.1.3.6.1.4.1.5491.10.1.3.3 · 1 row entry · 5 columns
Uses the riello variant from /opt/observium/mibs/riello.
Command help
Walk rupsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsInputTable'
A list of input table entries.  The number of entries
is given by the value of upsInputNumLines.
rupsInputEntry row .1.3.6.1.4.1.5491.10.1.3.3.1
An entry containing information applicable to a
particular input line.
Column Syntax OID
The input line identifier.
PositiveInteger
Type Constraints:
range: 1..2147483647
Description:
This data type is a non-zero and non-negative value.
.1.3.6.1.4.1.5491.10.1.3.3.1.1
The present input frequency.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.3.3.1.2
The magnitude of the present input voltage.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.3.3.1.3
The magnitude of the present input current.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.3.3.1.4
The magnitude of the present input true power.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.3.3.1.5
.1.3.6.1.4.1.5491.10.1.4.4 · 1 row entry · 6 columns
Uses the riello variant from /opt/observium/mibs/riello.
Command help
Walk rupsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsOutputTable'
A list of output table entries.  The number of
entries is given by the value of rupsOutputNumLines.
rupsOutputEntry row .1.3.6.1.4.1.5491.10.1.4.4.1
An entry containing information applicable to a
particular output line.
Column Syntax OID
The output line identifier.
PositiveInteger
Type Constraints:
range: 1..2147483647
Description:
This data type is a non-zero and non-negative value.
.1.3.6.1.4.1.5491.10.1.4.4.1.1
The present output voltage.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.4.4.1.2
The present output current.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.4.4.1.3
The present output true power.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.4.4.1.4
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5491.10.1.4.4.1.5
The present output peak current.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.4.4.1.6
.1.3.6.1.4.1.5491.10.1.5.3 · 1 row entry · 4 columns
Uses the riello variant from /opt/observium/mibs/riello.
Command help
Walk rupsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsBypassTable'
A list of bypass table entries.  The number of
entries is given by the value of rupsBypassNumLines.
rupsBypassEntry row .1.3.6.1.4.1.5491.10.1.5.3.1
An entry containing information applicable to a
particular bypass input.
Column Syntax OID
The bypass line identifier.
PositiveInteger
Type Constraints:
range: 1..2147483647
Description:
This data type is a non-zero and non-negative value.
.1.3.6.1.4.1.5491.10.1.5.3.1.1
The present bypass voltage.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.5.3.1.2
The present bypass current.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.5.3.1.3
The present true power conveyed by the bypass.
NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.5491.10.1.5.3.1.4
.1.3.6.1.4.1.5491.10.1.6.2 · 1 row entry · 3 columns
Uses the riello variant from /opt/observium/mibs/riello.
Command help
Walk rupsAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'RIELLOUPS-MIB' -M '/opt/observium/mibs/riello:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'RIELLOUPS-MIB::rupsAlarmTable'
A list of alarm table entries.  The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect.  The table
is initially empty at agent startup.  The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.  The agent creates the first row with
rupsAlarmId equal to 1, and increments the value of
rupsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of rupsAlarmId would otherwise be
exceeded.  Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
rupsAlarmId might have wrapped.
          
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), rupsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device.  No
two rows will have the same value of rupsAlarmDescr,
since alarms define conditions.  In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
          
The number of rows in the table at any given time is
reflected by the value of rupsAlarmsPresent.
rupsAlarmEntry row .1.3.6.1.4.1.5491.10.1.6.2.1
An entry containing information applicable to a





particular alarm.
Indexes
Column Syntax OID
A unique identifier for an alarm condition. This
value must remain constant.
PositiveInteger
Type Constraints:
range: 1..2147483647
Description:
This data type is a non-zero and non-negative value.
.1.3.6.1.4.1.5491.10.1.6.2.1.1
A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition.
ObjectIdentifier .1.3.6.1.4.1.5491.10.1.6.2.1.2
The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the
time of agent startup and presumably existed before
agent startup, the value of rupsAlarmTime shall equal
0.
PositiveInteger
Type Constraints:
range: 1..2147483647
Description:
This data type is a non-zero and non-negative value.
.1.3.6.1.4.1.5491.10.1.6.2.1.3