batteryTestStartAllowed
RPS-SC300-MIB ·
.1.3.6.1.4.1.1918.2.14.10.70.70.7
Object
scalar CanStart
Indicates if a Battery Test is allowed to start. Battery Tests cannot start within 48 hours of an AC failure, if there are no rectifiers, if Equalize or Fast Charge is active, if any rectifiers are failed or have lost communications, if the battery fuse has failed or if the system is overloaded.
Context
- MIB
- RPS-SC300-MIB
- OID
.1.3.6.1.4.1.1918.2.14.10.70.70.7- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- batteryTest
- Groups
- 1
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'RPS-SC300-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RPS-SC300-MIB::batteryTestStartAllowed.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'RPS-SC300-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'RPS-SC300-MIB::batteryTestStartAllowed'
Values & Constraints
Type Values
190 | started |
191 | canStart |
192 | busy |
193 | disabled |
194 | alarmsActive |
195 | sensorFailed |
196 | batteryNotCharged |
197 | noRectifiersNorSolarAvailable |
198 | rectifierOvsd |
199 | noBatteryConfigured |
200 | loadCurrentTooLow |
201 | acFailed |
202 | manualStop |
203 | batteryNotDischarged |
204 | acStateUnavailable |
205 | systemOverloaded |
206 | noPeakLoadReduction |
207 | inLockout |
208 | rectifiersFailed |
209 | rectifiersCommsLost |
210 | systemInOverload |
211 | batteryFuseFail |
212 | batteryTestFail |
213 | bAcFailed |
214 | bAcStateUnavailable |
215 | bNoBatteryConfigured |
216 | bSensorFailed |
217 | bNoRectifiersNorSolarAvailable |
218 | bRectifiersFailed |
219 | bRectifiersCommsLost |
220 | bSystemInOverload |
221 | bBatteryFuseFail |
222 | bBusy |
223 | bBatteryTestFail |
224 | bSystemOverloaded |
Conformance
Member of