xupsOutputCumulativePowerUsage
XUPS-MIB ·
.1.3.6.1.4.1.534.1.4.7
Object
scalar
r/w
Wh Integer32
Units are Watt-hours.This is the energy consumed since the last reset. This object is writable so that it can be reset to 0. When it is written to 0, the xupsOutputCumulativeWhTimer will be reset to 0 as well.
Context
- MIB
- XUPS-MIB
- OID
.1.3.6.1.4.1.534.1.4.7- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- Wh
- Parent
- xupsOutput
Syntax
Wh Integer32
Values & Constraints
Object Constraints
range: 0-2147483647