5800.3.1.4
npPwrRepeatingResetsCounter
Counter of continous failed
watchdog resets
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.25728.5800.3.1.5
npPwrMemo
Relay channel memo
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.25728.5800.3.1.6
npPwrRelayFlip
Write -1 to flip between manual on and manual off states of relay
Enumerationr/w
Enumerated Values:
-1flip
.1.3.6.1.4.1.25728.5800.3.1.14
npPwrRelayState
Actual relay state at the moment,
regardless of source of control.
0 - relay is off
1 - relay is on
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.25728.5800.3.1.15
.1.3.6.1.4.1.25728.8300.1 · 1 row entry · 6 columns
Current loop sensors Table
npCurLoopEntry entry .1.3.6.1.4.1.25728.8300.1.1
Current loop sensors Table Row
Indexes
npCurLoopN
Column Syntax OID
npCurLoopN
Index of current loop, 1 to max supported
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.25728.8300.1.1.1
npCurLoopStatus
Status of the loop
0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered
Enumeration
Enumerated Values:
0ok
1alert
2cut
3short
4notPowered
.1.3.6.1.4.1.25728.8300.1.1.2
npCurLoopI
Loop current, mA
Integer32
Constraints:
range: 0-99999
.1.3.6.1.4.1.25728.8300.1.1.3
npCurLoopV
Voltage drop on the loop, mV
Integer32
Constraints:
range: 0-99999
.1.3.6.1.4.1.25728.8300.1.1.4
npCurLoopR
Resistance of the loop, Ohm
Integer32
Constraints:
range: 0-99999
.1.3.6.1.4.1.25728.8300.1.1.5
npCurLoopPower
Control of loop power
0=Off, 1=On, 2=reset by off/on power
Enumerationr/w
Enumerated Values:
0off
1on
2cyclePower
.1.3.6.1.4.1.25728.8300.1.1.7
.1.3.6.1.4.1.25728.8800.1 · 1 row entry · 6 columns
Thermo Sensors Table
npThermoEntry entry .1.3.6.1.4.1.25728.8800.1.1
Thermo Sensors Table Row
Indexes
npThermoSensorN
Column Syntax OID
npThermoSensorN
The id of temperature sensor, 1 to 8
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.25728.8800.1.1.1
npThermoValue
Temperature, deg.C
Integer32
Constraints:
range: -60-280
.1.3.6.1.4.1.25728.8800.1.1.2
npThermoStatus
Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)
Enumeration
Enumerated Values:
0failed
1low
2norm
3high
.1.3.6.1.4.1.25728.8800.1.1.3
npThermoLow
Bottom margin of normal temperature range, deg.C
Integer32
Constraints:
range: -60-280
.1.3.6.1.4.1.25728.8800.1.1.4
npThermoHigh
Top margin of normal temperature range, deg.C
Integer32
Constraints:
range: -60-280
.1.3.6.1.4.1.25728.8800.1.1.5
npThermoMemo
T channel memo
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.25728.8800.1.1.6
.1.3.6.1.4.1.25728.8900.1 · 1 row entry · 7 columns
Digital Input/output Table
npIoEntry entry .1.3.6.1.4.1.25728.8900.1.1
Digital Input/output Table Row
Indexes
npIoLineN
Column Syntax OID
npIoLineN
Number of IO line, from 1 to max supported
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.25728.8900.1.1.1
npIoLevelIn
Input level, 0 or 1
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.25728.8900.1.1.2
npIoLevelOut
Output level, 0 or 1.
Write -1 to flip output.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.25728.8900.1.1.3
npIoMemo
IO line memo
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.25728.8900.1.1.6
npIoPulseCounter
Pulse Counter on IO input line (counts positive fronts)
Write 0 to reset.
SNMPv2-SMICounter32r/w
Textual Convention: SNMPv2-SMICounter32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.8900.1.1.9
npIoSinglePulseDuration
Set duration of single pulse on IO output line,
100ms to 25500ms, min. step is 100ms
Integer32r/w
Constraints:
range: 100-25500
.1.3.6.1.4.1.25728.8900.1.1.12
npIoSinglePulseStart
Write 1 to start single pulse on IO output.
Output will be inverted for time, specified by npIoSinglePulseDuration
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.25728.8900.1.1.13
.1.3.6.1.4.1.25728.9700.1 · 1 row entry · 5 columns
Electricity Meter Table
npElecEntry entry .1.3.6.1.4.1.25728.9700.1.1
Electricity Meter Table Table Row
Indexes
npElecIndex
Column Syntax OID
npElecIndex
Number of elec.meter, associated with IO line
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.25728.9700.1.1.1
npElecPulsesPerKwh
Pulses on IO line input per 1 kWh of consumed energy
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.25728.9700.1.1.2
npElecPower
Power, Watts, based on pulse rate/interval, 5 minute average
SNMPv2-SMIGauge32
Textual Convention: SNMPv2-SMIGauge32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.9700.1.1.3
npElecEnergy
Energy counter, kWh, based on pulse count
SNMPv2-SMICounter32r/w
Textual Convention: SNMPv2-SMICounter32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.9700.1.1.4
npElecEnergy100
Energy counter, kWh*100, based on pulse count
SNMPv2-SMICounter32r/w
Textual Convention: SNMPv2-SMICounter32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.9700.1.1.5