APNL-MODULAR-PDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
2
Rows
2
Columns
31
.1.3.6.1.4.1.29640.4.3.33 · 1 row entry · 21 columns
A table of the modules on the PDU.
Each entry represents an module unit.
nodeEntry entry .1.3.6.1.4.1.29640.4.3.33.1
An port entry in the port table.
Indexes
nodeIndex
Column Syntax OID
nodeIndex
The node table Index.
Unsigned32
Constraints:
range: 1-30
.1.3.6.1.4.1.29640.4.3.33.1.1
nodeType
Type of the node.
TypeUnknown (0) Unknown node.
TypePresModChar (1) PM LCD Character Module.
TypePresModMono (2) PM Mono Graphics Module.
TypePresModGraph (3) PM Color Graphics Mo…
Enumeration
Enumerated Values:
0typeUnknown
1typePresModChar
2typePresModMono
3typePresModGraph
4typePowerMeter
5typePowerMeterSwitch
6typeSwitch
.1.3.6.1.4.1.29640.4.3.33.1.2
nodeOutlet
The number associated with the physical outlet of the node.
The special value of 0 indicates that this entry is not associated with a physical port.
SNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.3
nodeAlarmStatus
Array of bits each one indicates an alarm activated in the alarm selector value.
TrapCurrHi (0) The current is to high against the high current threshold.
TrapCurrLo (1) The current is to low against the low current th…
Bits
Enumerated Values:
0trapCurrHi
1trapCurrLo
2trapVoltHi
3trapVoltLo
4switchOn
5switchOff
.1.3.6.1.4.1.29640.4.3.33.1.4
nodePower
The measured node power in Kilo Watt's*Hour.
kiloWattHoursSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.5
nodeAcurrent
The measured ac current at the node (in 1/10th Amperes).
DeciAmpersSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.6
nodePeakCurrent
The measured max current since last reset of the node (in 1/10th Amperes).
DeciAmpersSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.7
nodeVoltage
The measured voltage on the node.
VoltsSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.8
nodeMinVoltage
The measured minimum voltage at the node since last reset.
VoltsSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.9
nodeKvar
The Reactive Power. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux.
KiloWattHoursSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.10
nodeFrequency
The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA.
HertzSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.11
nodePowerFactor
The effective power facton (Cosinus Phi) in percents of the node.
PercentSNMPv2-SMIUnsigned32
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.12
nodeSwitchOperStatus
The actual operational Status of the node.
Unknown (0) not known status.
Off (1) switch is off.
On (2) switch is on.
Enumeration
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.29640.4.3.33.1.13
nodeSwitchAdminStatus
The desired admin Status of the switch.
Unknown (0) not known.
Off (1) switch is off.
On (2) switch is on.
Enumerationr/w
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.29640.4.3.33.1.14
nodeCurrHiThresh
The current high threshold (in 1/10th Amperes).
DeciAmpersSNMPv2-SMIUnsigned32r/w
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.15
nodeCurrLoThresh
The current low threshold (in 1/10th Amperes).
DeciAmpersSNMPv2-SMIUnsigned32r/w
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.16
nodeVoltHiThresh
The voltage high threshold.
VoltsSNMPv2-SMIUnsigned32r/w
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.17
nodeVoltLoThresh
The voltage low threshold.
VoltsSNMPv2-SMIUnsigned32r/w
Textual Convention: SNMPv2-SMIUnsigned32 Unsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.29640.4.3.33.1.18
nodeAlarmSelector
Array of bits each one controls one alarm.
TrapCurrHi (0) Enable/disable the high current alarm.
TrapCurrLo (1) Enable/disable the low current alarm.
TrapVoltHi (2) Enable/disable the high voltage alarm.
TrapVoltLo (…
Bitsr/w
Enumerated Values:
0trapCurrHi
1trapCurrLo
2trapVoltHi
3trapVoltLo
4switchOn
5switchOff
.1.3.6.1.4.1.29640.4.3.33.1.19
nodeName
The node name. My be set by manager.
OctetStringr/w
Constraints:
range: 1-14
.1.3.6.1.4.1.29640.4.3.33.1.20
nodePhase
The measured phase of the node.
Maybe assigned when not configured in production.
PhaseUnknown (0).
PhaseL1 (1).
PhaseL2 (2).
PhaseL3 (3).
Enumerationr/w
Enumerated Values:
0phaseUnknown
1phaseL1
2phaseL2
3phaseL3
.1.3.6.1.4.1.29640.4.3.33.1.21
.1.3.6.1.4.1.29640.4.3.34 · 1 row entry · 10 columns
A table of the Sensors on the PDU.
Each entry represents an an Sensor unit.
sensorEntry entry .1.3.6.1.4.1.29640.4.3.34.1
An Sensor Entry in the Sensor table
Indexes
sensorIndex
Column Syntax OID
sensorIndex
The Sensor table Index.
Unsigned32
Constraints:
range: 1-4
.1.3.6.1.4.1.29640.4.3.34.1.1
sensorType
Sensor Typ:
Measured values are used according to sensor type.
Other (0) unknown sensor type.
Temperature (1) .
Humidity (2).
Smoke (3).
CO1 (4).
Vibration (5).
Doorstatus …
Enumeration
Enumerated Values:
0other
1temperature
2humidity
3smoke
4co1
5vibration
6doorStatus
.1.3.6.1.4.1.29640.4.3.34.1.2
sensorAlarmStatus
Array of bits each one indicates an alarm activated in the alarm selector value.
Bits
Enumerated Values:
0trapHi
1trapLo
2switchOn
3switchOff
4beeperHi
5beeperLo
.1.3.6.1.4.1.29640.4.3.34.1.3
sensorValue
The measured value of the sensor, units are depending on sensor type.
by typeSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.29640.4.3.34.1.4
sensorSwitchOperStatus
The actual operational Status of the switch.
Enumeration
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.29640.4.3.34.1.5
sensorSwitchAdminStatus
The desired admin Status of the switch.
Enumerationr/w
Enumerated Values:
0unknown
1off
2on
.1.3.6.1.4.1.29640.4.3.34.1.6
sensorHiThresh
High threshold.
by typeSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.29640.4.3.34.1.7
sensorLoThresh
Low threshold.
by typeSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.29640.4.3.34.1.8
sensorAlarmSelector
Array of bits each one controls one alarm.
E.g trap, beeper etc.
Bitsr/w
Enumerated Values:
0trapHi
1trapLo
2switchOn
3switchOff
4beeperHi
5beeperLo
.1.3.6.1.4.1.29640.4.3.34.1.9
sensorName
The sensor name. May be set by the manager.
OctetStringr/w
Constraints:
range: 1-12
.1.3.6.1.4.1.29640.4.3.34.1.10