lgpPwrBypassReXfrRemainTime

LIEBERT-GP-POWER-MIB · .1.3.6.1.4.1.476.1.42.3.5.3.54

Object

scalar seconds Integer32
The time remaining before an inverter overload or inverter fault can 
be cleared and auto retransfer from the bypass to the inverter can take 
place. 
          
Note: If an inverter overload or fault is not taking place, this point
will return 65535.

Context

MIB
LIEBERT-GP-POWER-MIB
OID
.1.3.6.1.4.1.476.1.42.3.5.3.54
Type
scalar
Access
readonly
Status
current
Units
seconds
Parent
lgpPwrStatus

Syntax

seconds Integer32

Values & Constraints

No enumerated values or constraints recorded.