EMAP-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
46
Rows
46
Columns
532
hwSiteActiveAlarmTable
table.1.3.6.1.4.1.2011.6.164.1.1.2.99
·
1 row entry
·
12 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteActiveAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteActiveAlarmTable'
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Site active alarm table index. It is the unique ID of the site alarm.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.1 |
||||||||||||
|
Active alarm name. It is of the character string type, and used to specify the content of a specific alarm.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.2 |
||||||||||||
|
Active alarm level, which users can configure the alarm severity, is an enumeration type:
If the enumeration value is 1, it indicates a critical alarm; If the enumeration value is 2, it indicates a major alarm; If the e… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.3 |
||||||||||||
|
Active alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.4 |
||||||||||||
|
Active alarm time. It is of the character string type, and used to specify the content of a specific alarm.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.5 |
||||||||||||
|
Site name, which users can configure, is used to specify a site. Otherwise, the configured character can not be any other languages except English.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.6 |
||||||||||||
|
Site administrant address, which users can assigned, is the unique ID of a site. It is used for device management by NMS, and value range is 0 to 65535.
|
Unsigned32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.7 |
||||||||||||
|
NE ID. It is of the character string type. It is the unique ID of the site (an independent network element (NE)) on the network. Otherwise, the configured character can not be any other languages except English.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.8 |
||||||||||||
|
Site description. It is of the character string type. It is used to describe the site information such as the site location, which users can configure. Otherwise, the configured character can not be any other languages…
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.9 |
||||||||||||
|
Equipment ID. Value range: 000,000 to 000,100, in which the first three digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.10 |
||||||||||||
|
Equipment name. It is of the character string type, and users can set the name of the monitor.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.11 |
||||||||||||
|
Rowstatus of active alarm table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.100 |
hwSiteAlarmTable
table.1.3.6.1.4.1.2011.6.164.1.1.2.100
·
1 row entry
·
5 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteAlarmTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Site alarm table index. It is the unique ID of the site alarm.
|
Unsigned32 Constraints: range: 1-4294967295 |
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.1 |
||||||||||||
|
Alarm name. It is of the character string type, and used to specify the content of a specific alarm.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.2 |
||||||||||||
|
Alarm level, which users can configure the alarm severity, is an enumeration type:
If the enumeration value is 1, it indicates a critical alarm; If the enumeration value is 2, it indicates a major alarm; If the enumerat… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.3 |
||||||||||||
|
Alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.4 |
||||||||||||
|
RowStatus of site alarms table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.100 |
hwMonitorTable
table.1.3.6.1.4.1.2011.6.164.1.2.2.1
·
1 row entry
·
14 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwMonitorTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Table index of the site monitors (hwSiteMonitorTable) is restricted by the quantity of the site monitors (hwMonsQuantity).
Value range: 1 to 100. |
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.1 |
||||||||||||
|
Site monitor ID.
Value range: 001,001 to 001,100, in which the first three digits indicate the device type and the last three digits indicate the device SN. |
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.2 |
||||||||||||
|
Monitor name. It is of the character string type, and users can set the name of the monitor.
Otherwise, the configured character can not be any other languages except English. |
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.3 |
||||||||||||
|
Monitor description. It is of the character string type. Users can set the description of the monitor.
Otherwise, the configured character can not be any other languages except English. |
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.4 |
||||||||||||
|
Monitor software version. It is of the character string type.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.5 |
||||||||||||
|
Monitor printed circuit board (PCB) hardware version. It is of the character string type.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.6 |
||||||||||||
|
Monitor manufacture. It is of the character string type, and is an inherent attribute of the device.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.7 |
||||||||||||
|
Monitor production date. It is of the character string type, and is an inherent attribute of the device.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.8 |
||||||||||||
|
Production SN of the monitor. It is the electronic tag of the products.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.9 |
||||||||||||
|
Total monitor runtime. The monitor counts the data in real time.
Value range is 0 to 65535, The value is an integer (1), Units:hours. (h). It is used for performance measurement and evaluation of the monitor. |
Unsigned32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.10 |
||||||||||||
|
Monitor control status. It is an enumeration type:
If the enumeration value is 1, it indicates the background control; If the enumeration value is 2, it indicates the automatic control. If the enumeration value is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.11 |
||||||||||||
|
Warm-reset control of the monitor. It is an enumeration type:
If the enumeration value is 1, it indicates the Warm-reset control of the monitor is normal; If the enumeration value is 2, it indicates the Warm-reset contr… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.12 |
||||||||||||
|
State of the site monitor module. It is an enumeration type:
If the enumeration value is 1, it indicates that the site monitor module is in the normal state; If the enumeration value is 2, it indicates that the monitor… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.99 |
||||||||||||
|
RowStatus of site monitor.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.100 |
hwRectConfigTable
table.1.3.6.1.4.1.2011.6.164.1.3.2.1
·
1 row entry
·
13 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwRectConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwRectConfigTable'
Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off. This table's index is hwRectConfigIndex, clone Rectifier config information table.
Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off.
This table's index is hwRe…
This table's index is hwRe…
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Index of the device configuration list for the rectifier modules, which value range: 1 to 256(To the actual subject). Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectsTotalQ…
|
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.1 |
||||||||||||
|
Rectifier module ID. Value range: 002'001 to 002'255. The first digits indicate the device type and last three digits indicate the device SN.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.2 |
||||||||||||
|
Device name of the rectifier module, character string type, is used to specify the rectifier module. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.3 |
||||||||||||
|
Specific type of the rectifier module. It is an enumeration type:
If the enumeration value is 1, it indicates a 5A rectifier module; If the enumeration value is 2, it indicates a 15A rectifier module; If the enumerati… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.4 |
||||||||||||
|
Software version of the rectifier module. It indicates the software version ID of the module.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.5 |
||||||||||||
|
Manufacture of the rectifier module.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.6 |
||||||||||||
|
Manufacture date of rectifiers is of string type.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.7 |
||||||||||||
|
Rectifier module SN. It indicates the electronic tag of the product.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.8 |
||||||||||||
|
Rated voltage of the rectifier module, is an inherent attribute.
Value range: 0 to 200, Units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Unsigned32 Constraints: range: 0-2000 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.9 |
||||||||||||
|
Efficiency of the rectifier module, is an inherent attribute.
Value range: 0 to 100, Units: %, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.10 |
||||||||||||
|
Input AC type of the rectifier module. It is an enumeration value:
If the value of the node is 1, it indicates single-phase AC input; If the value of the node is 2, it indicates three-phase AC input; If the value of th… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.11 |
||||||||||||
|
Power-on or power-off of the rectifier module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the rectifier module:
If the NMS notifies the… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.12 |
||||||||||||
|
RowStatus of rectifier config table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.100 |
hwRectOperTable
table.1.3.6.1.4.1.2011.6.164.1.3.2.2
·
1 row entry
·
10 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwRectOperTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwRectOperTable'
Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status. This table's index is hwRectRunIndex, clone rectifier runing information table.
Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status.
This table's index is hwRectRunIndex, clone rectifier runing information t…
This table's index is hwRectRunIndex, clone rectifier runing information t…
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Table index of the running rectifier modules,
which value range: 1 to 256(To the actual subject). Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectsTotalQuantity). |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.1 |
||||||||||||||||||||||
|
Output current of the rectifier module. It is a real-time analog parameter.
Value range: 0 to 300, Units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates … |
Unsigned32 Constraints: range: 0-3000 |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.2 |
||||||||||||||||||||||
|
Output voltage of the rectifier module. It is a real-time analog parameter.
Value range: 0 to 65, Units: V, the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that … |
Unsigned32 Constraints: range: 0-650 |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.3 |
||||||||||||||||||||||
|
Total runtime of the rectifier module.
Value units: minute (m), and the value is an integer (1). |
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.4 |
||||||||||||||||||||||
|
DC output power.
Value range: 0 to 30000, units: W, and the value is an integer.(1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-30000 |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.5 |
||||||||||||||||||||||
|
AC input voltage.
Value range: 0 to 600, units: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-6000 |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.6 |
||||||||||||||||||||||
|
Rated Efficiency.
Value range: 0 to 100, units: %, and the value is an integer.(1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.7 |
||||||||||||||||||||||
|
Rectifier Temperature.
Value range: -300 to 300, units: degC, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -3000-3000 |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.8 |
||||||||||||||||||||||
|
State of the rectifier module. It is an enumeration type:
If the enumeration value is 1, the rectifier module is in the normal state; If the enumeration value is 2, a fault occurs on the rectifier module; If the enume… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.99 |
||||||||||||||||||||||
|
RowStatus of rectifier runing table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.100 |
hwBattsTestResultTable
table.1.3.6.1.4.1.2011.6.164.1.4.3.100
·
1 row entry
·
12 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwBattsTestResultTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwBattsTestResultTable'
Battery test result record table. Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and test terminated course. This table's index is hwBattsTestResultIndex, clone Battery test result record table.
Battery test result record table.
Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and t…
Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and t…
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Table index of the battery test results. Currently up to 10 times of the battery test results are saved by default.
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.1 |
||||||||||||||||
|
Record test type of the battery test. It is an enumeration value:
If the NMS notifies the SNMP agent that this node is set to 1, it indicates a manual test; If the NMS notifies the SNMP agent that this node is set to … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.2 |
||||||||||||||||
|
Test start time of the record in the battery test. It is of the character string type.
|
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.3 |
||||||||||||||||
|
Battery test result. It is an enumeration value.
If the enumeration value of the node is 1, it indicates that the battery test has no result: If the enumeration value of the node is 2, it indicates that the battery is … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.4 |
||||||||||||||||
|
Battery efficiency test.
Value range: 0 to 100, Units: %, and the value is an integer (1). If the value is -1, it indicates that the test value is inefficient. If the value is 255, it indicates that the test valu… |
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.5 |
||||||||||||||||
|
Discharge time of the battery test records.
Value range: 0 to 100, units: hour (h), and the value is accurate to two decimal places (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inva… |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.6 |
||||||||||||||||
|
Discharge termination voltage of the battery test.
Value range: 0 to 60, units: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-600 |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.7 |
||||||||||||||||
|
Average discharge current of the battery test.
Value range: -1000 to 1000, units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inval… |
Integer32 Constraints: range: -10000-10000 |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.8 |
||||||||||||||||
|
Discharge ampere per hour the battery test.
Value range: 0 to 5000, Units: Ah, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-5000 |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.9 |
||||||||||||||||
|
Battery temperature of the battery test termination.
Value range: -50 to +100, Units: centigrade (degC), and the value is an integer (1). If the value is -1024, it indicates that no battery temperature value sensor … |
Integer32 Constraints: range: -50-100 |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.10 |
||||||||||||||||
|
Termination factors of the battery test. It is an enumeration value.
If the enumeration value is 1, it indicates that the voltage value of the battery test reaches the set termination voltage; If the enumeration value… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.11 |
||||||||||||||||
|
RowStatus of battery test table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.100 |
hwBattStringConfigTable
table.1.3.6.1.4.1.2011.6.164.1.4.4.1
·
1 row entry
·
10 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwBattStringConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwBattStringConfigTable'
Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone battery string config table.
Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone …
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Device table index of the battery string,
value range: 1 to 100(To the actual subject). |
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.1 |
||||||||||||
|
Batteries device ID, can be configured by users. Value range: 003,001 to 003,100, in which the first three digits specify the device type and the last three specify the device SN.
|
Unsigned32 Constraints: range: 3001-3100 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.2 |
||||||||||||
|
Batteries device name, of the character string type, is used to specify the batteries. Users can configure it. Otherwise, the configured character can not be any other languages except English.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.3 |
||||||||||||
|
Upper threshold of the battery temperature alarm, can be configured by users.
Value range: 25 to 80, Units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates t… |
Integer32r/w Constraints: range: 25-80 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.4 |
||||||||||||
|
Lower threshold of the battery temperature alarm, can be configured by users.
Value range: -20 to 20, Units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates … |
Integer32r/w Constraints: range: -20-20 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.5 |
||||||||||||
|
Upper threshold of the battery temperature measurement, can be configured by users.
Value range: 0 to 100, Units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indic… |
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.6 |
||||||||||||
|
Lower threshold of the battery temperature measurement, can be configured by users.
Value range: -50 to 0, Units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indic… |
Integer32r/w Constraints: range: -50-0 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.7 |
||||||||||||
|
Set battery standard capacity, is an inherent attribute of the device.
Value range: 5 to 10000, units: Ah, the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invali… |
Integer32r/w Constraints: range: 5-10000 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.8 |
||||||||||||
|
Set battery install time, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English.
|
OctetStringr/w Constraints: range: 0-128 |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.9 |
||||||||||||
|
RowStatus of battery string config table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.100 |
hwBattStringOperTable
table.1.3.6.1.4.1.2011.6.164.1.4.4.2
·
1 row entry
·
9 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwBattStringOperTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwBattStringOperTable'
Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as battery temperature. This table's index is hwBattStringRunIndex, clone battery string runing table.
Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as battery temperature.
This table's index is hwBattStri…
This table's index is hwBattStri…
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Device table index of the battery string,
which value range: 1 to 100(To the actual subject). |
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.1 |
||||||||||||||||||||
|
Batteries current. It is an analog parameter collected by the battery string in real time.
Value range: -1000 to +1000, units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7F… |
Integer32 Constraints: range: -10000-10000 |
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.2 |
||||||||||||||||||||
|
Remaining capacity percentage of the battery string.
Value range: 0 to 100, units: %, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inva… |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.3 |
||||||||||||||||||||
|
Remaining capacity of the battery string. It is an analog parameter collected by the battery string in real time.
Value range: 0 to 1000, units: Ah, and the value is an integer (1). If the value is 2147483647(0x7FF… |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.4 |
||||||||||||||||||||
|
Batteries actual capacity. It is an analog parameter collected by the battery string in real time.
Value range: 0 to 5000, units: Ah, the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates… |
Unsigned32 Constraints: range: 0-5000 |
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.5 |
||||||||||||||||||||
|
Battery temperature. It is a battery parameter collected in real time.
Value range: -300 to +200, unit: centigrade (degC), and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), … |
Integer32 Constraints: range: -3000-2000 |
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.6 |
||||||||||||||||||||
|
Batteries midpoint voltage. It is an analog parameter collected by the battery string in real time.
Value range: -90 to +90, unit: V, and the value is accurate to one decimal place (.1). |
Integer32 Constraints: range: -900-900 |
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.7 |
||||||||||||||||||||
|
State of the site battery string module. It is an enumeration type:
If the enumeration value is 1, it indicates that the site battery string is in the normal state; If the enumeration value is 2, it indicates that the… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.99 |
||||||||||||||||||||
|
RowStatus of battery string runing table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.100 |
hwAcInputTable
table.1.3.6.1.4.1.2011.6.164.1.5.2.1
·
1 row entry
·
12 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwAcInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcInputTable'
AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status, as well as AC output breakers quantity, which defines hwAcOutputBreakerTable row number. This table's index is hwAcInputIndex, clone AC input table.
AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status,
as well as AC outpu…
as well as AC outpu…
Indexes
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
ACU device table index,
which value range: 1 to 100. Lines of the device list are restricted by the total quantity of ACUs (hwAcsInputQuantity). |
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.1 |
||||||||||||||||||
|
ACU device ID, which users can configure. Value range: 004,001 to 004,100,
in which The first digits indicate the device type and the last three digits indicate the device SN. |
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.2 |
||||||||||||||||||
|
ACU device name, of the character string type, is used to specify the alternating current unit (ACU).
Users can configure it. Otherwise, the configured character can not be any other languages except English. |
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.3 |
||||||||||||||||||
|
ACU A-phase or AB-line voltage.
Value range: 0 to 600, units: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-6000 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.4 |
||||||||||||||||||
|
ACU B-phase or BC-line voltage.
Value range: 0 to 600, units: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-6000 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.5 |
||||||||||||||||||
|
ACU C-phase or CA-line voltage.
Value range: 0 to 600, units: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-6000 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.6 |
||||||||||||||||||
|
ACU A-phase current. It is an analog parameter collected by the ACU in real time.
Value range: 0 to 20000, units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it i… |
Integer32 Constraints: range: 0-200000 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.7 |
||||||||||||||||||
|
ACU B-phase current. It is an analog parameter collected by the ACU in real time.
Value range: 0 to 20000, units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it in… |
Integer32 Constraints: range: 0-200000 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.8 |
||||||||||||||||||
|
ACU C-phase current. It is an analog parameter collected by the ACU in real time.
Value range: 0 to 20000, units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it i… |
Integer32 Constraints: range: 0-200000 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.9 |
||||||||||||||||||
|
Quantity of the AC air circuit breakers.
As the ACU lower-level subset, the node indicates the quantity of the output air circuit breakers contained by each ACU lower-level subset. Value range: 0 to 100. |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.10 |
||||||||||||||||||
|
State of the site AC distribution uint. It is an enumeration type:
If the enumeration value is 1, it indicates that the site AC distribution uint is in the normal state; If the enumeration value is 2, it indicates tha… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.99 |
||||||||||||||||||
|
RowStatus of ACU.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.100 |
hwAcInputBreakerTable
table.1.3.6.1.4.1.2011.6.164.1.5.2.2
·
1 row entry
·
5 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwAcInputBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcInputBreakerTable'
Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBreakersQuantity in hwAcInputTable, clone Ac input breaker table.
Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBrea…
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Device table index of the AC air circuit breaker.
Value range: 1 to 100. An input air circuit breaker device can be uniquely identified through the ACU table index and device index of the AC air circuit breaker. |
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.1 |
||||||||||||
|
AC input air circuit breaker ID.
Value range: 005,001 to 005,100. The first digits indicate the device type and the last three digits indicate the device SN. |
Unsigned32 Constraints: range: 5001-5100 |
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.2 |
||||||||||||
|
AC input air circuit breaker name, of the character string type, can configured by users. Otherwise, the configured character can not be any other languages except English.
|
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.3 |
||||||||||||
|
Operation state of the site AC input breaker. It is an enumeration type:
If the enumeration value is 1, it indicates that the site AC input breaker is in the normal state; If the enumeration value is 2, it indicates t… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.99 |
||||||||||||
|
RowStatus of AC input breaker.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.100 |
hwDcOutputTable
table.1.3.6.1.4.1.2011.6.164.1.6.2.1
·
1 row entry
·
10 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwDcOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwDcOutputTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Device table index of the DC units, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of DC units (hwDcsQuantity).
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.1 |
||||||||||||||
|
DC unit device ID, which value range: 006,001 to 006,100. The first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 6001-6100 |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.2 |
||||||||||||||
|
DC unit device name, of the character string type, can be configued by users. Otherwise, the configured character can not be any other languages except English.
|
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.3 |
||||||||||||||
|
DC output voltage. It is an analog parameter collected by the DC power in real time.
Value range: 0 to 100, units: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it … |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.4 |
||||||||||||||
|
DC output current. It is an analog parameter collected by the DC power in real time.
Value range: -30000 to 30000, units: A, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF… |
Integer32 Constraints: range: -300000-300000 |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.5 |
||||||||||||||
|
DC output power. It is an analog parameter collected by the DC power in real time.
Value range: 0 to 3000000, units: W, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the… |
Unsigned32 Constraints: range: 0-3000000 |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.6 |
||||||||||||||
|
Quantity of the DC load output branches,
which value range: 0 to 100. As the DC unit lower-level subset, the node indicates the quantity of the DC load output branches contained by each DC unit lower-level subset. |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.7 |
||||||||||||||
|
The load usage of rated rectifier capacity.
Value range: 0 to 100, units: %, and the value is an integer (1). |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.8 |
||||||||||||||
|
State of the site DC distribution uint. It is an enumeration type:
If the enumeration value is 1, it indicates that the site DC distribution uint is in the normal state; If the enumeration value is 2, it indicates tha… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.99 |
||||||||||||||
|
RowStatus of Dc output equipments.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.100 |
hwLoadBranchTable
table.1.3.6.1.4.1.2011.6.164.1.6.2.2
·
1 row entry
·
11 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwLoadBranchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwLoadBranchTable'
Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity in hwDcOutputTable, clone loads output table.
Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity …
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Device table index of the DC load output branch,
which value range: 1 to 100. A DC load output branch can be uniquely identified through the DC unit table index and device index of the DC load output branch. |
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.1 |
||||||||||||
|
Device ID of the DC load output branch. Value range: 007,001 to 007,100. The first digits indicate the device type and the last three digits indicate the SN of the device.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.2 |
||||||||||||
|
Device name of the DC load output branch, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English.
|
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.3 |
||||||||||||
|
DC load output branch current. It is an analog parameter collected by the load branch in real time.
Value range: 0 to 10000, units: A, and the value is accurate to one decimal space (.1). If the value is 2147483647… |
Integer32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.4 |
||||||||||||
|
DC load branch power. It is an analog parameter collected by the DC power in real time.
Value range: 0 to 600000, units: W, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that… |
Unsigned32 Constraints: range: 0-600000 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.5 |
||||||||||||
|
DC load branch power consumption,
Value range: 0 to 4294967295, units: KWh, and the value is accurate to one decimal space (.1). |
Unsigned32 Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.6 |
||||||||||||
|
DC load branch power consumption,Value range: 0 to 4294967295, resolution:1 KWh.
|
Unsigned32 Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.8 |
||||||||||||
|
Low 32 bits of DC load branch power consumption,Value range: 0 to 4294967295, resolution:10Wh
|
Unsigned32 Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.9 |
||||||||||||
|
High 32 bits of DC load branch power consumption,Value range: 0 to 4294967295, resolution:10Wh
|
Unsigned32 Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.10 |
||||||||||||
|
State of the site load output branch. It is an enumeration type:
If the enumeration value is 1, it indicates that the site load output branch is in the normal state; If the enumeration value is 2, it indicates that th… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.99 |
||||||||||||
|
RowStatus of loads output branch.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.100 |
hwLvdBranchTable
table.1.3.6.1.4.1.2011.6.164.1.7.2.1
·
1 row entry
·
12 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwLvdBranchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwLvdBranchTable'
Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLvdBranchIndex, which qualificated by hwLvdsQuantity, clone power-off unit table.
Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLv…
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Device table index of a power-off unit.
Value range: 1 to 100. Lines of the device list are restricted by the total quantity of the power-off units (hwLvdsTotalQuantity). |
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.1 |
||||||||||||||||||||||||
|
Device ID of a power-off unit. Value range: 8001 to 8100. The first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 8001-8100 |
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.2 |
||||||||||||||||||||||||
|
Device name of a power-off unit, of the character string type, is used to specify the low-voltage power-off unit. Users can configure it. Otherwise, the configured character can not be any other languages except English.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.3 |
||||||||||||||||||||||||
|
Control power-off unit enabling. It is an enumeration value, and users actively set it.
If the enumeration value is 1, it means to enable the power-off unit; If the enumeration value is 2, it means to disable the powe… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.4 |
||||||||||||||||||||||||
|
Low-voltage power-off voltage of a power-off unit can be configured by users.
Its value range: 35 to 56, units: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it ind… |
Integer32r/w Constraints: range: 350-560 |
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.5 |
||||||||||||||||||||||||
|
Control of the power-off unit. It is an enumeration value, users control it manually.
If the NMS notifies the SNMP agent that the node is set to 1, it means to power off the power-off unit; If the NMS notifies the SNM… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.6 |
||||||||||||||||||||||||
|
Select the control mode of the power-off unit. It is an enumeration value, users can configure it manually.
If the NMS notifies the SNMP agent that the node is set to 1, it means to select the voltage power off mode; … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.7 |
||||||||||||||||||||||||
|
Low-voltage power-off recover of a power-off unit can be configured by users.
Its value range: 37.0 to 58.0, unit: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it … |
Integer32r/w Constraints: range: 370-580 |
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.8 |
||||||||||||||||||||||||
|
Low-voltage power-off disconnected time, It can be configured by users,
value range defines between 5 to 1000, unit: minutes(min) ?? and its value is an integer (1). Here, if battery manual test is standard mode, If … |
Integer32r/w Constraints: range: 5-1000 |
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.9 |
||||||||||||||||||||||||
|
Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
Value range: 0 to 100, unit: %, and the value is accurate to one decimal space (.1). If the value i… |
Integer32r/w Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.10 |
||||||||||||||||||||||||
|
State of the site LVD uint. It is an enumeration type:
If the enumeration value is 1, the site LVD uint is in the normal state; If the enumeration value is 2, the power-off uint disconnect for low voltage; If the enu… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.99 |
||||||||||||||||||||||||
|
RowStatus of lvd table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.100 |
hwEnvTempSensorTable
table.1.3.6.1.4.1.2011.6.164.1.8.2.1
·
1 row entry
·
12 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwEnvTempSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwEnvTempSensorTable'
Site environment temperature table. Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment temperature lower limit, and environment temperature alarm enable. This table's index is hwEnvTempSensorIndex, which qualificated by hwEnvTempSensorsQuantity, clone site environment temperature table.
Site environment temperature table.
Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment …
Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment …
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Table index of the environment temperature sensors.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.1 |
||||||||||||
|
Environment temperature sensor ID.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.2 |
||||||||||||
|
Environment temperature sensor name, of the character string type, is used to specify an environment temperature sensor.
Users can configure it. Otherwise, the configured character can not be any other languages excep… |
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.3 |
||||||||||||
|
Environment temperature. It is an environment parameter collected in real time.
Value range: -50 to +100, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647, it indicates that the… |
Integer32 Constraints: range: -50-100 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.4 |
||||||||||||
|
Upper threshold of the environment temperature alarm, can be configured by users.
units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inva… |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.5 |
||||||||||||
|
Lower threshold of the environment temperature alarm, can be configured by users.
units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inv… |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.6 |
||||||||||||
|
Upper threshold of the environment temperature measurement, can be configured by users.
Value range: 0 to 100, unit: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it in… |
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.7 |
||||||||||||
|
Lower threshold of the environment temperature measurement, can be configured by users.
Value range: -50 to 0, unit: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it in… |
Integer32r/w Constraints: range: -50-0 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.8 |
||||||||||||
|
Environment temperature alarm. It is an enumeration type:
If the enumeration value is 1, enable the alarm of the environment temperature; If the enumeration value is 2, disable the alarm of the environment temperature. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.9 |
||||||||||||
|
Threshold of the environment ultra high temperature measurement, can be configured by users.
unit: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value … |
SNMPv2-SMIUnsigned32r/w Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.10 |
||||||||||||
|
State of the site environment temperature sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site environment temperature sensor is in the normal state; If the enumeration value is… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.99 |
||||||||||||
|
RowStatus of Environment temperature table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.100 |
hwEnvHumiSensorTable
table.1.3.6.1.4.1.2011.6.164.1.8.2.2
·
1 row entry
·
11 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwEnvHumiSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwEnvHumiSensorTable'
Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit, and environment humidity alarm enable. This table's index is hwEnvHumiSensorIndex, which qualificated by hwEnvHumiSensorIndex, clone site environment humidity table.
Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit…
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Table index of the environment humility sensors.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.1 |
||||||||||||
|
Environment humility sensor ID
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.2 |
||||||||||||
|
Environment humility sensor name, of the character string type, is used to specify an environment humility sensor.
Users can configure it.Otherwise, the configured character can not be any other languages except Englis… |
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.3 |
||||||||||||
|
Environment humility. It is an environment parameter collected in real time.
Value range: 0 to 100, units: %RH, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the humidity… |
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.4 |
||||||||||||
|
Upper threshold of the environment humility alarm, can be configured by users.
Value range: 0 to 100, units: %RH, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.5 |
||||||||||||
|
Lower threshold of the environment humility alarm, can be configured by users.
Value range: 0 to 100, units: %RH, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.6 |
||||||||||||
|
Upper threshold of the environment humility measurement, can be configured by users.
Value range: 0 to 100, units: %RH, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the… |
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.7 |
||||||||||||
|
Lower threshold of the environment humility measurement, can be configured by users.
Value range: 0 to 100, units: %RH, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the v… |
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.8 |
||||||||||||
|
Environment humility alarm. It is an enumeration type:
If the enumeration value is 1, enable the alarm of the environment humility; If the enumeration value is 2, disable the alarm of the environment humility. The env… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.9 |
||||||||||||
|
State of the site environment humidity sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site environment humidity sensor is in the normal state; If the enumeration value is 2, it… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.99 |
||||||||||||
|
RowStatus of Environment humidity table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.100 |
hwSpareDigitalTable
table.1.3.6.1.4.1.2011.6.164.1.8.2.3
·
1 row entry
·
7 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSpareDigitalTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSpareDigitalTable'
Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table.
Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareD…
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Spare digital table index, which
value range: 1 to 256. Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity). |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.1 |
||||||||||||
|
Spare digital device ID. Value range: 011'001 to 011'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 11001-11255 |
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.2 |
||||||||||||
|
Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any other languages except English.
|
OctetStringr/w Constraints: range: 0-8 |
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.3 |
||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a low-tension alarm; If the value of the node is 2, it indicates a high-tension alarm. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.4 |
||||||||||||
|
Spare digital alarm enabling. It is an enumeration type:
If the enumeration value is 1, it means to enable the alarm; If the enumeration value is 2, it means to disable the alarm. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.5 |
||||||||||||
|
State of the site Spare digital. It is an enumeration type:
If the enumeration value is 1, it indicates that the Spare digital operation state is normal; If the enumeration value is 2, it indicates that a alarm occurs… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.99 |
||||||||||||
|
RowStatus of of the site Spare digital.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.100 |
.1.3.6.1.4.1.2011.6.164.1.8.2.4
·
1 row entry
·
7 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSpareDigitalOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSpareDigitalOutputTable'
Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table.
Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareD…
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Spare digital table index, which
value range: 1 to 256. Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity). |
Integer32 Constraints: range: 1-256 |
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.1 |
||||||||||||
|
Spare digital device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 12001-12255 |
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.2 |
||||||||||||
|
Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any other languages except English.
|
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.3 |
||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a low-tension alarm; If the value of the node is 2, it indicates a high-tension alarm. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.4 |
||||||||||||
|
Spare digital alarm enabling. It is an enumeration type:
If the enumeration value is 1, it means to enable the alarm; If the enumeration value is 2, it means to disable the alarm. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.5 |
||||||||||||
|
State of the site Spare digital. It is an enumeration type:
If the enumeration value is 1, it indicates that the Spare digital operation state is normal; If the enumeration value is 2, it indicates that a alarm occurs… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.99 |
||||||||||||
|
RowStatus of Spare digital device table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.100 |
hwTemp1Table
table.1.3.6.1.4.1.2011.6.164.1.8.2.5
·
1 row entry
·
7 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwTemp1Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwTemp1Table'
Temp1 Table.
Temp1 Table.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Table index of the temp1 sensors. Value range: 1 to 256. Lines of the device list are restricted by the quantity of temp1 sensors (hwEnvHumiSensorsTotalQuantity).
|
Integer32 Constraints: range: 3394-3394 |
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.1 |
||||||||||||||
|
Temp1 sensor ID, can be configured by users. Value range: 026'000 to 026'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 26000-26255 |
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.2 |
||||||||||||||
|
Temp1 sensor name, of the character string type, is used to specify an temp1 sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.3 |
||||||||||||||
|
Temp1. It is an environment parameter collected in real time.
Value range: -40 to +80, units: centigrade (degC), and the value is an integer (1). If the value is -1024, it indicates that the temperature sensor is n… |
Integer32 Constraints: range: -40-80 |
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.4 |
||||||||||||||
|
Upper threshold of the temp1 alarm, can be configured by users.
Value range: 25 to 80, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value … |
Integer32r/w Constraints: range: 25-80 |
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.5 |
||||||||||||||
|
Lower threshold of the temp1 alarm, can be configured by users. Value range: -20 to 20, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is …
|
Integer32r/w Constraints: range: -20-20 |
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.6 |
||||||||||||||
|
State of the site temp1 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state; If the enumeration value is 2, it indicates that the temp1 sens… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.99 |
hwTemp2Table
table.1.3.6.1.4.1.2011.6.164.1.8.2.6
·
1 row entry
·
7 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwTemp2Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwTemp2Table'
Temp2 Table.
Temp2 Table.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Table index of the temp2 sensors.
Value range: 1 to 256. Lines of the device list are restricted by the quantity of temp2 sensors (hwEnvHumiSensorsTotalQuantity). |
Integer32 Constraints: range: 3394-3394 |
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.1 |
||||||||||||||
|
Temp2 sensor ID, can be configured by users. Value range: 027'000 to 027'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 27000-27255 |
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.2 |
||||||||||||||
|
Temp2 sensor name, of the character string type, is used to specify an temp2 sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.3 |
||||||||||||||
|
Temp2. It is an environment parameter collected in real time.
Value range: -40 to +80, units: centigrade (degC), and the value is an integer (1). If the value is -1024, it indicates that the temperature sensor is n… |
Integer32 Constraints: range: -40-80 |
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.4 |
||||||||||||||
|
Upper threshold of the temp2 alarm, can be configured by users.
Value range: 25 to 80, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value … |
Integer32r/w Constraints: range: 25-80 |
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.5 |
||||||||||||||
|
Lower threshold of the temp2 alarm, can be configured by users.
Value range: -20 to 20, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Integer32r/w Constraints: range: -20-20 |
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.6 |
||||||||||||||
|
State of the site temp2 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp2 sensor is in the normal state; If the enumeration value is 2, it indicates that the temp2 sens… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.99 |
hwSmokeSensorTable
table.1.3.6.1.4.1.2011.6.164.1.8.2.13
·
1 row entry
·
4 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSmokeSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSmokeSensorTable'
/
/
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
The tem_hum equip Index.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.13.1.1 |
||||
|
/
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.13.1.2 |
||||
|
/
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.8.2.13.1.3 |
||||
|
The smoke sensor status
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.13.1.4 |
hwWaterSensorTable
table.1.3.6.1.4.1.2011.6.164.1.8.2.14
·
1 row entry
·
4 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwWaterSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwWaterSensorTable'
/
/
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
The tem_hum equip Index.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.14.1.1 |
||||
|
/
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.14.1.2 |
||||
|
/
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.8.2.14.1.3 |
||||
|
The smoke sensor status
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.14.1.4 |
hwDoorSensorTable
table.1.3.6.1.4.1.2011.6.164.1.8.2.15
·
1 row entry
·
4 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwDoorSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwDoorSensorTable'
/
/
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
The tem_hum equip Index.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.15.1.1 |
||||
|
/
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.8.2.15.1.2 |
||||
|
/
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.8.2.15.1.3 |
||||
|
The smoke sensor status
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.8.2.15.1.4 |
hwInverterTable
table.1.3.6.1.4.1.2011.6.164.1.9.2.1
·
1 row entry
·
26 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwInverterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwInverterTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Inverter table index,which value range:1 to 256.Lines of the device list are restricted by the quantity of Inverter.
|
Unsigned32 Constraints: range: 1-256 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.1 |
||||||||||||
|
Inverter device ID. Value range: 018'001 to 018'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 18001-18255 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.2 |
||||||||||||
|
Inverter name, of the character string type, is used to specify Inverters. Users can configure it.Otherwise, the configured character can not be any other languages except English.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.3 |
||||||||||||
|
Inverter AC Output voltage,
Value range: 0.0 to 10000.0. Unit: V. and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.4 |
||||||||||||
|
Inverter AC Output current,
Value range: 0.0 to 10000.0. Unit: A. and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.5 |
||||||||||||
|
Inverter AC Output frequency,
Value range: 0 to 10000. Unit: Hz. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.6 |
||||||||||||
|
Inverter AC Output power,
Value range: 0 to 10000000. Unit: W. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.7 |
||||||||||||
|
Inverter AC Output power,
Value range: 0.0 to 100000.0. Unit: VA. and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.8 |
||||||||||||
|
Inverter AC Input voltage,
Value range: 0.0 to 10000.0. Unit: V. and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.9 |
||||||||||||
|
Inverter AC Input current,
Value range: 0.0 to 10000.0. Unit: A. and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.10 |
||||||||||||
|
Inverter AC Input frequency,
Value range: 0 to 10000. Unit: Hz. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.11 |
||||||||||||
|
Inverter AC Input power,
Value range: 0 to 10000000. Unit: W. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.12 |
||||||||||||
|
Inverter AC Input power,
Value range: 0.0 to 10000.0. Unit: VA. and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.13 |
||||||||||||
|
Inverter DC Input voltage,
Value range: 0.0 to 10000.0. Unit: V. and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.14 |
||||||||||||
|
Inverter DC Input current,
Value range: 0 to 10000. Unit: A. and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.15 |
||||||||||||
|
Inverter DC Input power,
Value range: 0 to 10000000. Unit: W. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.16 |
||||||||||||
|
Inverter software version number.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.17 |
||||||||||||
|
Inverter Number of the phase module, Value range: 0 to 10000. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
|
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.18 |
||||||||||||
|
Inverter Number of AC group,
Value range: 0 to 10000. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.19 |
||||||||||||
|
Inverter Number of DC group,
Value range: 0 to 10000. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.20 |
||||||||||||
|
Inverter Number of Major alarm,
Value range: 0 to 10000. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.21 |
||||||||||||
|
Inverter Number of Minor alarm,
Value range: 0 to 10000. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.22 |
||||||||||||
|
Inverter T2S serial number,
Value range: 0 to 4294967295. If the value is 4294967295(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.23 |
||||||||||||
|
Inverter module Temperature,
Value range: -300 to 10000. Unit: degC. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -300-10000 |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.24 |
||||||||||||
|
State of the Inverter. It is an enumeration type:
If the enumeration value is 1, it indicates that the Inverter is in the normal state; If the enumeration value is 2, it indicates that the Inverter is in the alarm stat… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.99 |
||||||||||||
|
RowStatus of Inverter table.
|
RowStatus Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.100 |
hwFanTable
table.1.3.6.1.4.1.2011.6.164.1.10.2.1
·
1 row entry
·
14 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwFanTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwFanTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Fan table index,which
value range: 1 to 256. Lines of the device list are restricted by the quantity of Fan. |
Unsigned32 Constraints: range: 1-256 |
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.1 |
||||||||||||
|
Fan device ID. Value range: 020'001 to 020'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 20001-20255 |
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.2 |
||||||||||||
|
Fan name, of the character string type, is used to specify Fans. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.3 |
||||||||||||
|
State of the Fan ctrl mode. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in autoControl state; If the enumeration value is 2, it indicates that the fan is in manualControl stat… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.4 |
||||||||||||
|
State of the Fan1 status. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in normal state; If the enumeration value is 2, it indicates that the fan is in fault state; If the enume… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.5 |
||||||||||||
|
State of the Fan2 status. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in normal state; If the enumeration value is 2, it indicates that the fan is in fault state; If the enume… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.6 |
||||||||||||
|
State of the Fan3 status. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in normal state; If the enumeration value is 2, it indicates that the fan is in fault state; If the enume… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.7 |
||||||||||||
|
State of the Fan4 status. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in normal state; If the enumeration value is 2, it indicates that the fan is in fault state; If the enume… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.8 |
||||||||||||
|
Fan1 speed,
Value range: 0 to 10000. Unit: rpm. the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.9 |
||||||||||||
|
Fan2 speed,
Value range: 0 to 10000. Unit: rpm. the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.10 |
||||||||||||
|
Fan3 speed,
Value range: 0 to 10000. Unit: rpm. the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.11 |
||||||||||||
|
Fan4 speed,
Value range: 0 to 10000. Unit: rpm. the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.12 |
||||||||||||
|
State of the fan. It is an enumeration type:
If the enumeration value is 1, it indicates that the Inverter is in the normal state; If the enumeration value is 2, it indicates that the Inverter is in the fault state; … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.99 |
||||||||||||
|
RowStatus fo fan table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.100 |
hwDcAirConditionTable
table.1.3.6.1.4.1.2011.6.164.1.10.2.2
·
1 row entry
·
20 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwDcAirConditionTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwDcAirConditionTable'
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Dc aircondition table index
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.1 |
||||||||||||
|
Dc aircondition device ID.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.2 |
||||||||||||
|
Dc aircondition name, of the character string type, is used to specify Fans. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.3 |
||||||||||||
|
State of the Dc aircondition ctrl mode. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in autoControl state; If the enumeration value is 2, it indicates that the Dc a… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.4 |
||||||||||||
|
State of the Dc aircondition control on or off. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in on state; If the enumeration value is 2, it indicates that the Dc ai… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.5 |
||||||||||||
|
State of the Dc aircondition run status. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in standby state; If the enumeration value is 2, it indicates that the Dc airc… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.6 |
||||||||||||
|
State of the Dc air compressor run status. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in standby state; If the enumeration value is 2, it indicates that the Dc ai… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.7 |
||||||||||||
|
Dc aircondition innr speed,
Value range: 0 to 60000. Unit: rpm, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: 0-60000 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.8 |
||||||||||||
|
Dc aircondition outer speed,
Value range: 0.0 to 60000.0. Unit: rpm, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: 0-60000 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.9 |
||||||||||||
|
Dc aircondition compressor run time,
Value range: 0 to 175200. Unit: h, the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: 0-175200 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.10 |
||||||||||||
|
Dc aircondition run time,
Value range: 0 to 175200. Unit: H, the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: 0-175200 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.11 |
||||||||||||
|
Dc aircondition enter channel temperature,
Value range:-500.0 to 1000.0. Unit: degC. and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -500-1000 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.13 |
||||||||||||
|
Dc aircondition power on temperature point,
Value range:-200 to 800. Unit: degC. the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32r/w Constraints: range: -200-800 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.14 |
||||||||||||
|
Dc aircondition power off temperature point,
Value range:-200 to 800 Unit: degC. the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32r/w Constraints: range: -200-800 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.15 |
||||||||||||
|
State of the Dc air energy saving status. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in disable state; If the enumeration value is 2, it indicates that the Dc air… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.17 |
||||||||||||
|
Dc aircondition power on ac fail temperature point,
Value range:-200 to 800. Unit: degC. and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32r/w Constraints: range: -200-800 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.18 |
||||||||||||
|
Dc aircondition compressor start temperature point,
Value range:-200 to 800. Unit: degC. and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32r/w Constraints: range: -200-800 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.19 |
||||||||||||
|
DC Air Device address
And the value is an integer (1). |
Unsigned32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.21 |
||||||||||||
|
State of the dc aircondition. It is an enumeration type:
If the enumeration value is 1, it indicates that the Inverter is in the standby state; If the enumeration value is 2, it indicates that the Inverter is in the ru… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.99 |
||||||||||||
|
RowStatus fo dc aircondition table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.100 |
hwSiteAcAmmeterTable
table.1.3.6.1.4.1.2011.6.164.1.11.2.1
·
1 row entry
·
37 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteAcAmmeterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteAcAmmeterTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Ac Ammeter table index,which value range:4096 to 20479. Lines of the device list are restricted by the quantity of AcAmmeter
|
Unsigned32 Constraints: range: 4096-20479 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.1 |
||||||||||||
|
Ac Ammeter device ID. Value range: 022'001 to 022'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 22001-22255 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.2 |
||||||||||||
|
Ac Ammeter name, of the character string type, is used to specify Fans. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.3 |
||||||||||||
|
Ac Ammeter frequency,
Value range: 0.00 to 1000.00. Unit: Hz. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.4 |
||||||||||||
|
Ac Ammeter phase a voltage,
Value range: 0.00 to 2000.00. Unit: V. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-200000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.5 |
||||||||||||
|
Ac Ammeter phase b voltage,
Value range: 0.00 to 2000.0. Unit: V. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-200000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.6 |
||||||||||||
|
Ac Ammeter phase c voltage,
Value range: 0.00 to 2000.0. Unit: V. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-200000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.7 |
||||||||||||
|
Ac Ammeter set channel number,
Value range: 1 to 4. Unit: NA. and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32r/w Constraints: range: 1-4 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.8 |
||||||||||||
|
Ac Ammeter clear communication failure . It is an enumeration type:
If the enumeration value is 1, it indicates that the ac ammeter clear communication failure alarm; |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.9 |
||||||||||||
|
Ac Ammeter type, Value range: 0 to 65535. And the value is an integer(1).
|
Unsigned32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.10 |
||||||||||||
|
Ac Ammeter version, of the character string type, is used to specify Ac Ammeter. Users can not configure it.
|
OctetString Constraints: range: 0-56 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.11 |
||||||||||||
|
Ac Ammeter phase a current of channel 1,
Value range: 0.00 to 1000.0. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.12 |
||||||||||||
|
Ac Ammeter phase b current of channel 1,
Value range: 0.00 to 1000.0. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.13 |
||||||||||||
|
Ac Ammeter phase c current of channel 1,
Value range: 0.00 to 1000.0. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.14 |
||||||||||||
|
Ac Ammeter phase c current of channel 1,
Value range: -1000000.00 to 1000000.00. Unit: kW. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is i… |
Integer32 Constraints: range: -100000000-100000000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.15 |
||||||||||||
|
Ac Ammeter total power factor of channel 1,
Value range: -10.00 to 10.00. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.16 |
||||||||||||
|
Ac Ammeter total active engry acc of channel 1,
Value range: 0.00 to 1000000000.00. Unit: kWh. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value … |
Unsigned32 Constraints: range: 0-10000000000000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.17 |
||||||||||||
|
Ac Ammeter phase a current of channel 2,
Value range: 0.00 to 1000.00. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.18 |
||||||||||||
|
Ac Ammeter phase b current of channel 2,
Value range: 0.00 to 1000.00. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.19 |
||||||||||||
|
Ac Ammeter phase c current of channel 2,
Value range: 0.00 to 1000.00. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.20 |
||||||||||||
|
Ac Ammeter phase c current of channel 2,
Value range: -1000000.00 to 1000000.00. Unit: kW. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is i… |
Integer32 Constraints: range: -100000000-100000000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.21 |
||||||||||||
|
Ac Ammeter total power factor of channel 2,
Value range: -10.00 to 10.00. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.22 |
||||||||||||
|
Ac Ammeter total active engry acc of channel 2,
Value range: 0.00 to 1000000000.00. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is… |
Unsigned32 Constraints: range: 0-100000000000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.23 |
||||||||||||
|
Ac Ammeter phase a current of channel 3,
Value range: 0.00 to 1000.00. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.24 |
||||||||||||
|
Ac Ammeter phase b current of channel 3,
Value range: 0.00 to 1000.00. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.25 |
||||||||||||
|
Ac Ammeter phase c current of channel 3,
Value range: 0.00 to 1000.00. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.26 |
||||||||||||
|
Ac Ammeter phase c current of channel 3,
Value range: -1000000.00 to 1000000.00. Unit: kW. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is i… |
Integer32 Constraints: range: -100000000-100000000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.27 |
||||||||||||
|
Ac Ammeter total power factor of channel 3,
Value range: -10.00 to 10.00. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.28 |
||||||||||||
|
Ac Ammeter total active engry acc of channel 3,
Value range: 0.00 to 1000000000.00. Unit: kWh. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value … |
Unsigned32 Constraints: range: 0-100000000000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.29 |
||||||||||||
|
Ac Ammeter phase a current of channel 4,
Value range: 0 to 1000. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.30 |
||||||||||||
|
Ac Ammeter phase b current of channel 4,
Value range: 0 to 1000. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.31 |
||||||||||||
|
Ac Ammeter phase c current of channel 4,
Value range: 0 to 1000. Unit: A. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.32 |
||||||||||||
|
Ac Ammeter phase c current of channel 4,
Value range: -1000000 to 1000000. Unit: kW. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -100000000-100000000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.33 |
||||||||||||
|
Ac Ammeter total power factor of channel 4,
Value range: -10.00 to 10.00. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.34 |
||||||||||||
|
Ac Ammeter total active engry acc of channel 4,
Value range: 0 to 1000000000. Unit: kWh. and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inv… |
Unsigned32 Constraints: range: 0-100000000000 |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.35 |
||||||||||||
|
State of the Ac Ammeter. It is an enumeration type:
If the enumeration value is 1, it indicates that the Ac Ammeter is in the normal state; If the enumeration value is 2, it indicates that the Ac Ammeter is in the faul… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.99 |
||||||||||||
|
RowStatus fo Ac Ammeter table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.100 |
hwDGTable
table.1.3.6.1.4.1.2011.6.164.1.12.2.1
·
1 row entry
·
23 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwDGTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwDGTable'
/
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
DG table index,which value range:1 to 256. Lines of the device list are restricted by the quantity of DG.
|
Integer32 Constraints: range: 0-256 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.1 |
||||||||||||
|
DG device ID. Value range: 023'001 to 023'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 23001-23255 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.2 |
||||||||||||
|
Device name of the DG module, character string type, is used to specify the DG module. Otherwise, the configured character can not be any other languages except English.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.3 |
||||||||||||
|
Specific type of the DG module. It is an enumeration type:
If the enumeration value is 1, it indicates a intelligent DG module; If the enumeration value is 2, it indicates a non_intelligent module; If the enumeration … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.4 |
||||||||||||
|
A-phase voltage.
Value range: 0 to 500, units: V, and the value is accurate to one decimal place (.1). |
Unsigned32 Constraints: range: 0-5000 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.5 |
||||||||||||
|
B-phase voltage.
Value range: 0 to 500, units: V, and the value is accurate to one decimal place (.1). |
Unsigned32 Constraints: range: 0-5000 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.6 |
||||||||||||
|
C-phase voltage.
Value range: 0 to 500, units: V, and the value is accurate to one decimal place (.1). |
Unsigned32 Constraints: range: 0-5000 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.7 |
||||||||||||
|
A-phase current.
Value range: 0 to 100, units: A, and the value is an integer (1). |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.8 |
||||||||||||
|
B-phase current.
Value range: 0 to 100, units: A, and the value is an integer (1). |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.9 |
||||||||||||
|
C-phase current.
Value range: 0 to 100, units: A, and the value is an integer (1). |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.10 |
||||||||||||
|
DG output power.
Value range: 0 to 100, units: kw, and the value is one decimal space (.1). |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.11 |
||||||||||||
|
The frequency of DG.
Value range: 5 to 120, units: Hz, and the value is one decimal space (.1). |
Unsigned32 Constraints: range: 50-1200 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.12 |
||||||||||||
|
The voltage of DG battery.
Value range: 0 to 24, units: V, and the value is one decimal space (.1). |
Unsigned32 Constraints: range: 0-240 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.13 |
||||||||||||
|
The total running time of DG,
Value range: 0 to 876000, units: h, and the value is one decimal space (.1). |
Unsigned32 Constraints: range: 0-8760000 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.14 |
||||||||||||
|
A phase power factor of DG,
Value range: -1 to 1, units: , and the value is two decimal space (.01). |
Integer32 Constraints: range: -100-100 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.15 |
||||||||||||
|
B phase power factor of DG,
Value range: -1 to 1, units: , and the value is two decimal space (.01). |
Integer32 Constraints: range: -100-100 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.16 |
||||||||||||
|
C phase power factor of DG,
Value range: -1 to 1, units: , and the value is two decimal space (.01). |
Integer32 Constraints: range: -100-100 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.17 |
||||||||||||
|
The load rate of DG,
Value range: 0 to 100, units: %, and the value is one decimal space (.1). |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.18 |
||||||||||||
|
Power-on or power-off of the DG module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the DG module:
If the NMS notifies the SNMP agent th… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.19 |
||||||||||||
|
DG fault reset.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.20 |
||||||||||||
|
DG maintenance confirm.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.21 |
||||||||||||
|
State of the DG. It is an enumeration type:
If the enumeration value is 1, it indicates that the DG is in the normal state; If the enumeration value is 2, it indicates that the DG is in the fault state; If the enumer… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.99 |
||||||||||||
|
RowStatus fo DG.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.100 |
hwSSUTable
table.1.3.6.1.4.1.2011.6.164.1.13.2.1
·
1 row entry
·
9 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSSUTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSSUTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
SSU table index,which value range:1 to 256. Lines of the device list are restricted by the quantity of SSU.
|
Integer32 Constraints: range: 0-256 |
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.1 |
||||||||||||
|
SSU device ID. Value range: 024'001 to 024'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 24001-24255 |
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.2 |
||||||||||||
|
Device name of the SSU module, character string type, is used to specify the SSU module.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.3 |
||||||||||||
|
The running status of the SSU module. It is an enumeration type:
If the enumeration value is 1, it indicates that the SSU module is power on ; If the enumeration value is 2, it indicates that the SSU module is power of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.4 |
||||||||||||
|
The input voltage of SSU,
Value range: 0 to 200, units: V, and the value is one decimal space (.1). |
Unsigned32 Constraints: range: 0-2000 |
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.5 |
||||||||||||
|
The output voltage of SSU,
Value range: 0 to 200, units: V, and the value is one decimal space (.1). |
Unsigned32 Constraints: range: 0-2000 |
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.6 |
||||||||||||
|
The output current of SSU,
Value range: 0 to 1000, units: A, and the value is one decimal space (.1). |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.7 |
||||||||||||
|
The address of SSU,
Value range: 0 to 100, units: , and the value is an integer (1). |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.8 |
||||||||||||
|
RowStatus fo SSU.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.100 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1
·
1 row entry
·
19 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteBatteryCabinetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteBatteryCabinetTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Battery Cabinet table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Battery Cabinet
|
Unsigned32 Constraints: range: 4096-20479 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.1 |
||||||||||||
|
Battery Cabinet device ID. Value range: 025'001 to 025'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 25000-25255 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.2 |
||||||||||||
|
Battery Cabinet name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.3 |
||||||||||||
|
Indoor vent temperature. It is an environment parameter collected in real time.
Value range: -40 to +100, units: centigrade, and the value is an integer (1). If the value is -99999, it indicates that the temperatur… |
Integer32 Constraints: range: -40-100 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.4 |
||||||||||||
|
Battery temperature. It is an environment parameter collected in real time.
Value range: -40 to +100, units: centigrade, and the value is an integer (1). If the value is -99999, it indicates that the temperature sen… |
Integer32 Constraints: range: -40-100 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.5 |
||||||||||||
|
Fan 1 speed,
Value range: 0.0 to 10000.0. Unit: rpm, the value is an integer (1). If the value is -1, it indicates that the fan is not configured. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.6 |
||||||||||||
|
Fan 2 speed,
Value range: 0.0 to 10000.0. Unit: rpm, the value is an integer (1). If the value is -1, it indicates that the fan is not configured. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.7 |
||||||||||||
|
Fan 3 speed,
Value range: 0.0 to 10000.0. Unit: rpm, the value is an integer (1). If the value is -1, it indicates that the fan is not configured. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.8 |
||||||||||||
|
Fan 4 speed,
Value range: 0.0 to 10000.0. Unit: rpm, the value is an integer (1). If the value is -1, it indicates that the fan is not configured. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.9 |
||||||||||||
|
State of the airconditioner. It is an enumeration type:
If the enumeration value is 1, it indicates that the airconditioner is in the standby state; If the enumeration value is 2, it indicates that the airconditioner i… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.10 |
||||||||||||
|
State of the compressor. It is an enumeration type:
If the enumeration value is 1, it indicates that the compressor is in the standby state; If the enumeration value is 2, it indicates that the compressor is in the run… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.11 |
||||||||||||
|
Internal Fan speed,
Value range: 0 to 10000. Unit: rpm, the value is an integer (1). If the value is -1, it indicates that the fan is not configured. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.12 |
||||||||||||
|
External Fan speed,
Value range: 0 to 10000. Unit: rpm, the value is an integer (1). If the value is -1, it indicates that the temperature sensor is not configured. |
Integer32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.13 |
||||||||||||
|
Total runtime of the air conditioner.
Value units: hour (h), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.14 |
||||||||||||
|
Total runtime of the compressor.
Value units: hour (h), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.15 |
||||||||||||
|
Battery cabinet aircondition power on temperature point,
Value range:-20 to 80 Unit: degC. and the value is an integer (1). |
Integer32r/w Constraints: range: -20-80 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.16 |
||||||||||||
|
Battery cabinet aircondition power off temperature point,
Value range:-20 to 80 Unit: degC. and the value is an integer(1). |
Integer32r/w Constraints: range: -20-80 |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.17 |
||||||||||||
|
State of the Battery Cabinet. It is an enumeration type:
If the enumeration value is 1, it indicates that the Inverter is in the normal state; If the enumeration value is 2, it indicates that the Inverter is in the fau… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.99 |
||||||||||||
|
RowStatus fo Battery Cabinet table.
|
RowStatusr/w Type Values:
Description: Description. |
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.100 |
hwEsduTable
table.1.3.6.1.4.1.2011.6.164.1.15.2
·
1 row entry
·
38 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwEsduTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwEsduTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
ESDU equip index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Battery Cabinet
|
Unsigned32 Constraints: range: 3428-3443 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.1 |
||||||||||||||
|
Esdu device ID. Value range: 028,001 to 028,255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 28001-28255 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.2 |
||||||||||||||
|
/
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.3 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.4 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.5 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.6 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.7 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.8 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.9 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.10 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.11 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.12 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.13 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.If the value of the node is 1, it indicates a high-tension alarm;If the value of the node is 2, it indicates a low-tension alarm;If the value of the node is 255, it …
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.14 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.15 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.16 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.17 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.18 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.19 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.20 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.21 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.22 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.23 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.24 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.25 |
||||||||||||||
|
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm; If the value of the node is 2, it indicates a low-tension alarm; If the value of the node is 255, … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.26 |
||||||||||||||
|
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal; If the value of the node is 2, it indicates that the diesel of… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.27 |
||||||||||||||
|
Temp1. It is an environment parameter collected in real time.
Value range: -40 to +80, Unit: degC and the value is an integer (1). If the value is -1024, it indicates that the temperature sensor is not configured. |
Integer32 Constraints: range: -40-80 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.28 |
||||||||||||||
|
State of the site temp1 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state; If the enumeration value is 2, it indicates that the temp1 sens… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.31 |
||||||||||||||
|
Temp1. It is an environment parameter collected in real time.
Value range: -40 to +80, units: centigrade (degC), and the value is an integer (1). If the value is -1024, it indicates that the temperature sensor is n… |
Integer32 Constraints: range: -40-80 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.32 |
||||||||||||||
|
Upper threshold of the temp1 alarm, can be configured by users.
Value range: 25 to 80, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value … |
Integer32r/w Constraints: range: 25-80 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.33 |
||||||||||||||
|
Lower threshold of the temp1 alarm, can be configured by users.
Value range: -20 to 20, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Integer32r/w Constraints: range: -20-20 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.34 |
||||||||||||||
|
State of the site temp1 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state; If the enumeration value is 2, it indicates that the temp1 sens… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.35 |
||||||||||||||
|
Temp2. It is an environment parameter collected in real time.
Value range: -40 to +80, units: centigrade (degC), and the value is an integer (1). If the value is -1024, it indicates that the temperature sensor is n… |
Integer32 Constraints: range: -40-80 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.36 |
||||||||||||||
|
Upper threshold of the temp2 alarm, can be configured by users.
Value range: 25 to 80, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value … |
Integer32r/w Constraints: range: 25-80 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.37 |
||||||||||||||
|
Lower threshold of the temp2 alarm, can be configured by users.
Value range: -20 to 20, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Integer32r/w Constraints: range: -20-20 |
.1.3.6.1.4.1.2011.6.164.1.15.2.1.38 |
||||||||||||||
|
State of the site temp2 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp2 sensor is in the normal state; If the enumeration value is 2, it indicates that the temp2 sens… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.39 |
||||||||||||||
|
Door Sensor Connected; It is an enumeration value, and can be configured.
If the enumeration value is 1, it indicates Door Sensor is disable; If the enumeration value is 2, it indicates Door Sensor is enalble; If the e… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.15.2.1.40 |
hwAcbGroupSampTable
table.1.3.6.1.4.1.2011.6.164.1.17.1
·
1 row entry
·
13 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwAcbGroupSampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbGroupSampTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
The battery group equip Index.
|
Unsigned32 Constraints: range: 0-256 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.1 |
||||||||||||||||
|
The battery group equip ID no.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.2 |
||||||||||||||||
|
The battery group equip name.
|
OctetString | .1.3.6.1.4.1.2011.6.164.1.17.1.1.3 |
||||||||||||||||
|
State of the Battery group unit running state. It is an enumeration type:
If the enumeration value is 1, it indicates the Battery is first on line, If the enumeration value is 2, it indicates that Battery power off, If … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.17.1.1.4 |
||||||||||||||||
|
The battery volt; Value range: 0 to 100,
units: V. and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.5 |
||||||||||||||||
|
The battery current; Value range: -4000 to 4000,
units: A. and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -40000-40000 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.6 |
||||||||||||||||
|
The battery total capacity; Value range: 0 to 10000,
units: Ah. and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.7 |
||||||||||||||||
|
The battery total remain capacity; Value range:0 to 100,
units: %. and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.8 |
||||||||||||||||
|
The battery temperature; Value range:-50 to 100,
units: degC. and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Integer32 Constraints: range: -500-1000 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.9 |
||||||||||||||||
|
The battery backup time; Value range: 0 to 256,
units: h. and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-2560 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.11 |
||||||||||||||||
|
The esmu communicate number,
Value range: 0 to 100. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.12 |
||||||||||||||||
|
The battery soh: 0 to 100,
units: %. and the value is accurate to one decimal place (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.13 |
||||||||||||||||
|
The battery total discharge depth,
units: %. and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 10-1000 |
.1.3.6.1.4.1.2011.6.164.1.17.1.1.22 |
hwAcbGroupSetTable
table.1.3.6.1.4.1.2011.6.164.1.17.2
·
1 row entry
·
10 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwAcbGroupSetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbGroupSetTable'
/
/
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Battery cell number.
Value range: 1 to 32, If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 1-32 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.5 |
|
The battery total capacity,
units: wh. and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-10000 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.6 |
|
Battery equalcharge voltage, can be configued by users.
Value range: 42 to 58, units: v, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inval… |
Unsigned32r/w Constraints: range: 420-580 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.11 |
|
Battery floatcharge voltage, can be configued by users.
Value range: 42 to 58, units: v, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invali… |
Unsigned32r/w Constraints: range: 420-580 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.12 |
|
Battery charge limited threhold , can be configued by users.
Value range: 0.05 to 2, units: C10, and the value is accurate to two decimal space (.01). If the setting value is beyond the current support range, it will fa… |
Unsigned32r/w Constraints: range: 5-200 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.13 |
|
Battery over charge current limited threhold , can be configued by users.
Value range: 0.15 to 1.2, units: C10, and the value is accurate to two decimal space (.01). If the value is 2147483647(0x7FFFFFFF), it indicates … |
Unsigned32r/w Constraints: range: 15-120 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.14 |
|
Upper threshold of the environment temperature alarm, can be configured by users.
Value range: 35 to 70, units: centigrade (??C), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates tha… |
Unsigned32r/w Constraints: range: 35-70 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.21 |
|
Lower threshold of the environment temperature alarm, can be configured by users.
Value range: -50 to 0, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates th… |
Integer32r/w Constraints: range: -50-0 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.22 |
|
The lithium battery discharge depth for Acid Battery running; ,units: %.
|
Unsigned32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.26 |
|
Battery default charge limited threhold , can be configued by users.
Value range: 0.05 to 2, units: C10, and the value is accurate to two decimal space (.01). If the setting value is beyond the current support rang… |
Unsigned32r/w Constraints: range: 5-200 |
.1.3.6.1.4.1.2011.6.164.1.17.2.1.27 |
hwAcbBaseTable
table.1.3.6.1.4.1.2011.6.164.1.18.1
·
1 row entry
·
5 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwAcbBaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbBaseTable'
/
/
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The battery equip Index.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.18.1.1.1 |
|
The battery equip ID no.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.18.1.1.2 |
|
The battery equip name.
|
OctetStringr/w | .1.3.6.1.4.1.2011.6.164.1.18.1.1.3 |
|
The battery communica address.
|
Unsigned32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.164.1.18.1.1.4 |
|
The Battery software version.
|
OctetString | .1.3.6.1.4.1.2011.6.164.1.18.1.1.5 |
hwAcbSampTable
table.1.3.6.1.4.1.2011.6.164.1.18.2
·
1 row entry
·
49 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwAcbSampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbSampTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
voltage of the battery. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it in… |
Unsigned32 Constraints: range: 0-600 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.1 |
||||||||||||||||
|
Current of the battery. It indicates the real-time statistics of the battery on the site.
Value range: -200 to 200, unit: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Integer32 Constraints: range: -2000-2000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.2 |
||||||||||||||||
|
Battery charging state, indicates the charging and discharging information about the battery group. It is an enumeration type.
If the enumeration value is 1, it indicates a battery in the Offline state. If the enumerat… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.18.2.1.3 |
||||||||||||||||
|
Soh of the battery. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 100, unit: %, and the value is accurate to two decimal place (1). If the value is 2147483647(0x7FFFFFFF), it indica… |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.4 |
||||||||||||||||
|
Capacity of the battery.
Value range: 0 to 10000, unit: Ah, and the value is accurate to two decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-100000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.5 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.6 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.7 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.8 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.9 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.10 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.11 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.12 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.13 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.14 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.15 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.16 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.17 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.18 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.19 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.20 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.21 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.22 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.23 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.24 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.25 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.26 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.27 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.28 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.29 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.30 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.31 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.32 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.33 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.34 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.35 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.36 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.37 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.38 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.39 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.40 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.41 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.42 |
||||||||||||||||
|
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100, units: centigrade(degC), and the value is accurate to one decimal place (.1). If the value is … |
Integer32 Constraints: range: -1000-1000 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.43 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.44 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.45 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.46 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.47 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.48 |
||||||||||||||||
|
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5, unit: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), i… |
Unsigned32 Constraints: range: 0-50 |
.1.3.6.1.4.1.2011.6.164.1.18.2.1.49 |
hwAcbSetTable
table.1.3.6.1.4.1.2011.6.164.1.18.3
·
1 row entry
·
2 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwAcbSetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbSetTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
Gyro Function Enable,
Restricted use in special areas. If the value of the device is within the range, but the setting fails, the function is not supported. It is an enumeration value: If the enumeration value is 1, i… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.18.3.1.5 |
||||||||
|
Gyro Level of Sensitivity.
Restricted use in special areas. If the value of the device is within the range, but the setting fails, the function is not supported. It is an enumeration value: If the enumeration value is 1… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.18.3.1.6 |
hwSiteIboxTable
table.1.3.6.1.4.1.2011.6.164.1.20.1
·
1 row entry
·
4 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteIboxTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteIboxTable'
/
/
Indexes
| Column | Syntax | OID |
|---|---|---|
|
ibox table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of ibox
|
Unsigned32 Constraints: range: 560-575 |
.1.3.6.1.4.1.2011.6.164.1.20.1.1.1 |
|
ibox device ID. Value range: 029'001 to 029'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 29001-29255 |
.1.3.6.1.4.1.2011.6.164.1.20.1.1.2 |
|
Ibox name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.20.1.1.3 |
|
Number of Batteries.
Value range: 0 to 96, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32r/w Constraints: range: 0-96 |
.1.3.6.1.4.1.2011.6.164.1.20.1.1.4 |
hwSiteIbatTable
table.1.3.6.1.4.1.2011.6.164.1.21.1
·
1 row entry
·
6 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteIbatTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteIbatTable'
/
/
Indexes
| Column | Syntax | OID |
|---|---|---|
|
ibox table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of ibox
|
Unsigned32 Constraints: range: 24576-26112 |
.1.3.6.1.4.1.2011.6.164.1.21.1.1.1 |
|
ibat device ID. Value range: 030'001 to 031'537, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 30001-31537 |
.1.3.6.1.4.1.2011.6.164.1.21.1.1.2 |
|
Ibat name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.21.1.1.3 |
|
Ibat temperature. It is a ibat parameter collected in real time.
Value range: -50 to +125, unit: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that ibox tem… |
Integer32 Constraints: range: -50-125 |
.1.3.6.1.4.1.2011.6.164.1.21.1.1.4 |
|
Ibat Voltage of the ibat. It is an inherent attribute.
Value range: 0 to 100, Units: V, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is in… |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.21.1.1.5 |
|
IbatResistance
Value range: 0 to 1000000, units: (mohm), and the value is accurate to two decimal place (.01). |
Unsigned32 Constraints: range: 0-100000000 |
.1.3.6.1.4.1.2011.6.164.1.21.1.1.6 |
hwSiteCommExBoardTable
table.1.3.6.1.4.1.2011.6.164.1.22.1
·
1 row entry
·
3 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteCommExBoardTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteCommExBoardTable'
/
/
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Communication Expansion Board table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Communication Expansion Board
|
Unsigned32 Constraints: range: 1297-1301 |
.1.3.6.1.4.1.2011.6.164.1.22.1.1.1 |
|
Communication Expansion Board device ID. Value range: 032,256 to 033,249, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 32266-33049 |
.1.3.6.1.4.1.2011.6.164.1.22.1.1.2 |
|
Communication Expansion Board name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.22.1.1.3 |
hwSiteDGCommExBoardTable
table.1.3.6.1.4.1.2011.6.164.1.23.1
·
1 row entry
·
3 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteDGCommExBoardTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteDGCommExBoardTable'
/
/
Indexes
| Column | Syntax | OID |
|---|---|---|
|
DG Communication Expansion Board table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of DG Communication Expansion Board
|
Unsigned32 Constraints: range: 2185-2185 |
.1.3.6.1.4.1.2011.6.164.1.23.1.1.1 |
|
DG Communication Expansion Board device ID. Value range: 034'001, in which the first digits indicate the device type and the last three digits indicate the device SN.
|
Unsigned32 Constraints: range: 34001-34001 |
.1.3.6.1.4.1.2011.6.164.1.23.1.1.2 |
|
DG Communication Expansion Board name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.23.1.1.3 |
hwElockEquipTable
table.1.3.6.1.4.1.2011.6.164.1.27.1
·
1 row entry
·
3 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwElockEquipTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwElockEquipTable'
/
/
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The elock equip Index.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.27.1.1.1 |
|
The elock equip ID no.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.27.1.1.2 |
|
The elock equip name.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.27.1.1.3 |
hwTemHumEquipTable
table.1.3.6.1.4.1.2011.6.164.1.28.1
·
1 row entry
·
10 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwTemHumEquipTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwTemHumEquipTable'
/
/
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The tem_hum equip Index.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.1 |
|
The tem_hum equip ID no.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.2 |
|
The tem_hum equip name.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.3 |
|
the environment temperature.
units: centigrade (degC), and the value is an integer (1). |
Integer32 Constraints: range: -20-80 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.4 |
|
environment temperature ,
units: %RH, and the value is an integer (1). |
Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.5 |
|
Upper threshold of the environment temperature alarm, can be configured by users.
Value range: 25 to 80, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicate… |
Integer32r/w Constraints: range: 25-80 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.6 |
|
Lower threshold of the environment temperature alarm, can be configured by users.
Value range: -20 to 20, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indica… |
Integer32r/w Constraints: range: -20-20 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.7 |
|
Upper threshold of the environment humility alarm, can be configured by users.
Value range: 0 to 100, units: %RH, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.8 |
|
Lower threshold of the environment humility alarm, can be configured by users.
Value range: 0 to 100, units: %RH, and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value… |
Integer32r/w Constraints: range: 0-100 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.9 |
|
Device address
And the value is an integer (1). |
Unsigned32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.164.1.28.1.1.10 |
hwHeaterDeviceTable
table.1.3.6.1.4.1.2011.6.164.1.29.1
·
1 row entry
·
5 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwHeaterDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwHeaterDeviceTable'
Indexes
| Column | Syntax | OID |
|---|---|---|
|
heater device table index.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.29.1.1.1 |
|
heater device equipid.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.29.1.1.2 |
|
heater device equipname.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.2011.6.164.1.29.1.1.3 |
|
heater start temperature;
Value range:-10 to 15.Unit: degC. and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. note: hwHeaterStartTemperature's set value … |
Integer32r/w Constraints: range: -10-15 |
.1.3.6.1.4.1.2011.6.164.1.29.1.1.4 |
|
heater stop temperature;
Value range: 5 to 20.Unit: degC. and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. note: hwHeaterStartTemperature's set value mus… |
Integer32r/w Constraints: range: 5-20 |
.1.3.6.1.4.1.2011.6.164.1.29.1.1.5 |
hwSiteDMUSampTable
table.1.3.6.1.4.1.2011.6.164.1.31.1
·
1 row entry
·
6 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteDMUSampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteDMUSampTable'
Indexes
| Column | Syntax | OID |
|---|---|---|
|
DMU table index,
which value range:1 to 256. Lines of the device list are restricted by the quantity of DMU. |
Unsigned32 Constraints: range: 0-256 |
.1.3.6.1.4.1.2011.6.164.1.31.1.1.1 |
|
DMU device ID.
Value range: 033'001 to 033'255, in which the first digits indicate the device type and the last three digits indicate the device SN. |
Unsigned32 Constraints: range: 33001-33255 |
.1.3.6.1.4.1.2011.6.164.1.31.1.1.2 |
|
Device name of the DMU module,
character string type, is used to specify the DMU module. Otherwise, the configured character can not be any other languages except English. |
OctetString Constraints: range: 0-56 |
.1.3.6.1.4.1.2011.6.164.1.31.1.1.3 |
|
DC output voltage: 0 to 100,
units: V, and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-1000 |
.1.3.6.1.4.1.2011.6.164.1.31.1.1.4 |
|
Load current: 0 to 30000,
units: A, and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-300000 |
.1.3.6.1.4.1.2011.6.164.1.31.1.1.5 |
|
Total load consumption: 0 to 4294967295,
units: kWh, and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid. |
Unsigned32 Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.2011.6.164.1.31.1.1.6 |
hwSiteDMUSetTable
table.1.3.6.1.4.1.2011.6.164.1.31.2
·
1 row entry
·
12 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteDMUSetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteDMUSetTable'
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
load1 lvd enable :It is an enumeration type:
If the enumeration value is 1, it means to disable the lvd control; If the enumeration value is 2, it means to enable the lvd control |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.31.2.1.1 |
||||
|
load1 lvd mode :It is an enumeration type:
If the enumeration value is 1, it means the voltage mode; If the enumeration value is 2, it means the time mode |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.31.2.1.2 |
||||
|
Low-voltage power-off voltage of the DMU unit can be configured by users.
Its value range: 36 to 56, units: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicat… |
Unsigned32r/w Constraints: range: 360-560 |
.1.3.6.1.4.1.2011.6.164.1.31.2.1.3 |
||||
|
Low-voltage power-off recover of the DMU unit can be configured by users.
Its value range: 37.0 to 58.0, unit: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indic… |
Unsigned32r/w Constraints: range: 370-580 |
.1.3.6.1.4.1.2011.6.164.1.31.2.1.4 |
||||
|
Low-voltage power-off disconnected time, It can be configured by users, and its value is an integer (1).
Here, if lvd mode is time mode, value range defines between 0 to 6000, unit: minutes(min). If the value is 2147… |
Integer32r/w Constraints: range: 0-6000 |
.1.3.6.1.4.1.2011.6.164.1.31.2.1.5 |
||||
|
Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
Value range: 0 to 99, unit: %, and the value is accurate to one decimal place (.1). If the value is… |
Integer32r/w Constraints: range: 0-99 |
.1.3.6.1.4.1.2011.6.164.1.31.2.1.6 |
||||
|
load1 lvd enable :It is an enumeration type:
If the enumeration value is 1, it means to disable the lvd control; If the enumeration value is 2, it means to enable the lvd control |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.31.2.1.7 |
||||
|
load1 lvd mode :It is an enumeration type:
If the enumeration value is 1, it means the voltage mode; If the enumeration value is 2, it means the time mode |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.1.31.2.1.8 |
||||
|
Low-voltage power-off voltage of the DMU unit can be configured by users.
Its value range: 36 to 56, units: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicat… |
Unsigned32r/w Constraints: range: 360-560 |
.1.3.6.1.4.1.2011.6.164.1.31.2.1.9 |
||||
|
Low-voltage power-off recover of the DMU unit can be configured by users.
Its value range: 37.0 to 58.0, unit: V, and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indic… |
Unsigned32r/w Constraints: range: 370-580 |
.1.3.6.1.4.1.2011.6.164.1.31.2.1.10 |
||||
|
Low-voltage power-off disconnected time, It can be configured by users, and its value is an integer (1).
Here, if lvd mode is time mode, value range defines between 0 to 6000, unit: minutes(min). If the value is 2147… |
Integer32r/w Constraints: range: 0-6000 |
.1.3.6.1.4.1.2011.6.164.1.31.2.1.11 |
||||
|
Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
Value range: 0 to 99, unit: %, and the value is accurate to one decimal place (.1). If the value is … |
Integer32r/w Constraints: range: 0-99 |
.1.3.6.1.4.1.2011.6.164.1.31.2.1.12 |
hwAtsSampTable
table.1.3.6.1.4.1.2011.6.164.1.33.1
·
1 row entry
·
3 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwAtsSampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAtsSampTable'
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table index of the running ATS modules
|
Unsigned32 Constraints: range: 0-256 |
.1.3.6.1.4.1.2011.6.164.1.33.1.1.1 |
|
ATS module ID.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.2011.6.164.1.33.1.1.2 |
|
Device name of the ATS module
|
OctetString Constraints: range: 0-56 |
.1.3.6.1.4.1.2011.6.164.1.33.1.1.3 |
hwSiteCameraTable
table.1.3.6.1.4.1.2011.6.164.3.1
·
1 row entry
·
14 columns
Uses the huawei variant from
Command help
/opt/observium/mibs/huawei.
Walk hwSiteCameraTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteCameraTable'
/
/
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
the camera ip adress.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.1 |
||||||||
|
camera connect port number.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.3.1.1.2 |
||||||||
|
You can set the alarm type to obtain the historical picture of the camera-related alarm shooting.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.164.3.1.1.5 |
||||||||
|
Associated alarm picture 1.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.6 |
||||||||
|
Associated alarm picture 2.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.7 |
||||||||
|
Associated alarm picture 3.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.8 |
||||||||
|
Associated alarm picture 4.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.9 |
||||||||
|
Associated alarm picture 5.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.10 |
||||||||
|
Associated alarm picture 6.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.11 |
||||||||
|
Associated alarm picture 7.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.12 |
||||||||
|
Associated alarm picture 8.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.13 |
||||||||
|
Associated alarm picture 9.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.14 |
||||||||
|
Associated alarm picture 10.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.15 |
||||||||
|
Additional associated alarm pictures.
|
OctetString | .1.3.6.1.4.1.2011.6.164.3.1.1.16 |