rPDU2GroupEnergyReset
PowerNet-Inova ·
.1.3.6.1.4.1.63131.1.1.26.11.4
Object
scalar mandatory
r/w
Enumeration
Setting this OID to reset (2) will cause the device energy meter value
on each device in the Rack PDU Network Port Sharing (NPS) group to be
reset to zero.
Each device in the Rack PDU group will also have its corresponding
rPDU2DeviceStatusEnergyStartTime OID value updated.
Getting this OID in models that support this feature will do nothing
and return the noOperation(1) value.
Models that do not support this feature, as well as guest units in an
NPS group, will respond to this OID with a value of notSupported (3).
Attempts to set this OID in these units will fail.
Context
- MIB
- PowerNet-Inova
- OID
.1.3.6.1.4.1.63131.1.1.26.11.4- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- rPDU2Group
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-Inova' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-Inova::rPDU2GroupEnergyReset.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-Inova' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-Inova::rPDU2GroupEnergyReset'
Syntax
Enumeration
Values & Constraints