XUPS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
6
Rows
6
Columns
40
.1.3.6.1.4.1.534.1.3.4 · 1 row entry · 7 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk xupsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'XUPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'XUPS-MIB::xupsInputTable'
A list of input table entries.  The number of entries
is given by the value of xupsInputNumPhases.
xupsInputEntry row .1.3.6.1.4.1.534.1.3.4.1
The input table entry containing the current,
voltage, etc. readings for one phase.
Indexes
Column Syntax OID
The number of the phase. Serves as index for input table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.534.1.3.4.1.1
The measured input voltage from the UPS meters in volts.
RMS VoltsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.3.4.1.2
The measured input current from the UPS meters in amps.
RMS AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.3.4.1.3
The measured input real power in watts.
WattsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.3.4.1.4
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral,
phase1 to phase2, phase2 to phase3, phase3 to phase1.
Enumeration
Enumerated Values:
1phase1toN
2phase2toN
3phase3toN
4phase1to2
5phase2to3
6phase3to1
.1.3.6.1.4.1.534.1.3.4.1.5
A descriptive name for the phase, example : L1/A for the phase 1.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.1.3.4.1.6
The measured input current from the UPS meters in tenth of amps.
RMS tenth of AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.3.4.1.7
.1.3.6.1.4.1.534.1.4.4 · 1 row entry · 9 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk xupsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'XUPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'XUPS-MIB::xupsOutputTable'
A list of output table entries.  The number of entries
is given by the value of xupsOutputNumPhases.
xupsOutputEntry row .1.3.6.1.4.1.534.1.4.4.1
Output Table Entry containing voltage, current, etc.
Indexes
Column Syntax OID
The number of the phase. Serves as index for output table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.534.1.4.4.1.1
The measured output voltage from the UPS metering in volts.
RMS VoltsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.2
The measured UPS output current in amps.
RMS AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.3
The measured real output power in watts.
WattsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.4
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral,
phase1 to phase2, phase2 to phase3, phase3 to phase1.
Enumeration
Enumerated Values:
1phase1toN
2phase2toN
3phase3toN
4phase1to2
5phase2to3
6phase3to1
.1.3.6.1.4.1.534.1.4.4.1.5
A descriptive name for the phase.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.1.4.4.1.6
The measured output current from the UPS meters in tenth of amps.
RMS tenth of AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.7
The percentage of the UPS power capacity presently
being used on this output line
percentInteger32
Constraints:
range: 0-200
.1.3.6.1.4.1.534.1.4.4.1.8
The measured apparent output power in VA.
VAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.4.4.1.9
.1.3.6.1.4.1.534.1.5.3 · 1 row entry · 6 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk xupsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'XUPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'XUPS-MIB::xupsBypassTable'
A list of bypass table entries.  The number of entries
is given by the value of xupsBypassNumPhases.
xupsBypassEntry row .1.3.6.1.4.1.534.1.5.3.1
Bypass Table Entry containing voltage for each phase.
Indexes
Column Syntax OID
The Bypass Phase, index for the table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.534.1.5.3.1.1
The measured UPS bypass voltage in volts.
RMS VoltsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.5.3.1.2
value indicates what measurement is being stored in this table row :
phase1 to neutral, phase2 to neutral, phase3 to neutral,
phase1 to phase2, phase2 to phase3, phase3 to phase1.
Enumeration
Enumerated Values:
1phase1toN
2phase2toN
3phase3toN
4phase1to2
5phase2to3
6phase3to1
.1.3.6.1.4.1.534.1.5.3.1.3
A descriptive name for the phase.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.1.5.3.1.4
The measured bypass current from the UPS meters in tenth of amps.
RMS tenth of AmpsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.5.3.1.5
The measured real bypass power in watts.
WattsInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.5.3.1.6
.1.3.6.1.4.1.534.1.7.2 · 1 row entry · 3 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk xupsAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'XUPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'XUPS-MIB::xupsAlarmTable'
A list of alarm table entries.  The number of entries
is given by the value of xupsAlarms.
Note that this table is sparsely (non-consecutively)
numbered and will be empty if there are no active alarms.
xupsAlarmEntry row .1.3.6.1.4.1.534.1.7.2.1
Alarm Table Entry containing descriptive information
for one alarm entry.
Indexes
Column Syntax OID
A unique identifier for an alarm condition.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.534.1.7.2.1.1
A reference to an alarm description object. The object
referenced should not be accessible, but rather be used to
provide a unique description of the alarm condition.
ObjectIdentifier .1.3.6.1.4.1.534.1.7.2.1.2
The value of the MIB-II variable sysUpTime when the alarm
condition occurred.
SNMPv2-SMITimeTicks
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.534.1.7.2.1.3
.1.3.6.1.4.1.534.1.7.19 · 1 row entry · 5 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk xupsAlarmEventTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'XUPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'XUPS-MIB::xupsAlarmEventTable'
A table of the UPS internal event history queue.
xupsAlarmEventEntry row .1.3.6.1.4.1.534.1.7.19.1
One of the entries in the UPS event history queue.
Column Syntax OID
A unique number that reflects the order in which the event
occurred. The oldest event in the queue will be number 1.
Subsequent events will be numbered 2, 3, 4, etc.
Integer32
Constraints:
range: 1-400
.1.3.6.1.4.1.534.1.7.19.1.1
The time and date that an event occurred as recorded in the UPS
internal event queue. This string will reflect the time and
date as set in the UPS itself and will not be referenced to sysUpTime.
The format is MM/DD/YYY…
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.534.1.7.19.1.2
Enumerated value that tells whether the event is an
occurrence of an alarm condition or a clearing of an
alarm condition.
Enumeration
Enumerated Values:
1occurred
2cleared
3unknown
.1.3.6.1.4.1.534.1.7.19.1.3
A description of the event stored in the UPS event queue.
This description will be a sixteen bit integer value
representing one of the defined alarms in the Powerware Binary
Computer Mode communication specification…
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.7.19.1.4
A text string describing each entry in the Event Log. The format of this
text message is free (not fixed) for the operator to read; good contents
would be a time & date stamp, the event type, and a description of the …
OctetString
Constraints:
range: 0-80
.1.3.6.1.4.1.534.1.7.19.1.5
.1.3.6.1.4.1.534.1.12.2 · 1 row entry · 10 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk xupsRecepTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'XUPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'XUPS-MIB::xupsRecepTable'
A list of receptacle table entries.  The number of entries
is given by the value of xupsNumReceptacles.
xupsRecepEntry row .1.3.6.1.4.1.534.1.12.2.1
A receptacle table entry containing the status and
control values for one receptacle.
Indexes
Column Syntax OID
The number of the Receptacle. Serves as index for Receptacle table.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.534.1.12.2.1.1
The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown, 6=Reserved for future,
7=Failed in Closed position, 8=Failed in Open position.
Enumeration
Enumerated Values:
1on
2off
3pendingOff
4pendingOn
5unknown
6reserved
7failedClosed
8failedOpen
.1.3.6.1.4.1.534.1.12.2.1.2
The Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to
turn off after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abor…
secondsInteger32r/w
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.534.1.12.2.1.3
The Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to
turn on after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abort …
secondsInteger32r/w
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.534.1.12.2.1.4
The delay after going On Battery until the Receptacle is
automatically turned Off. A value of -1 means that this Output should
never be turned Off automatically, but must be turned Off only by command.
Values from 0 …
secondsInteger32r/w
Constraints:
range: -1-32767
.1.3.6.1.4.1.534.1.12.2.1.5
Seconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never
be turned On automatically, but only when specifically commanded to d…
secondsInteger32r/w
Constraints:
range: -1-32767
.1.3.6.1.4.1.534.1.12.2.1.6
Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Unlike xupsRecepOffDelaySecs, which might …
secondsInteger32r/w
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.12.2.1.7
Units are Watt-hours.This is the energy consumed during the last hour.
WhInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.12.2.1.8
Units are Watt-hours.This is the energy consumed since the last reset.
This object is writable so that it can be reset to 0.
When it is written to 0, the xupsRecepCumulativePowerUsageTimer will be reset to 0 as well.
WhInteger32r/w
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.534.1.12.2.1.9
Time in seconds since the cumulative power usage was last reset.
SecondsSNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.534.1.12.2.1.10