lgpEnvConfigFanSpeedPropBandDegC
LIEBERT-GP-ENVIRONMENTAL-MIB ·
.1.3.6.1.4.1.476.1.42.3.4.4.46
Object
scalar
r/w
degrees Celsius Integer32
Temperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan speed operations are proportionally controlled.
Context
- MIB
- LIEBERT-GP-ENVIRONMENTAL-MIB
- OID
.1.3.6.1.4.1.476.1.42.3.4.4.46- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- degrees Celsius
- Parent
- lgpEnvConfig
Syntax
degrees Celsius Integer32
Values & Constraints
No enumerated values or constraints recorded.