batteryTestInterval

RPS-SC300-MIB · .1.3.6.1.4.1.1918.2.14.10.70.70.17

Object

scalar r/w dTimeIntervalInDays
The time between scheduled Battery Tests. The interval period begins at the start of a Battery Test. Zero disables scheduled Battery Tests. Zero also disables the 48 hour lockout following an AC failure, allowing an immediate manual test.

Context

MIB
RPS-SC300-MIB
OID
.1.3.6.1.4.1.1918.2.14.10.70.70.17
Type
scalar
Access
readwrite
Status
current
Units
d
Parent
batteryTest
Groups
1

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'RPS-SC300-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RPS-SC300-MIB::batteryTestInterval.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'RPS-SC300-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'RPS-SC300-MIB::batteryTestInterval'

Syntax

Source
TimeIntervalInDays
Base type
Integer32

Values & Constraints

Type Constraints
range: 0..2147483646

Conformance