rupsSecondsOnBattery
RIELLOUPS-MIB ·
.1.3.6.1.4.1.5491.10.1.2.2
Object
scalar NonNegativeInteger
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
Context
- MIB
- RIELLOUPS-MIB
- OID
.1.3.6.1.4.1.5491.10.1.2.2- Type
- scalar
- Access
- readonly
- Status
- current
- Parent
- rupsBattery
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsSecondsOnBattery.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'RIELLOUPS-MIB::rupsSecondsOnBattery'
Syntax
- Source
- NonNegativeInteger
- Base type
Integer32- Display format
d
Type Description
This data type is a non-negative value.
Values & Constraints
Type Constraints
range: 0..2147483647