pdug5OutletGroupControl

PANDUIT-MIB · .1.3.6.1.4.1.19536.10.1.5.3.1.4

Object

Getting this variable will return the group state.
If the group is on, the immediateOn (2)
value will be returned. If the group is off,
the immediateOff (1) value will be returned.
If the state of the group cannot be determined, the
outletUnknown (7) value will be returned. If the
outletUnknown condition should occur, all devices
powered by the PDU should be shut down. The PDU's
power should then be cycled to clear this condition.
Setting this variable to immediateOn (2) will immediately
turn the group on. Setting this variable to
immediateOff (1) will immediately turn the group off.
Setting this variable to immediateReboot (5)
will cause the Switched PDU to perform an immediateOff
command, wait the pdug5OutletControlRebootOffTime
OID time, and then perform an immediateOn command.
Setting this variable to delayedOn (4) will turn the
group on after the pdug5OutletControlSequenceDelay
OID time has elapsed. Setting this variable to
delayedOff (3) will turn the group off after the
pdug5OutletControlShutoffDelay OID time has elapsed.
Setting this variable to delayedReboot  (6) will cause
the Switched PDU to perform a delayedOff command, wait
the pdug5OutletControlRebootOffTime OID time, and
then perform a delayedOn command.

Context

MIB
PANDUIT-MIB
OID
.1.3.6.1.4.1.19536.10.1.5.3.1.4
Type
column
Access
readwrite
Status
current
Parent
pdug5OutletGroupEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5OutletGroupControl'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5OutletGroupControl.<index>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PANDUIT-MIB::pdug5OutletGroupControl'

Syntax

Source
SNMPv2-TCDisplayString
Base type
OctetString
Display format
255a
Type Description
Represents textual information taken from the NVT ASCII
          
character set, as defined in pages 4, 10-11 of RFC 854.
          
To summarize RFC 854, the NVT ASCII repertoire specifies:
          
  - the use of character codes 0-127 (decimal)
          
  - the graphics characters (32-126) are interpreted as
    US ASCII
          
  - NUL, LF, CR, BEL, BS, HT, VT and FF have the special
    meanings specified in RFC 854
          
  - the other 25 codes have no standard interpretation
          
  - the sequence 'CR LF' means newline
          
  - the sequence 'CR NUL' means carriage-return
          
  - an 'LF' not preceded by a 'CR' means moving to the
    same column on the next line.
          
  - the sequence 'CR x' for any x other than LF or NUL is
    illegal.  (Note that this also means that a string may
    end with either 'CR LF' or 'CR NUL', but not with CR.)
          
Any object defined using this syntax may not exceed 255
characters in length.

Values & Constraints

Type Constraints
range: 0..255