redundancy
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.60.70.50
Object
For N+1 there is always one spare rectifier above what is needed. N+2 maintains 2 spare. For N there are always at least enough rectifiers to supply the load. If an alternative energy source is supplying the load, all rectifiers can be shut down. Rectifiers will restart when the battery begins to discharge.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.60.70.50- Type
- scalar
- Access
- readwrite
- Status
- current
- Parent
- loadBasedRectifierShutdownConfig
- Groups
- 1
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'RPS-SC300-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RPS-SC300-MIB::redundancy.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'RPS-SC300-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'RPS-SC300-MIB::redundancy'
Syntax
- Source
- Redundancy
- Base type
Enumeration
Values & Constraints
Type Values
1 | n |
2 | nPlus1 |
3 | nPlus2 |
Conformance
Member of