RIELLOUPS-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
4
Rows
4
Columns
18
rupsInputTable
table.1.3.6.1.4.1.5491.10.1.3.3
·
1 row entry
·
5 columns
Uses the riello variant from
Command help
/opt/observium/mibs/riello.
Walk rupsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsInputTable'
A list of input table entries. The number of entries is given by the value of upsInputNumLines.
An entry containing information applicable to a
particular input line.
particular input line.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The input line identifier.
|
PositiveInteger Type Constraints: range: 1..2147483647Description: This data type is a non-zero and non-negative value. |
.1.3.6.1.4.1.5491.10.1.3.3.1.1 |
|
The present input frequency.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.3.3.1.2 |
|
The magnitude of the present input voltage.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.3.3.1.3 |
|
The magnitude of the present input current.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.3.3.1.4 |
|
The magnitude of the present input true power.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.3.3.1.5 |
rupsOutputTable
table.1.3.6.1.4.1.5491.10.1.4.4
·
1 row entry
·
6 columns
Uses the riello variant from
Command help
/opt/observium/mibs/riello.
Walk rupsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsOutputTable'
A list of output table entries. The number of entries is given by the value of rupsOutputNumLines.
An entry containing information applicable to a
particular output line.
particular output line.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The output line identifier.
|
PositiveInteger Type Constraints: range: 1..2147483647Description: This data type is a non-zero and non-negative value. |
.1.3.6.1.4.1.5491.10.1.4.4.1.1 |
|
The present output voltage.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.4.4.1.2 |
|
The present output current.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.4.4.1.3 |
|
The present output true power.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.4.4.1.4 |
|
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5491.10.1.4.4.1.5 |
|
The present output peak current.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.4.4.1.6 |
rupsBypassTable
table.1.3.6.1.4.1.5491.10.1.5.3
·
1 row entry
·
4 columns
Uses the riello variant from
Command help
/opt/observium/mibs/riello.
Walk rupsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsBypassTable'
A list of bypass table entries. The number of entries is given by the value of rupsBypassNumLines.
An entry containing information applicable to a
particular bypass input.
particular bypass input.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The bypass line identifier.
|
PositiveInteger Type Constraints: range: 1..2147483647Description: This data type is a non-zero and non-negative value. |
.1.3.6.1.4.1.5491.10.1.5.3.1.1 |
|
The present bypass voltage.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.5.3.1.2 |
|
The present bypass current.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.5.3.1.3 |
|
The present true power conveyed by the bypass.
|
NonNegativeInteger Type Constraints: range: 0..2147483647Description: This data type is a non-negative value. |
.1.3.6.1.4.1.5491.10.1.5.3.1.4 |
rupsAlarmTable
table.1.3.6.1.4.1.5491.10.1.6.2
·
1 row entry
·
3 columns
Uses the riello variant from
Command help
/opt/observium/mibs/riello.
Walk rupsAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsAlarmTable'
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
rupsAlarmId equal to 1, and increments the value of
rupsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of rupsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
rupsAlarmId might have wrapped.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), rupsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of rupsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of rupsAlarmsPresent.
An entry containing information applicable to a
particular alarm.
particular alarm.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
A unique identifier for an alarm condition. This
value must remain constant. |
PositiveInteger Type Constraints: range: 1..2147483647Description: This data type is a non-zero and non-negative value. |
.1.3.6.1.4.1.5491.10.1.6.2.1.1 |
|
A reference to an alarm description object. The
object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. |
ObjectIdentifier | .1.3.6.1.4.1.5491.10.1.6.2.1.2 |
|
The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of rupsAlarmTime shall equal 0. |
PositiveInteger Type Constraints: range: 1..2147483647Description: This data type is a non-zero and non-negative value. |
.1.3.6.1.4.1.5491.10.1.6.2.1.3 |