hwSetLvdVoltage
EMAP-MIB ·
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.5
Object
column r/w
Integer32
Low-voltage power-off voltage of a power-off unit can be configured by users. Its value range: 35 to 56, units: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. NOTE: There is linkage between hwSetLvdVoltage and hwSetLvdReconnectedVoltage
Context
- MIB
- EMAP-MIB
- OID
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.5- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- hwLvdBranchEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSetLvdVoltage'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSetLvdVoltage.<hwLvdBranchIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'EMAP-MIB::hwSetLvdVoltage'
Syntax
Integer32
Values & Constraints
Object Constraints
range: 350-560