lgpPwrStateUpsModuleRedundantCount

LIEBERT-GP-POWER-MIB · .1.3.6.1.4.1.476.1.42.3.5.3.41.2

Object

scalar CountSNMPv2-SMIInteger32
Number of redundant UPS modules in the system. In a single module
system, the value is zero. This value is dependent upon the present
load and the number of modules (i.e. the value may change during normal
operation based upon a load change). This value represents the number
of extra modules above the minimum needed to support the load.

Context

MIB
LIEBERT-GP-POWER-MIB
OID
.1.3.6.1.4.1.476.1.42.3.5.3.41.2
Type
scalar
Access
readonly
Status
current
Units
Count
Parent
lgpPwrStateModuleGroup

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'LIEBERT-GP-POWER-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-POWER-MIB::lgpPwrStateUpsModuleRedundantCount.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'LIEBERT-GP-POWER-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'LIEBERT-GP-POWER-MIB::lgpPwrStateUpsModuleRedundantCount'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647