lgpPwrMeasurementPointTruePower
LIEBERT-GP-POWER-MIB ·
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.8
Object
column WattSNMPv2-SMIInteger32
The present AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
Context
- MIB
- LIEBERT-GP-POWER-MIB
- OID
.1.3.6.1.4.1.476.1.42.3.5.2.2.1.8- Type
- column
- Access
- readonly
- Status
- current
- Units
- Watt
- Parent
- lgpPwrMeasurementPointEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'LIEBERT-GP-POWER-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointTruePower'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'LIEBERT-GP-POWER-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointTruePower.<lgpPwrMeasurementPointIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'LIEBERT-GP-POWER-MIB' -M '/opt/observium/mibs/liebert:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'LIEBERT-GP-POWER-MIB::lgpPwrMeasurementPointTruePower'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647