lgpEnvConfigFilterServiceInterval

LIEBERT-GP-ENVIRONMENTAL-MIB · .1.3.6.1.4.1.476.1.42.3.4.4.10

Object

scalar r/w hours Unsigned32
The amount of time, in hours, between scheduled maintenance
of the system filter.  When the filter service timer reaches this
value an lgpConditionChangeFilter will be activated.  Once service
has been completed the filter service timer should be reset to 0.

Context

MIB
LIEBERT-GP-ENVIRONMENTAL-MIB
OID
.1.3.6.1.4.1.476.1.42.3.4.4.10
Type
scalar
Access
readwrite
Status
current
Units
hours
Parent
lgpEnvConfig

Syntax

hours Unsigned32

Values & Constraints

No enumerated values or constraints recorded.