controlTempDeadBand
TELESTE-COMMON-MIB ·
.1.3.6.1.4.1.3715.99.2.3.1.1.9
Object
column
optional
r/w
Integer32
Module temperature alarm/warning deadband in 0.1 degC. Common
to all limit values (LoLo, Lo, Hi, HiHi). The deadband defines
the difference between the 'ON' limit and the 'OFF' limit of
the corresponding alarm.
Example: The Hi limit is 65 degC and the deadband is 5 degC.
The high warning is activated when the temperature exceeds
65 degC and deactivated only after it falls below 60 degC.
Context
- MIB
- TELESTE-COMMON-MIB
- OID
.1.3.6.1.4.1.3715.99.2.3.1.1.9- Type
- column
- Access
- readwrite
- Status
- optional
- Parent
- moduleControlEntry
Syntax
Integer32
Values & Constraints
No enumerated values or constraints recorded.