PANDUIT-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
20
Rows
20
Columns
243
pdug5IdentTable
table.1.3.6.1.4.1.19536.10.1.1.2
·
1 row entry
·
17 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5IdentTable'
Aggregate Object with number of entries equal to pdug5NumberPDU .
The Identity table entry containing the name, model, manufacturer,
firmware version, part number, etc.
firmware version, part number, etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
Index for the pdug5IdentEntry table.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.1.2.1.1 |
|
The string identify the device in daisy chain. Example PDU A.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.1.2.1.2 |
|
The Device Model.
|
OctetString | .1.3.6.1.4.1.19536.10.1.1.2.1.3 |
|
The Device Manufacturer Name.
|
OctetString | .1.3.6.1.4.1.19536.10.1.1.2.1.4 |
|
The firmware revision level of the device.
|
OctetString | .1.3.6.1.4.1.19536.10.1.1.2.1.5 |
|
Timestamp of when the PDU firmware was last updated
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.1.2.1.6 |
|
The device part number. Example P36E09M.
|
OctetString | .1.3.6.1.4.1.19536.10.1.1.2.1.7 |
|
The device serial number, 10-digit.
|
OctetString | .1.3.6.1.4.1.19536.10.1.1.2.1.8 |
|
The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of failed(4) indicates the devic… |
Enumeration | .1.3.6.1.4.1.19536.10.1.1.2.1.9 |
|
This object indicates whether or not the device is controllable.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.1.2.1.10 |
|
The number of input phase on this pdu 1 or 3.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.1.2.1.11 |
|
The number of groups (breakers) on this pdu.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.1.2.1.12 |
|
The number of outlets in this PDU.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.1.2.1.13 |
|
The assigned MAC address for this PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.1.2.1.14 |
|
The current IPv4 Address.
A value of 0.0.0.0 indicates an error or an unset option. |
SNMPv2-SMIIpAddress Type Constraints: range: 4 |
.1.3.6.1.4.1.19536.10.1.1.2.1.15 |
|
The current IPv6 Address.
A value of 0.0.0.0.0.0 indicates an error or an unset option. |
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.1.2.1.16 |
|
The current Hardware Version.
1.0 - G5 (STM) No Powershare, 1.5 - G5 (STM) with Powershare, 2.0 - G6 Processor |
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.1.2.1.17 |
pdug5ConfigTable
table.1.3.6.1.4.1.19536.10.1.1.3
·
1 row entry
·
12 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5ConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5ConfigTable'
Aggregate Object with number of entries equal to pdug5NumberPDU.
Read Configuration data from the PDU being queried.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
The index of PDU configuration entry.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.1.3.1.1 |
|
Setting this OID to off(0) will disable the SSH connection.
Setting this OID to on(1) will enable the SSH connection. iNC reboot will be required for the settings to take effect. |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.2 |
|
Setting this OID to off(0) will disable the FTPS connection.
Setting this OID to on(1) will enable the FTPS connection. iNC reboot will be required for the settings to take effect |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.3 |
|
Setting this OID to off(0) will disable the HTTP connection.
Setting this OID to on(1) will enable the HTTP connection.iNC reboot will be required for the settings to take effect |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.4 |
|
Setting this OID to off(0) will disable the HTTPS connection.
Setting this OID to on(1) will enable the HTTPS connection.iNC reboot will be required for the settings to take effect |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.5 |
|
Setting this OID to IPv4(1) will enable the IPv4 configuration.
Setting this OID to IPv6(2) will enable the IPv6 configuration. Setting this OID to IPv4&IPv6(3) will enable both IPv4 and IPv6 configuration.iNC reboot wi… |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.6 |
|
Setting this OID to off(0) will disable the Redfish API.
Setting this OID to on(1) will enable the Redfish API.iNC reboot will be required for the settings to take effect |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.7 |
|
Indicates the intended physical orientation of OLED display.
displayNormal(1) indicates normal orientation. displayReverse(2) indicates upside down orientation. |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.8 |
|
Setting this OID to reset(2) will cause the device energy meter value
to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not sup… |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.9 |
|
Getting this OID will return noOperation(0).
Getting this OID to reset(1) will reset iNC. |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.10 |
|
Setting this OID will change daisychain mode. 0:QNA,1:DNA.
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.11 |
|
Setting this OID to off(0) will disable the Telnet connection.
Setting this OID to on(1) will enable the Telnet connection. iNC reboot will be required for the settings to take effect. |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.1.3.1.12 |
pdug5InputTable
table.1.3.6.1.4.1.19536.10.1.2.1
·
1 row entry
·
11 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5InputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5InputTable'
Aggregate Object with number of entries equal to pdug5NumberPDU .
The ident table entry containing the VA, Watts, WH, etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
Type of input - single phase, split phase, three phase delta, or three
phase wye. |
Enumeration | .1.3.6.1.4.1.19536.10.1.2.1.1.1 |
|
The measured input frequency from the PDU meters in tenths of Hz.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.2.1.1.2 |
|
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.2.1.1.3 |
|
A total input VA of all phases. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.1.1.4 |
|
A total input Watts of all phases. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.1.1.5 |
|
A total input Watt-Hour value for all phases. Units are KWh. This value is accumulated since PDU in service.
A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.1.1.6 |
|
A Timestamp of when the Total Input WH was last reset.
|
OctetString | .1.3.6.1.4.1.19536.10.1.2.1.1.7 |
|
A total input Watt-Hour value for all phases. Units are Wh. This value can be reset to 0
using GUI. In that case, the pdug5InputPowerWattHourTimer will be reset as well A negative value indicates that this object is no… |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.1.1.8 |
|
An input PF value. Units are in hundredths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.1.1.9 |
|
An input VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.1.1.10 |
|
All phases total current value. Units are 0.01 amps.
For 3 phase, mathematically add totally 3 phase current together. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.1.1.11 |
pdug5InputPhaseTable
table.1.3.6.1.4.1.19536.10.1.2.2
·
1 row entry
·
43 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5InputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5InputPhaseTable'
Aggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of input phase (pdug5InputPhaseCount).
The input table entry containing the voltage, current, frequency, power for each phase.
Entries are given with number of pdu and number of input phase 1, 2, or 3.
Entries are given with number of pdu and number of input phase 1, 2, or 3.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
Index for the pdug5InputEntry table.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.2.2.1.1 |
|
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.2 |
|
An input voltage measurement value. Values is in 0.1 V.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.3 |
|
Status of the measured input voltage relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.4 |
|
Lower warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.5 |
|
Lower critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.6 |
|
Upper warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.7 |
|
Upper critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.8 |
|
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. |
Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.9 |
|
Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are 0.01 amps. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.10 |
|
An input current measurement value. Units are 0.01 amps.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.11 |
|
Status of the measured input current relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.12 |
|
Lower warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.13 |
|
Lower critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.14 |
|
Upper warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.15 |
|
Upper critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.16 |
|
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.17 |
|
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. |
Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.18 |
|
An input VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.19 |
|
An input Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.20 |
|
A Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0
using GUI. In that case, the pdug5InputPhasePowerWattHourTimer will be reset as well A negative value indicates that this object is not… |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.21 |
|
Timestamp of when input Watt-hours (inputWh) was last reset.
|
OctetString | .1.3.6.1.4.1.19536.10.1.2.2.1.22 |
|
An input PF value. Units are in hundredths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.23 |
|
An input VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.24 |
|
The Reset threshold is the number of volts the reading needs to fall below
the threshold setting for the condition to be cleared. Units are 0.1 volts. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.25 |
|
The number of consecutive sample that the condition is present before
an alarm is raised. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.26 |
|
Input phase voltage alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 … |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.27 |
|
The Reset threshold is the number of amps the reading needs to fall below
the threshold setting for the condition to be cleared. Units are 0.01 amps. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.28 |
|
The number of consecutive sample that the condition is present before
an alarm is raised. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.29 |
|
Input phase current alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 … |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.30 |
|
Lower warning Power threshold. Units are in Watts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.31 |
|
Lower critical Power threshold. Units are in Watts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.32 |
|
Upper warning Power threshold. Units are in Watts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.33 |
|
Upper critical Power threshold. Units are in Watts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.34 |
|
The Reset threshold is the number of watts the reading needs to fall below
the threshold setting for the condition to be cleared. Units are watts. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.35 |
|
The number of consecutive sample that the condition is present before
an alarm is raised. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.36 |
|
Power alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 -… |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.37 |
|
Upper warning Energy threshold. Units are in Watts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.38 |
|
Upper critical Energy threshold. Units are in Watts. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.39 |
|
The Reset threshold is the number of watts the reading needs to fall below
the threshold setting for the condition to be cleared. Units are watts. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.40 |
|
The number of consecutive sample that the condition is present before
an alarm is raised. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.2.1.41 |
|
Energy alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, 1 … |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.2.1.42 |
|
Status of the measured input current relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.2.2.1.43 |
pdug5InputRcmTable
table.1.3.6.1.4.1.19536.10.1.2.3
·
1 row entry
·
9 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5InputRcmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5InputRcmTable'
Aggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of RCM modules per PDU.
The ident table entry containing the RCM Module status, RCM current, RCM module threshold settings, etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
RCM configuration value
off(0) if the PDU doesn't have RCM, on(1) if the PDU has RCM. |
Enumeration | .1.3.6.1.4.1.19536.10.1.2.3.1.1 |
|
RCM module status
ok(2) if the PDU can communicate with the RCM module, failed(4) if the PDU cannot communicate with the RCM module, degraded(3) if the PDU can communicate with the RCM module and the last self-test fail… |
Enumeration | .1.3.6.1.4.1.19536.10.1.2.3.1.2 |
|
RCM Current Upper warning threshold. Units are 0.01 amps.
A negative value indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.3.1.3 |
|
RCM Current Upper critical threshold. Units are 0.01 amps.
A negative value indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.3.1.4 |
|
The Reset threshold is the number of amps the reading needs to fall below
the threshold setting for the condition to be cleared. Units are 0.01 amps. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.3.1.5 |
|
The number of consecutive sample that the condition is present before
an alarm is raised. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.3.1.6 |
|
Rcm current alarm threshold control:
0 - Enable UC and UW 1 - Disable UC and Enable UW 2 - Enable UC and Disable UW 3 - Disable UC and UW 4 and above - Bad input |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.3.1.7 |
|
Status of the measured Rcm current relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.2.3.1.8 |
|
Rcm module current reading. Units are milliAmps.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.2.3.1.9 |
.1.3.6.1.4.1.19536.10.1.2.4
·
1 row entry
·
10 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5InputRcmSelfTestTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5InputRcmSelfTestTable'
Aggregate Object with number of entries equal to number of PDUs (pdug5NumberPDU) and number of Rcm modules per PDU.
The ident table entry containing the Rcm Module Self Test Enable, Schedule, LastRunTime,LastRunStatus etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
Rcm Self Test configuration value
Disable(0) if the self test is disabled on the PDU, Enable(1) if self test is enabled on the PDU . |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.2.4.1.1 |
|
Rcm module self test run frequency , the time for the test is set from Pdug5RcmSelfTestNextRunTime, the self test will be repeated based on the setting as Daily(1),Weekly(2),First Day Of Month(3),Yearly(4)
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.2.4.1.2 |
|
Rcm module self test schedule hour setting (0 to 23 hour),-1 means feature not available
|
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.4.1.3 |
|
Rcm module self test schedule minute setting (0 to 59 minute),-1 means feature not available
|
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.4.1.4 |
|
Rcm module self test schedule day setting
- Can be 0 to 6 when pduInputRcmSelfTestFreq is weekly(2), - Can be 1 to 31 when pduInputRcmSelfTestFreq is monthly(3) or yearly(4), - (-1) means feature not available |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.4.1.5 |
|
Rcm module self test schedule month setting,-1 means feature not available
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.2.4.1.6 |
|
next run date and Time for self test.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.2.4.1.7 |
|
Date and Time when the self test run previously
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.2.4.1.8 |
|
Status of the lastest self test run
|
Enumeration | .1.3.6.1.4.1.19536.10.1.2.4.1.9 |
|
Rcm module on demand self test, 1 to start the on demand self test
|
Integer32r/w | .1.3.6.1.4.1.19536.10.1.2.4.1.10 |
pdug5GroupTable
table.1.3.6.1.4.1.19536.10.1.3.1
·
1 row entry
·
28 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5GroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5GroupTable'
Aggregate Object with number of entries equal to number of PDUs and number of breakers (pdug5GroupCount).
The input table entry containing the name, voltages, currents, power, etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
Index for the pdug5GroupEntry table.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.3.1.1.1 |
|
A descriptive name for the group.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.3.1.1.2 |
|
The type of the group. (5) has no breaker
|
Enumeration | .1.3.6.1.4.1.19536.10.1.3.1.1.3 |
|
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
Enumeration | .1.3.6.1.4.1.19536.10.1.3.1.1.4 |
|
Units are 0.1 volts.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.5 |
|
Status of the measured group voltage relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.3.1.1.6 |
|
Lower warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. |
Integer32 | .1.3.6.1.4.1.19536.10.1.3.1.1.7 |
|
Lower critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. |
Integer32 | .1.3.6.1.4.1.19536.10.1.3.1.1.8 |
|
Upper warning threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. |
Integer32 | .1.3.6.1.4.1.19536.10.1.3.1.1.9 |
|
Upper critical threshold. Units are 0.1 volts. A negative value indicates
that this object is not available. |
Integer32 | .1.3.6.1.4.1.19536.10.1.3.1.1.10 |
|
Rated current capacity of the group. Units are 0.01 amps. A negative
value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups). |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.11 |
|
A group current measurement value. Units are 0.01 amps.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.12 |
|
Status of the measured group current relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.3.1.1.13 |
|
Lower warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.3.1.1.14 |
|
Lower critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.3.1.1.15 |
|
Upper warning threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.3.1.1.16 |
|
Upper critical threshold. Units are 0.01 amps. A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.3.1.1.17 |
|
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.18 |
|
A group VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.19 |
|
A group power value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.20 |
|
A Watt-Hour value for each section. Units are WH. This value can be reset to 0
using GUI. In that case, the pdug5GroupPowerWattHourTimer will be reset as well. A negative value indicates that this object is not availab… |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.21 |
|
Timestamp of when group Watt-hours (groupWh) was last reset.
|
OctetString | .1.3.6.1.4.1.19536.10.1.3.1.1.22 |
|
A group PF value. Units are in hundredths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.23 |
|
A group VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.24 |
|
The number of outlets in each group (breaker).
|
Integer32 | .1.3.6.1.4.1.19536.10.1.3.1.1.25 |
|
Only applicable to groups with breaker. Indicates whether a breaker is turned
off or on. |
Enumeration | .1.3.6.1.4.1.19536.10.1.3.1.1.26 |
|
Circuit Breaker voltage alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit… |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.27 |
|
Circuit Breaker current alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit… |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.3.1.1.28 |
pdug5EnvProbeTable
table.1.3.6.1.4.1.19536.10.1.4.1
·
1 row entry
·
8 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5EnvProbeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5EnvProbeTable'
A list of environment probe (1 per PDU) for temperature, humidity, and contacts. The number of entries is given by number of PDUs in daisy chain.
Aggregate entries equal to number of PDUs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
Scale used to return temperature objects.
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.4.1.1.1 |
|
The number of temperature measurements.The MAX is 6 (1 per probe).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.1.1.2 |
|
The number of humidity measurements.The MAX is 6(1 per probe).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.1.1.3 |
|
The number of door sensors.The MAX is 6(1 per probe).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.1.1.4 |
|
The number of dry sensors.The MAX is 2(1 per probe).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.1.1.5 |
|
The number of spot sensors.The MAX is 2(1 per probe).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.1.1.6 |
|
The number of rope sensors.The MAX is 2(1 per probe).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.1.1.7 |
|
The number of hid sensors. The MAX is 2(1 per probe).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.1.1.10 |
pdug5TemperatureTable
table.1.3.6.1.4.1.19536.10.1.4.2
·
1 row entry
·
10 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5TemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5TemperatureTable'
A list of temperature probe measurements. The number of entries are given by number of pdu and pdug5TemperatureCount.
An entry for a temperature measurement.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount. |
Integer32 | .1.3.6.1.4.1.19536.10.1.4.2.1.1 |
|
A descriptive name for the temperature probe.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.4.2.1.2 |
|
Indicates whether a probe is connected or not.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.2.1.3 |
|
Units are degree(either Fahrenheit or Celsius).
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.2.1.4 |
|
Status of the measured temperature relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.2.1.5 |
|
Lower warning threshold. Units are degrees. A negative value
indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.4.2.1.6 |
|
Lower critical threshold. Units are degrees. A negative value
indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.4.2.1.7 |
|
Upper warning threshold. Units are degrees. A negative value
indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.4.2.1.8 |
|
Upper critical threshold. Units are degrees. A negative value
indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.4.2.1.9 |
|
Temperature alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enabl… |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.2.1.10 |
pdug5HumidityTable
table.1.3.6.1.4.1.19536.10.1.4.3
·
1 row entry
·
10 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5HumidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5HumidityTable'
A list of humidity probe measurements. The number of entries are given by number of pdu and pdug5HumidityCount.
An entry for a humidity measurement.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
A unique value for each humidity probe measurement. Its value
ranges from 1 to pdug5HumidityCount per PDU. |
Integer32 | .1.3.6.1.4.1.19536.10.1.4.3.1.1 |
|
A descriptive name for the humidity probe.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.4.3.1.2 |
|
Indicates whether a probe is connected or not.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.3.1.3 |
|
Units are %RH.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.3.1.4 |
|
Status of the measured humidity relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.3.1.5 |
|
Lower warning threshold. Units are %RH. A negative value
indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.4.3.1.6 |
|
Lower critical threshold. Units are %RH. A negative value
indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.4.3.1.7 |
|
Upper warning threshold. Units are %RH. A negative value
indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.4.3.1.8 |
|
Upper critical threshold. Units are %RH. A negative value
indicates that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.4.3.1.9 |
|
Humidity alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 - enable, … |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.3.1.10 |
pdug5DoorTable
table.1.3.6.1.4.1.19536.10.1.4.4
·
1 row entry
·
4 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5DoorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5DoorTable'
A list of door sensors. The number of entries are given by number of PDU and pdug5DoorCount.
An entry for a door sensor
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
A unique value for each door sensor. Its value ranges from 1 to
doorCount. |
Integer32 | .1.3.6.1.4.1.19536.10.1.4.4.1.1 |
|
A descriptive name for the door sensor.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.4.4.1.2 |
|
Indicates whether a probe is connected or not.
Will not be returned if the door sensor is internal to the ePDU, in that case only doorState should be read. |
Enumeration | .1.3.6.1.4.1.19536.10.1.4.4.1.3 |
|
The state of the door sensor.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.4.1.4 |
pdug5DryTable
table.1.3.6.1.4.1.19536.10.1.4.5
·
1 row entry
·
4 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5DryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5DryTable'
A list of dry sensors. The number of entries are given by number of pdu and pdug5DryCount.
An entry for a contact sensor
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
A unique value for each dry sensor. Its value ranges from 1 to
dryCount. |
Integer32 | .1.3.6.1.4.1.19536.10.1.4.5.1.1 |
|
A descriptive name for the dry sensor.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.4.5.1.2 |
|
Indicates whether a probe is connected or not.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.5.1.3 |
|
The state of the dry sensor.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.5.1.4 |
pdug5SpotTable
table.1.3.6.1.4.1.19536.10.1.4.6
·
1 row entry
·
4 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5SpotTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5SpotTable'
A list of contact sensors. The number of entries are given by number of pdu and pdug5SpotCount.
An entry for a contact sensor
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
A unique value for each spot sensor. Its value ranges from 1 to
spotCount. |
Integer32 | .1.3.6.1.4.1.19536.10.1.4.6.1.1 |
|
A descriptive name for the spot sensor.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.4.6.1.2 |
|
Indicates whether a probe is connected or not.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.6.1.3 |
|
The state of the spot sensor.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.6.1.4 |
pdug5RopeTable
table.1.3.6.1.4.1.19536.10.1.4.7
·
1 row entry
·
4 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5RopeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5RopeTable'
A list of rope sensors. The number of entries are given by number of pdu and pdug5RopeCount.
An entry for a contact sensor
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
A unique value for each rope sensor. Its value ranges from 1 to
ropeCount. |
Integer32 | .1.3.6.1.4.1.19536.10.1.4.7.1.1 |
|
A descriptive name for the rope sensor.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.4.7.1.2 |
|
Indicates whether a probe is connected or not.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.7.1.3 |
|
The state of the rope sensor.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.7.1.4 |
pdug5EnvHidTable
table.1.3.6.1.4.1.19536.10.1.4.10.1
·
1 row entry
·
15 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5EnvHidTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5EnvHidTable'
A list of contact sensors. The number of entries are given by number of pdu and pdug5HidCount.
An entry for a contact sensor
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
The index of the PDU HID table entry
|
Integer32 | .1.3.6.1.4.1.19536.10.1.4.10.1.1.1 |
|
Aisle of HID handle.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.10.1.1.2 |
|
HID handle control operations
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.4.10.1.1.3 |
|
The firmware revision level of the HID
|
OctetString | .1.3.6.1.4.1.19536.10.1.4.10.1.1.4 |
|
HID Mechanical operations
|
Enumeration | .1.3.6.1.4.1.19536.10.1.4.10.1.1.5 |
|
The Serial Number of the HID
|
OctetString | .1.3.6.1.4.1.19536.10.1.4.10.1.1.6 |
|
The hardware revision level of the HID
|
OctetString | .1.3.6.1.4.1.19536.10.1.4.10.1.1.7 |
|
HID Electronic Latch Autolock Time in seconds, Value ranges (0-999)
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.10.1.1.8 |
|
HID Door Open Time in seconds, Value ranges (0-999)
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.10.1.1.9 |
|
HID Max Door Open Time in seconds, Value ranges (0-32400),
critical alarm will be raised if door is left open past this time |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.10.1.1.10 |
|
Rack Access User minimum PIN Length, value ranges(0-16)
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.10.1.1.11 |
|
Rack Access User PIN mode setting
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.4.10.1.1.12 |
|
Rack Access Aisle Control setting,
when set to standalone each aisle will controlled separately, when set to combined opposite aisle can be controlled with authenticated control action on either aisle |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.4.10.1.1.13 |
|
Beacon Function Control
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.4.10.1.1.14 |
|
Beacon Color Control
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.4.10.1.1.15 |
pdug5EnvHidControlTable
table.1.3.6.1.4.1.19536.10.1.4.10.2
·
1 row entry
·
10 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5EnvHidControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5EnvHidControlTable'
A list of smartcard. The number of entries are given by number of pdu and pdug5HidCount.
The smart card table entry containing the username, cardid, cardaisle etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
The index of the PDU smartcard table entry
|
Integer32 | .1.3.6.1.4.1.19536.10.1.4.10.2.1.1 |
|
User name of smartcard.
Use #delete# to delete the HID user |
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.4.10.2.1.2 |
|
HID smartcard ID.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.4.10.2.1.3 |
|
Indicates the date and time of accessing
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.4.10.2.1.4 |
|
Aisle of authorized card
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.4.10.2.1.5 |
|
Indicates the start date and time Rack access user is given access
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.4.10.2.1.6 |
|
Indicates the date and time when the access of user card will expire, To set expire time first set user as temporary user
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.4.10.2.1.7 |
|
Indicates if the card user has temporary access
|
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.4.10.2.1.8 |
|
Rack access control entry keypad PIN
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.4.10.2.1.9 |
|
Smartrack Access Card ID String
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.4.10.2.1.10 |
pdug5OutletTable
table.1.3.6.1.4.1.19536.10.1.5.1
·
1 row entry
·
21 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5OutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5OutletTable'
Aggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex) and Number of outlet per PDU (pdug5OutletIndex).
The Outlet table entry containing the type, voltage, current etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
Index for each outlet, value from 1 to the number of outlets per PDU.
|
Integer32 | .1.3.6.1.4.1.19536.10.1.5.1.1.1 |
|
A descriptive name for the outlet.
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.5.1.1.2 |
|
Type of this outlet - C13, C19, 5-20R, iecC13/C15 COMBO, iecC13/C15/C19 COMBO...
|
Enumeration | .1.3.6.1.4.1.19536.10.1.5.1.1.3 |
|
Rated current capacity of this outlet. Units are 0.01 amps. A negative
value indicates that the hardware current capacity is unknown. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.4 |
|
A outlet current measurement value. Units are 0.01 amps.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.5 |
|
Status of the measured outlet active power relative to the configured thresholds.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.5.1.1.6 |
|
Lower warning threshold. Units are Watts(W). A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.1.1.7 |
|
Lower critical threshold. Units are Watts(W). A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.1.1.8 |
|
Upper warning threshold. Units are Watts(W). A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.1.1.9 |
|
Upper critical threshold. Units are Watts(W). A negative value indicates
that this object is not available. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.1.1.10 |
|
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.11 |
|
A outlet VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.12 |
|
A outlet Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.13 |
|
A Watt-Hour value for each outlet. Units are WH.
This object is writable so that it can be reset to 0. When it is written to, the pdug5OutletWhTimer will be reset updated as well A negative value indicates that this o… |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.14 |
|
Timestamp (date and time) of outlet Watt-hours was last reset.
|
OctetString | .1.3.6.1.4.1.19536.10.1.5.1.1.15 |
|
An outlet PF value. Units are in hundredths, for example a power factor
of 0.95 would be returned as 95, and 0.92 would be returned as 92. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.16 |
|
An outlet VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.17 |
|
The branch number outlet located.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.18 |
|
The Reset threshold is the number of watss the reading needs to fall below
the threshold setting for the condition to be cleared. Units are watts. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.1.1.19 |
|
The number of consecutive sample that the condition is present before
an alarm is raised. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.1.1.20 |
|
Outlet Active Power alarm threshold control:
bit 0: up critical alarm control bit, 0 - enable, 1 - disable bit 1: up warning alarm control bit, 0 - enable, 1 - disable bit 2: low warning alarm control bit, 0 … |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.1.1.21 |
pdug5OutletControlTable
table.1.3.6.1.4.1.19536.10.1.5.2
·
1 row entry
·
10 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5OutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5OutletControlTable'
Aggregate Object with number of entries equal to Number of PDU (pdug5IdentIndex) and Number of outlets per PDU (pdug5OutletIndex).
The Outlet table entry containing the type, voltage, current etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
current state of a control outlet.
|
Enumeration | .1.3.6.1.4.1.19536.10.1.5.2.1.1 |
|
When write, once issued, the outlet will turn Off immediately.
0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet Off command When read, returns -1 if no command is pending, or the curre… |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.2.1.2 |
|
When write, once issued, the outlet will turn On immediately.
0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet On command When read, returns -1 if no command is pending, or the current… |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.2.1.3 |
|
When write, for outlets that are On prior to this Reboot command, they will
switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets that a… |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.2.1.4 |
|
Determines the outlet state when power is applied to the unit.
1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequenceTime 3 : should take the state the outlet had when power was… |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.5.2.1.5 |
|
Time delay in seconds from when a Global Sequence On command is issued to when
the command is executed on this outlet. This delay is also used as a power-on delay. |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.2.1.6 |
|
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
|
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.2.1.7 |
|
Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled 2 : control On/Off disabled. |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.5.2.1.8 |
|
Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first then write it to the command pdug5OutletControlO… |
Integer32r/w | .1.3.6.1.4.1.19536.10.1.5.2.1.9 |
|
Getting this variable will return the outlet state.
If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot b… |
Enumerationr/w | .1.3.6.1.4.1.19536.10.1.5.2.1.10 |
pdug5OutletGroupTable
table.1.3.6.1.4.1.19536.10.1.5.3
·
1 row entry
·
6 columns
Uses the panduit variant from
Command help
/opt/observium/mibs/panduit.
Walk pdug5OutletGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PANDUIT-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PANDUIT-MIB::pdug5OutletGroupTable'
Aggregate Object with Number of outlets per Group (pdug5OutletGroupsIndex).
The Outlet Group table entry containing the count, name, member etc.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
The numeric Switched Outlet Groups Count
|
Integer32 | .1.3.6.1.4.1.19536.10.1.5.3.1.1 |
|
The user-defined switched outlet Groups Name string
|
OctetStringr/w | .1.3.6.1.4.1.19536.10.1.5.3.1.2 |
|
The user-defined switched outlet Group Members string
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.5.3.1.3 |
|
Getting this variable will return the group state.
If the group is on, the immediateOn (2) value will be returned. If the group is off, the immediateOff (1) value will be returned. If the state of the group cannot be de… |
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.19536.10.1.5.3.1.4 |
|
The Sum of Active power of all Grouped Outlet.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.3.1.5 |
|
The Sum of Apparent power of all Grouped Outlet.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.19536.10.1.5.3.1.6 |