EMAP-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
46
Rows
46
Columns
532
.1.3.6.1.4.1.2011.6.164.1.1.2.99 · 1 row entry · 12 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteActiveAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteActiveAlarmTable'
hwSiteActiveAlarmEntry row .1.3.6.1.4.1.2011.6.164.1.1.2.99.1
Column Syntax OID
Site active alarm table index. It is the unique ID of the site alarm.
Integer32
Constraints:
range: 1-65535
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.1
Active alarm name. It is of the character string type, and used to specify the content of a specific alarm.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.2
Active alarm level, which users can configure the alarm severity, is an enumeration type:
If the enumeration value is 1, it indicates a critical alarm;
If the enumeration value is 2, it indicates a major alarm;
If the e…
Enumeration
Enumerated Values:
1critical
2major
3minor
4warning
255unknown
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.3
Active alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.4
Active alarm time. It is of the character string type, and used to specify the content of a specific alarm.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.5
Site name, which users can configure, is used to specify a site. Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.6
Site administrant address, which users can assigned, is the unique ID of a site. It is used for device management by NMS, and value range is 0 to 65535.
Unsigned32
Constraints:
range: 0-65535
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.7
NE ID. It is of the character string type. It is the unique ID of the site (an independent network element (NE)) on the network. Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.8
Site description. It is of the character string type. It is used to describe the site information such as the site location, which users can configure. Otherwise, the configured character can not be any other languages…
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.9
Equipment ID. Value range: 000,000 to 000,100, in which the first three digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.10
Equipment name. It is of the character string type, and users can set the name of the monitor.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.11
Rowstatus of active alarm table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.1.2.99.1.100
.1.3.6.1.4.1.2011.6.164.1.1.2.100 · 1 row entry · 5 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteAlarmTable'
/
hwSiteAlarmEntry row .1.3.6.1.4.1.2011.6.164.1.1.2.100.1
/
Indexes
Column Syntax OID
Site alarm table index. It is the unique ID of the site alarm.
Unsigned32
Constraints:
range: 1-4294967295
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.1
Alarm name. It is of the character string type, and used to specify the content of a specific alarm.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.2
Alarm level, which users can configure the alarm severity, is an enumeration type:
If the enumeration value is 1, it indicates a critical alarm;
If the enumeration value is 2, it indicates a major alarm;
If the enumerat…
Enumerationr/w
Enumerated Values:
1critical
2major
3minor
4warning
255unknown
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.3
Alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.4
RowStatus of site alarms table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.1.2.100.1.100
.1.3.6.1.4.1.2011.6.164.1.2.2.1 · 1 row entry · 14 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwMonitorTable'
/
hwMonitorEntry row .1.3.6.1.4.1.2011.6.164.1.2.2.1.1
/
Indexes
Column Syntax OID
Table index of the site monitors (hwSiteMonitorTable) is restricted by the quantity of the site monitors (hwMonsQuantity).
Value range: 1 to 100.
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.1
Site monitor ID.
Value range: 001,001 to 001,100, in which the first three digits indicate the device type and the last three digits indicate the device SN.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.2
Monitor name. It is of the character string type, and users can set the name of the monitor.
Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.3
Monitor description. It is of the character string type. Users can set the description of the monitor.
Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.4
Monitor software version. It is of the character string type.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.5
Monitor printed circuit board (PCB) hardware version. It is of the character string type.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.6
Monitor manufacture. It is of the character string type, and is an inherent attribute of the device.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.7
Monitor production date. It is of the character string type, and is an inherent attribute of the device.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.8
Production SN of the monitor. It is the electronic tag of the products.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.9
Total monitor runtime. The monitor counts the data in real time.
Value range is 0 to 65535,
The value is an integer (1),
Units:hours. (h).
It is used for performance measurement and evaluation of the monitor.
Unsigned32
Constraints:
range: 0-65535
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.10
Monitor control status. It is an enumeration type:
If the enumeration value is 1, it indicates the background control;
If the enumeration value is 2, it indicates the automatic control.
If the enumeration value is 255, …
Enumerationr/w
Enumerated Values:
1manualMode
2autoMode
255unknown
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.11
Warm-reset control of the monitor. It is an enumeration type:
If the enumeration value is 1, it indicates the Warm-reset control of the monitor is normal;
If the enumeration value is 2, it indicates the Warm-reset contr…
Enumerationr/w
Enumerated Values:
1normal
2reset
255unknown
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.12
State of the site monitor module. It is an enumeration type:
If the enumeration value is 1, it indicates that the site monitor module is in the normal state;
If the enumeration value is 2, it indicates that the monitor…
Enumeration
Enumerated Values:
1normal
2commRs485Fail
3commNetFail
4fault
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.99
RowStatus of site monitor.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.2.2.1.1.100
.1.3.6.1.4.1.2011.6.164.1.3.2.1 · 1 row entry · 13 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRectConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwRectConfigTable'
Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off. 
This table's index is hwRectConfigIndex, clone Rectifier config information table.
hwRectConfigEntry row .1.3.6.1.4.1.2011.6.164.1.3.2.1.1
Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off.
This table's index is hwRe…
Column Syntax OID
Index of the device configuration list for the rectifier modules, which value range: 1 to 256(To the actual subject). Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectsTotalQ…
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.1
Rectifier module ID. Value range: 002'001 to 002'255. The first digits indicate the device type and last three digits indicate the device SN.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.2
Device name of the rectifier module, character string type, is used to specify the rectifier module. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.3
Specific type of the rectifier module. It is an enumeration type:
If the enumeration value is 1, it indicates a 5A rectifier module;
If the enumeration value is 2, it indicates a 15A rectifier module;
If the enumerati…
Enumeration
Enumerated Values:
1eps5
2eps15
3eps30
4eps50
5eps100
255unknown
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.4
Software version of the rectifier module. It indicates the software version ID of the module.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.5
Manufacture of the rectifier module.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.6
Manufacture date of rectifiers is of string type.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.7
Rectifier module SN. It indicates the electronic tag of the product.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.8
Rated voltage of the rectifier module, is an inherent attribute.
Value range: 0 to 200, Units: A, and the value is accurate to one decimal place (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Unsigned32
Constraints:
range: 0-2000
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.9
Efficiency of the rectifier module, is an inherent attribute.
Value range: 0 to 100,
Units: %,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.10
Input AC type of the rectifier module. It is an enumeration value:
If the value of the node is 1, it indicates single-phase AC input;
If the value of the node is 2, it indicates three-phase AC input;
If the value of th…
Enumeration
Enumerated Values:
1single
2triple
3threeLivelines
4doubleLiveLines
255unknown
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.11
Power-on or power-off of the rectifier module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the rectifier module:
If the NMS notifies the…
Enumerationr/w
Enumerated Values:
1on
2off
255nullOper
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.12
RowStatus of rectifier config table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.3.2.1.1.100
.1.3.6.1.4.1.2011.6.164.1.3.2.2 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwRectOperTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwRectOperTable'
Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status. 
This table's index is hwRectRunIndex, clone rectifier runing information table.
hwRectOperEntry row .1.3.6.1.4.1.2011.6.164.1.3.2.2.1
Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status.
This table's index is hwRectRunIndex, clone rectifier runing information t…
Indexes
Column Syntax OID
Table index of the running rectifier modules,
which value range: 1 to 256(To the actual subject).
Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectsTotalQuantity).
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.1
Output current of the rectifier module. It is a real-time analog parameter.
Value range: 0 to 300,
Units: A,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates …
Unsigned32
Constraints:
range: 0-3000
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.2
Output voltage of the rectifier module. It is a real-time analog parameter.
Value range: 0 to 65,
Units: V,
the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that …
Unsigned32
Constraints:
range: 0-650
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.3
Total runtime of the rectifier module.
Value units: minute (m),
and the value is an integer (1).
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.4
DC output power.
Value range: 0 to 30000,
units: W,
and the value is an integer.(1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-30000
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.5
AC input voltage.
Value range: 0 to 600,
units: V,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-6000
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.6
Rated Efficiency.
Value range: 0 to 100,
units: %,
and the value is an integer.(1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.7
Rectifier Temperature.
Value range: -300 to 300,
units: degC,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -3000-3000
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.8
State of the rectifier module. It is an enumeration type:
If the enumeration value is 1, the rectifier module is in the normal state;
If the enumeration value is 2, a fault occurs on the rectifier module;
If the enume…
Enumeration
Enumerated Values:
1normal
2fault
3protect
4commFail
5switchOff
6invalid
7noConfig
8acOff
9rectLost
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.99
RowStatus of rectifier runing table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.3.2.2.1.100
.1.3.6.1.4.1.2011.6.164.1.4.3.100 · 1 row entry · 12 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBattsTestResultTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwBattsTestResultTable'
Battery test result record table. 
Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and test terminated course. 
This table's index is hwBattsTestResultIndex, clone Battery test result record table.
hwBattsTestResultEntry row .1.3.6.1.4.1.2011.6.164.1.4.3.100.1
Battery test result record table.
Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and t…
Column Syntax OID
Table index of the battery test results. Currently up to 10 times of the battery test results are saved by default.
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.1
Record test type of the battery test. It is an enumeration value:
If the NMS notifies the SNMP agent that this node is set to 1, it indicates a manual test;
If the NMS notifies the SNMP agent that this node is set to …
Enumeration
Enumerated Values:
1manualTest
2acOffAutoTest
3timedTest
4shortTest
255unknown
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.2
Test start time of the record in the battery test. It is of the character string type.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.3
Battery test result. It is an enumeration value.
If the enumeration value of the node is 1, it indicates that the battery test has no result:
If the enumeration value of the node is 2, it indicates that the battery is …
Enumeration
Enumerated Values:
1battNoResult
2battNormal
3battPreAlarm
4battAlarm
255unknown
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.4
Battery efficiency test.
Value range: 0 to 100,
Units: %,
and the value is an integer (1).
If the value is -1, it indicates that the test value is inefficient.
If the value is 255, it indicates that the test valu…
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.5
Discharge time of the battery test records.
Value range: 0 to 100,
units: hour (h),
and the value is accurate to two decimal places (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inva…
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.6
Discharge termination voltage of the battery test.
Value range: 0 to 60,
units: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-600
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.7
Average discharge current of the battery test.
Value range: -1000 to 1000,
units: A,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inval…
Integer32
Constraints:
range: -10000-10000
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.8
Discharge ampere per hour the battery test.
Value range: 0 to 5000,
Units: Ah,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-5000
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.9
Battery temperature of the battery test termination.
Value range: -50 to +100,
Units: centigrade (degC),
and the value is an integer (1).
If the value is -1024, it indicates that no battery temperature value sensor …
Integer32
Constraints:
range: -50-100
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.10
Termination factors of the battery test. It is an enumeration value.
If the enumeration value is 1, it indicates that the voltage value of the battery test reaches the set termination voltage;
If the enumeration value…
Enumeration
Enumerated Values:
1voltageToEnd
2timeToEnd
3acOnToEnd
4manulToEnd
5faultAlarmToEnd
6lowCapacityToEnd
7lowTempToEnd
255unknown
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.11
RowStatus of battery test table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.4.3.100.1.100
.1.3.6.1.4.1.2011.6.164.1.4.4.1 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBattStringConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwBattStringConfigTable'
Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone battery string config table.
hwBattStringConfigEntry row .1.3.6.1.4.1.2011.6.164.1.4.4.1.1
Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone …
Column Syntax OID
Device table index of the battery string,
value range: 1 to 100(To the actual subject).
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.1
Batteries device ID, can be configured by users. Value range: 003,001 to 003,100, in which the first three digits specify the device type and the last three specify the device SN.
Unsigned32
Constraints:
range: 3001-3100
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.2
Batteries device name, of the character string type, is used to specify the batteries. Users can configure it. Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.3
Upper threshold of the battery temperature alarm, can be configured by users.
Value range: 25 to 80,
Units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates t…
Integer32r/w
Constraints:
range: 25-80
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.4
Lower threshold of the battery temperature alarm, can be configured by users.
Value range: -20 to 20,
Units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates …
Integer32r/w
Constraints:
range: -20-20
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.5
Upper threshold of the battery temperature measurement, can be configured by users.
Value range: 0 to 100,
Units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indic…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.6
Lower threshold of the battery temperature measurement, can be configured by users.
Value range: -50 to 0,
Units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indic…
Integer32r/w
Constraints:
range: -50-0
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.7
Set battery standard capacity, is an inherent attribute of the device.
Value range: 5 to 10000,
units: Ah,
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invali…
Integer32r/w
Constraints:
range: 5-10000
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.8
Set battery install time, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-128
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.9
RowStatus of battery string config table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.4.4.1.1.100
.1.3.6.1.4.1.2011.6.164.1.4.4.2 · 1 row entry · 9 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwBattStringOperTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwBattStringOperTable'
Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as  battery temperature. 
This table's index is hwBattStringRunIndex, clone battery string runing table.
hwBattStringOperEntry row .1.3.6.1.4.1.2011.6.164.1.4.4.2.1
Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as battery temperature.
This table's index is hwBattStri…
Column Syntax OID
Device table index of the battery string,
which value range: 1 to 100(To the actual subject).
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.1
Batteries current. It is an analog parameter collected by the battery string in real time.
Value range: -1000 to +1000,
units: A,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7F…
Integer32
Constraints:
range: -10000-10000
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.2
Remaining capacity percentage of the battery string.
Value range: 0 to 100,
units: %,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inva…
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.3
Remaining capacity of the battery string. It is an analog parameter collected by the battery string in real time.
Value range: 0 to 1000,
units: Ah,
and the value is an integer (1).
If the value is 2147483647(0x7FF…
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.4
Batteries actual capacity. It is an analog parameter collected by the battery string in real time.
Value range: 0 to 5000,
units: Ah,
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates…
Unsigned32
Constraints:
range: 0-5000
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.5
Battery temperature. It is a battery parameter collected in real time.
Value range: -300 to +200,
unit: centigrade (degC),
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), …
Integer32
Constraints:
range: -3000-2000
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.6
Batteries midpoint voltage. It is an analog parameter collected by the battery string in real time.
Value range: -90 to +90,
unit: V,
and the value is accurate to one decimal place (.1).
Integer32
Constraints:
range: -900-900
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.7
State of the site battery string module. It is an enumeration type:
If the enumeration value is 1, it indicates that the site battery string is in the normal state;
If the enumeration value is 2, it indicates that the…
Enumeration
Enumerated Values:
1normal
2tempHigh
3tempLow
4loopBreak
5overCurrent
6unbalance
7discharge
8fuseBreak
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.99
RowStatus of battery string runing table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.100
.1.3.6.1.4.1.2011.6.164.1.5.2.1 · 1 row entry · 12 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwAcInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcInputTable'
AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status, 
as well as AC output breakers quantity, which defines hwAcOutputBreakerTable row number. This table's index is hwAcInputIndex, clone AC input table.
hwAcInputEntry row .1.3.6.1.4.1.2011.6.164.1.5.2.1.1
AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status,
as well as AC outpu…
Indexes
Column Syntax OID
ACU device table index,
which value range: 1 to 100.
Lines of the device list are restricted by the total quantity of ACUs (hwAcsInputQuantity).
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.1
ACU device ID, which users can configure. Value range: 004,001 to 004,100,
in which The first digits indicate the device type and the last three digits indicate the device SN.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.2
ACU device name, of the character string type, is used to specify the alternating current unit (ACU).
Users can configure it. Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.3
ACU A-phase or AB-line voltage.
Value range: 0 to 600,
units: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-6000
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.4
ACU B-phase or BC-line voltage.
Value range: 0 to 600,
units: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-6000
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.5
ACU C-phase or CA-line voltage.
Value range: 0 to 600,
units: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-6000
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.6
ACU A-phase current. It is an analog parameter collected by the ACU in real time.
Value range: 0 to 20000,
units: A,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it i…
Integer32
Constraints:
range: 0-200000
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.7
ACU B-phase current. It is an analog parameter collected by the ACU in real time.
Value range: 0 to 20000,
units: A,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it in…
Integer32
Constraints:
range: 0-200000
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.8
ACU C-phase current. It is an analog parameter collected by the ACU in real time.
Value range: 0 to 20000,
units: A,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it i…
Integer32
Constraints:
range: 0-200000
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.9
Quantity of the AC air circuit breakers.
As the ACU lower-level subset, the node indicates the quantity of the output air circuit breakers contained by each ACU lower-level subset. Value range: 0 to 100.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.10
State of the site AC distribution uint. It is an enumeration type:
If the enumeration value is 1, it indicates that the site AC distribution uint is in the normal state;
If the enumeration value is 2, it indicates tha…
Enumeration
Enumerated Values:
1normal
2acOff
3acAbsent
4voltHigh
5voltLow
6freqHigh
7freqLow
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.99
RowStatus of ACU.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.5.2.1.1.100
.1.3.6.1.4.1.2011.6.164.1.5.2.2 · 1 row entry · 5 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwAcInputBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcInputBreakerTable'
Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBreakersQuantity in hwAcInputTable, clone Ac input breaker table.
hwAcInputBreakerEntry row .1.3.6.1.4.1.2011.6.164.1.5.2.2.1
Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBrea…
Column Syntax OID
Device table index of the AC air circuit breaker.
Value range: 1 to 100.
An input air circuit breaker device can be uniquely identified through the ACU table index and device index of the AC air circuit breaker.
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.1
AC input air circuit breaker ID.
Value range: 005,001 to 005,100.
The first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 5001-5100
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.2
AC input air circuit breaker name, of the character string type, can configured by users. Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.3
Operation state of the site AC input breaker. It is an enumeration type:
If the enumeration value is 1, it indicates that the site AC input breaker is in the normal state;
If the enumeration value is 2, it indicates t…
Enumeration
Enumerated Values:
1normal
2disconnect
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.99
RowStatus of AC input breaker.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.5.2.2.1.100
.1.3.6.1.4.1.2011.6.164.1.6.2.1 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwDcOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwDcOutputTable'
/
hwDcOutputEntry row .1.3.6.1.4.1.2011.6.164.1.6.2.1.1
/
Indexes
Column Syntax OID
Device table index of the DC units, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of DC units (hwDcsQuantity).
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.1
DC unit device ID, which value range: 006,001 to 006,100. The first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 6001-6100
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.2
DC unit device name, of the character string type, can be configued by users. Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.3
DC output voltage. It is an analog parameter collected by the DC power in real time.
Value range: 0 to 100,
units: V,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it …
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.4
DC output current. It is an analog parameter collected by the DC power in real time.
Value range: -30000 to 30000,
units: A,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF…
Integer32
Constraints:
range: -300000-300000
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.5
DC output power. It is an analog parameter collected by the DC power in real time.
Value range: 0 to 3000000,
units: W,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the…
Unsigned32
Constraints:
range: 0-3000000
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.6
Quantity of the DC load output branches,
which value range: 0 to 100.
As the DC unit lower-level subset, the node indicates the quantity of the DC load output branches contained by each DC unit lower-level subset.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.7
The load usage of rated rectifier capacity.
Value range: 0 to 100,
units: %,
and the value is an integer (1).
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.8
State of the site DC distribution uint. It is an enumeration type:
If the enumeration value is 1, it indicates that the site DC distribution uint is in the normal state;
If the enumeration value is 2, it indicates tha…
Enumeration
Enumerated Values:
1normal
2voltHigh
3voltLow
4dcAbsent
5overload
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.99
RowStatus of Dc output equipments.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.6.2.1.1.100
.1.3.6.1.4.1.2011.6.164.1.6.2.2 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwLoadBranchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwLoadBranchTable'
Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity in hwDcOutputTable, clone loads output table.
hwLoadBranchEntry row .1.3.6.1.4.1.2011.6.164.1.6.2.2.1
Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity …
Column Syntax OID
Device table index of the DC load output branch,
which value range: 1 to 100.
A DC load output branch can be uniquely identified through the DC unit table index and device index of the DC load output branch.
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.1
Device ID of the DC load output branch. Value range: 007,001 to 007,100. The first digits indicate the device type and the last three digits indicate the SN of the device.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.2
Device name of the DC load output branch, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.3
DC load output branch current. It is an analog parameter collected by the load branch in real time.
Value range: 0 to 10000,
units: A,
and the value is accurate to one decimal space (.1).
If the value is 2147483647…
Integer32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.4
DC load branch power. It is an analog parameter collected by the DC power in real time.
Value range: 0 to 600000,
units: W,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that…
Unsigned32
Constraints:
range: 0-600000
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.5
DC load branch power consumption,
Value range: 0 to 4294967295,
units: KWh,
and the value is accurate to one decimal space (.1).
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.6
DC load branch power consumption,Value range: 0 to 4294967295, resolution:1 KWh.
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.8
Low 32 bits of DC load branch power consumption,Value range: 0 to 4294967295, resolution:10Wh
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.9
High 32 bits of DC load branch power consumption,Value range: 0 to 4294967295, resolution:10Wh
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.10
State of the site load output branch. It is an enumeration type:
If the enumeration value is 1, it indicates that the site load output branch is in the normal state;
If the enumeration value is 2, it indicates that th…
Enumeration
Enumerated Values:
1normal
2disconnect
3noresponse
4overload
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.99
RowStatus of loads output branch.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.6.2.2.1.100
.1.3.6.1.4.1.2011.6.164.1.7.2.1 · 1 row entry · 12 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwLvdBranchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwLvdBranchTable'
Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLvdBranchIndex, which qualificated by hwLvdsQuantity, clone power-off unit table.
hwLvdBranchEntry row .1.3.6.1.4.1.2011.6.164.1.7.2.1.1
Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLv…
Column Syntax OID
Device table index of a power-off unit.
Value range: 1 to 100. Lines of the device list are restricted by the total quantity of the power-off units (hwLvdsTotalQuantity).
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.1
Device ID of a power-off unit. Value range: 8001 to 8100. The first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 8001-8100
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.2
Device name of a power-off unit, of the character string type, is used to specify the low-voltage power-off unit. Users can configure it. Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.3
Control power-off unit enabling. It is an enumeration value, and users actively set it.
If the enumeration value is 1, it means to enable the power-off unit;
If the enumeration value is 2, it means to disable the powe…
Enumerationr/w
Enumerated Values:
1enabled
2disabled
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.4
Low-voltage power-off voltage of a power-off unit can be configured by users.
Its value range: 35 to 56,
units: V,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it ind…
Integer32r/w
Constraints:
range: 350-560
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.5
Control of the power-off unit. It is an enumeration value, users control it manually.
If the NMS notifies the SNMP agent that the node is set to 1, it means to power off the power-off unit;
If the NMS notifies the SNM…
Enumerationr/w
Enumerated Values:
1powerOff
2powerOn
255nullOper
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.6
Select the control mode of the power-off unit. It is an enumeration value, users can configure it manually.
If the NMS notifies the SNMP agent that the node is set to 1, it means to select the voltage power off mode;
Enumerationr/w
Enumerated Values:
1byVoltage
2byTime
3byCapacity
255unknown
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.7
Low-voltage power-off recover of a power-off unit can be configured by users.
Its value range: 37.0 to 58.0,
unit: V,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it …
Integer32r/w
Constraints:
range: 370-580
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.8
Low-voltage power-off disconnected time, It can be configured by users,
value range defines between 5 to 1000,
unit: minutes(min) ??
and its value is an integer (1).
Here, if battery manual test is standard mode,
If …
Integer32r/w
Constraints:
range: 5-1000
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.9
Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
Value range: 0 to 100,
unit: %,
and the value is accurate to one decimal space (.1).
If the value i…
Integer32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.10
State of the site LVD uint. It is an enumeration type:
If the enumeration value is 1, the site LVD uint is in the normal state;
If the enumeration value is 2, the power-off uint disconnect for low voltage;
If the enu…
Enumeration
Enumerated Values:
1normal
2lowVoltOff
3backgroundOff
4localManualOff
5lowTempOff
6highTempOff
7timeOff
8capacityOff
9forceOff
10maintenanceOff
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.99
RowStatus of lvd table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.100
.1.3.6.1.4.1.2011.6.164.1.8.2.1 · 1 row entry · 12 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwEnvTempSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwEnvTempSensorTable'
Site environment temperature table. 
Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment temperature lower limit, and environment temperature alarm enable. 
This table's index is hwEnvTempSensorIndex, which qualificated by hwEnvTempSensorsQuantity, clone site environment temperature table.
hwEnvTempSensorEntry row .1.3.6.1.4.1.2011.6.164.1.8.2.1.1
Site environment temperature table.
Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment …
Column Syntax OID
Table index of the environment temperature sensors.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.1
Environment temperature sensor ID.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.2
Environment temperature sensor name, of the character string type, is used to specify an environment temperature sensor.
Users can configure it. Otherwise, the configured character can not be any other languages excep…
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.3
Environment temperature. It is an environment parameter collected in real time.
Value range: -50 to +100,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647, it indicates that the…
Integer32
Constraints:
range: -50-100
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.4
Upper threshold of the environment temperature alarm, can be configured by users.
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inva…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.5
Lower threshold of the environment temperature alarm, can be configured by users.
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inv…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.6
Upper threshold of the environment temperature measurement, can be configured by users.
Value range: 0 to 100,
unit: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it in…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.7
Lower threshold of the environment temperature measurement, can be configured by users.
Value range: -50 to 0,
unit: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it in…
Integer32r/w
Constraints:
range: -50-0
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.8
Environment temperature alarm. It is an enumeration type:
If the enumeration value is 1, enable the alarm of the environment temperature;
If the enumeration value is 2, disable the alarm of the environment temperature.
Enumerationr/w
Enumerated Values:
1enable
2disable
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.9
Threshold of the environment ultra high temperature measurement, can be configured by users.
unit: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value …
SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.10
State of the site environment temperature sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site environment temperature sensor is in the normal state;
If the enumeration value is…
Enumeration
Enumerated Values:
1normal
2tempHigh
3tempLow
4notInslot
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.99
RowStatus of Environment temperature table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.8.2.1.1.100
.1.3.6.1.4.1.2011.6.164.1.8.2.2 · 1 row entry · 11 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwEnvHumiSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwEnvHumiSensorTable'
Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit, and environment humidity alarm enable. 
This table's index is hwEnvHumiSensorIndex, which qualificated by hwEnvHumiSensorIndex, clone site environment humidity table.
hwEnvHumiSensorEntry row .1.3.6.1.4.1.2011.6.164.1.8.2.2.1
Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit…
Column Syntax OID
Table index of the environment humility sensors.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.1
Environment humility sensor ID
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.2
Environment humility sensor name, of the character string type, is used to specify an environment humility sensor.
Users can configure it.Otherwise, the configured character can not be any other languages except Englis…
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.3
Environment humility. It is an environment parameter collected in real time.
Value range: 0 to 100,
units: %RH,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the humidity…
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.4
Upper threshold of the environment humility alarm, can be configured by users.
Value range: 0 to 100,
units: %RH,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.5
Lower threshold of the environment humility alarm, can be configured by users.
Value range: 0 to 100,
units: %RH,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.6
Upper threshold of the environment humility measurement, can be configured by users.
Value range: 0 to 100,
units: %RH,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.7
Lower threshold of the environment humility measurement, can be configured by users.
Value range: 0 to 100,
units: %RH,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the v…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.8
Environment humility alarm. It is an enumeration type:
If the enumeration value is 1, enable the alarm of the environment humility;
If the enumeration value is 2, disable the alarm of the environment humility.
The env…
Enumerationr/w
Enumerated Values:
1enable
2disable
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.9
State of the site environment humidity sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site environment humidity sensor is in the normal state;
If the enumeration value is 2, it…
Enumeration
Enumerated Values:
1normal
2humidityHigh
3humidityLow
4notInslot
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.99
RowStatus of Environment humidity table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.8.2.2.1.100
.1.3.6.1.4.1.2011.6.164.1.8.2.3 · 1 row entry · 7 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSpareDigitalTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSpareDigitalTable'
Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table.
hwSpareDigitalEntry row .1.3.6.1.4.1.2011.6.164.1.8.2.3.1
Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareD…
Column Syntax OID
Spare digital table index, which
value range: 1 to 256.
Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity).
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.1
Spare digital device ID. Value range: 011'001 to 011'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 11001-11255
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.2
Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-8
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.3
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a low-tension alarm;
If the value of the node is 2, it indicates a high-tension alarm.
Enumerationr/w
Enumerated Values:
0open
1close
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.4
Spare digital alarm enabling. It is an enumeration type:
If the enumeration value is 1, it means to enable the alarm;
If the enumeration value is 2, it means to disable the alarm.
Enumerationr/w
Enumerated Values:
1enable
2disable
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.5
State of the site Spare digital. It is an enumeration type:
If the enumeration value is 1, it indicates that the Spare digital operation state is normal;
If the enumeration value is 2, it indicates that a alarm occurs…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.99
RowStatus of of the site Spare digital.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.8.2.3.1.100
.1.3.6.1.4.1.2011.6.164.1.8.2.4 · 1 row entry · 7 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSpareDigitalOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSpareDigitalOutputTable'
Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table.
hwSpareDigitalOutputEntry row .1.3.6.1.4.1.2011.6.164.1.8.2.4.1
Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareD…
Column Syntax OID
Spare digital table index, which
value range: 1 to 256.
Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity).
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.1
Spare digital device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 12001-12255
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.2
Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any other languages except English.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.3
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a low-tension alarm;
If the value of the node is 2, it indicates a high-tension alarm.
Enumerationr/w
Enumerated Values:
1open
2close
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.4
Spare digital alarm enabling. It is an enumeration type:
If the enumeration value is 1, it means to enable the alarm;
If the enumeration value is 2, it means to disable the alarm.
Enumerationr/w
Enumerated Values:
1enable
2disable
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.5
State of the site Spare digital. It is an enumeration type:
If the enumeration value is 1, it indicates that the Spare digital operation state is normal;
If the enumeration value is 2, it indicates that a alarm occurs…
Enumeration
Enumerated Values:
1open
2close
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.99
RowStatus of Spare digital device table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.8.2.4.1.100

hwTemp1Table

table
.1.3.6.1.4.1.2011.6.164.1.8.2.5 · 1 row entry · 7 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwTemp1Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwTemp1Table'
Temp1 Table.
hwTemp1Entry row .1.3.6.1.4.1.2011.6.164.1.8.2.5.1
Temp1 Table.
Indexes
Column Syntax OID
Table index of the temp1 sensors. Value range: 1 to 256. Lines of the device list are restricted by the quantity of temp1 sensors (hwEnvHumiSensorsTotalQuantity).
Integer32
Constraints:
range: 3394-3394
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.1
Temp1 sensor ID, can be configured by users. Value range: 026'000 to 026'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 26000-26255
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.2
Temp1 sensor name, of the character string type, is used to specify an temp1 sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.3
Temp1. It is an environment parameter collected in real time.
Value range: -40 to +80,
units: centigrade (degC),
and the value is an integer (1).
If the value is -1024, it indicates that the temperature sensor is n…
Integer32
Constraints:
range: -40-80
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.4
Upper threshold of the temp1 alarm, can be configured by users.
Value range: 25 to 80,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value …
Integer32r/w
Constraints:
range: 25-80
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.5
Lower threshold of the temp1 alarm, can be configured by users. Value range: -20 to 20, units: centigrade (degC), and the value is an integer (1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is …
Integer32r/w
Constraints:
range: -20-20
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.6
State of the site temp1 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state;
If the enumeration value is 2, it indicates that the temp1 sens…
Enumeration
Enumerated Values:
1normal
2tempHigh
3tempLow
4notInslot
5tempFault
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.8.2.5.1.99

hwTemp2Table

table
.1.3.6.1.4.1.2011.6.164.1.8.2.6 · 1 row entry · 7 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwTemp2Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwTemp2Table'
Temp2 Table.
hwTemp2Entry row .1.3.6.1.4.1.2011.6.164.1.8.2.6.1
Temp2 Table.
Indexes
Column Syntax OID
Table index of the temp2 sensors.
Value range: 1 to 256.
Lines of the device list are restricted by the quantity of temp2 sensors (hwEnvHumiSensorsTotalQuantity).
Integer32
Constraints:
range: 3394-3394
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.1
Temp2 sensor ID, can be configured by users. Value range: 027'000 to 027'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 27000-27255
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.2
Temp2 sensor name, of the character string type, is used to specify an temp2 sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.3
Temp2. It is an environment parameter collected in real time.
Value range: -40 to +80,
units: centigrade (degC),
and the value is an integer (1).
If the value is -1024, it indicates that the temperature sensor is n…
Integer32
Constraints:
range: -40-80
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.4
Upper threshold of the temp2 alarm, can be configured by users.
Value range: 25 to 80,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value …
Integer32r/w
Constraints:
range: 25-80
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.5
Lower threshold of the temp2 alarm, can be configured by users.
Value range: -20 to 20,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Integer32r/w
Constraints:
range: -20-20
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.6
State of the site temp2 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp2 sensor is in the normal state;
If the enumeration value is 2, it indicates that the temp2 sens…
Enumeration
Enumerated Values:
1normal
2tempHigh
3tempLow
4notInslot
5tempFault
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.8.2.6.1.99
.1.3.6.1.4.1.2011.6.164.1.8.2.13 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSmokeSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSmokeSensorTable'
/
hwSmokeSensorEntry row .1.3.6.1.4.1.2011.6.164.1.8.2.13.1
/
Column Syntax OID
The tem_hum equip Index.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.13.1.1
/
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.13.1.2
/
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.8.2.13.1.3
The smoke sensor status
Enumeration
Enumerated Values:
0normal
1alarm
.1.3.6.1.4.1.2011.6.164.1.8.2.13.1.4
.1.3.6.1.4.1.2011.6.164.1.8.2.14 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwWaterSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwWaterSensorTable'
/
hwWaterSensorEntry row .1.3.6.1.4.1.2011.6.164.1.8.2.14.1
/
Column Syntax OID
The tem_hum equip Index.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.14.1.1
/
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.14.1.2
/
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.8.2.14.1.3
The smoke sensor status
Enumeration
Enumerated Values:
0normal
1alarm
.1.3.6.1.4.1.2011.6.164.1.8.2.14.1.4
.1.3.6.1.4.1.2011.6.164.1.8.2.15 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwDoorSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwDoorSensorTable'
/
hwDoorSensorEntry row .1.3.6.1.4.1.2011.6.164.1.8.2.15.1
/
Column Syntax OID
The tem_hum equip Index.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.15.1.1
/
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.8.2.15.1.2
/
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.8.2.15.1.3
The smoke sensor status
Enumeration
Enumerated Values:
0normal
1alarm
.1.3.6.1.4.1.2011.6.164.1.8.2.15.1.4
.1.3.6.1.4.1.2011.6.164.1.9.2.1 · 1 row entry · 26 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwInverterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwInverterTable'
/
hwInverterEntry row .1.3.6.1.4.1.2011.6.164.1.9.2.1.1
/
Indexes
Column Syntax OID
Inverter table index,which value range:1 to 256.Lines of the device list are restricted by the quantity of Inverter.
Unsigned32
Constraints:
range: 1-256
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.1
Inverter device ID. Value range: 018'001 to 018'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 18001-18255
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.2
Inverter name, of the character string type, is used to specify Inverters. Users can configure it.Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.3
Inverter AC Output voltage,
Value range: 0.0 to 10000.0.
Unit: V.
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.4
Inverter AC Output current,
Value range: 0.0 to 10000.0.
Unit: A.
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.5
Inverter AC Output frequency,
Value range: 0 to 10000.
Unit: Hz.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.6
Inverter AC Output power,
Value range: 0 to 10000000.
Unit: W.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.7
Inverter AC Output power,
Value range: 0.0 to 100000.0.
Unit: VA.
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.8
Inverter AC Input voltage,
Value range: 0.0 to 10000.0.
Unit: V.
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.9
Inverter AC Input current,
Value range: 0.0 to 10000.0.
Unit: A.
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.10
Inverter AC Input frequency,
Value range: 0 to 10000.
Unit: Hz.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.11
Inverter AC Input power,
Value range: 0 to 10000000.
Unit: W.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.12
Inverter AC Input power,
Value range: 0.0 to 10000.0.
Unit: VA.
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.13
Inverter DC Input voltage,
Value range: 0.0 to 10000.0.
Unit: V.
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.14
Inverter DC Input current,
Value range: 0 to 10000.
Unit: A.
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.15
Inverter DC Input power,
Value range: 0 to 10000000.
Unit: W.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.16
Inverter software version number.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.17
Inverter Number of the phase module, Value range: 0 to 10000. If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.18
Inverter Number of AC group,
Value range: 0 to 10000.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.19
Inverter Number of DC group,
Value range: 0 to 10000.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.20
Inverter Number of Major alarm,
Value range: 0 to 10000.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.21
Inverter Number of Minor alarm,
Value range: 0 to 10000.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.22
Inverter T2S serial number,
Value range: 0 to 4294967295.
If the value is 4294967295(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.23
Inverter module Temperature,
Value range: -300 to 10000.
Unit: degC.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -300-10000
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.24
State of the Inverter. It is an enumeration type:
If the enumeration value is 1, it indicates that the Inverter is in the normal state;
If the enumeration value is 2, it indicates that the Inverter is in the alarm stat…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknow
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.99
RowStatus of Inverter table.
RowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.9.2.1.1.100

hwFanTable

table
.1.3.6.1.4.1.2011.6.164.1.10.2.1 · 1 row entry · 14 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwFanTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwFanTable'
/
hwFanEntry row .1.3.6.1.4.1.2011.6.164.1.10.2.1.1
/
Indexes
Column Syntax OID
Fan table index,which
value range: 1 to 256.
Lines of the device list are restricted by the quantity of Fan.
Unsigned32
Constraints:
range: 1-256
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.1
Fan device ID. Value range: 020'001 to 020'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 20001-20255
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.2
Fan name, of the character string type, is used to specify Fans. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.3
State of the Fan ctrl mode. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in autoControl state;
If the enumeration value is 2, it indicates that the fan is in manualControl stat…
Enumerationr/w
Enumerated Values:
1autoControl
2manualControl
3other
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.4
State of the Fan1 status. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in normal state;
If the enumeration value is 2, it indicates that the fan is in fault state;
If the enume…
Enumeration
Enumerated Values:
1normal
2fault
3inexistent
255unknown
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.5
State of the Fan2 status. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in normal state;
If the enumeration value is 2, it indicates that the fan is in fault state;
If the enume…
Enumeration
Enumerated Values:
1normal
2fault
3inexistent
255unknown
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.6
State of the Fan3 status. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in normal state;
If the enumeration value is 2, it indicates that the fan is in fault state;
If the enume…
Enumeration
Enumerated Values:
1normal
2fault
3inexistent
255unknown
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.7
State of the Fan4 status. It is an enumeration type:
If the enumeration value is 1, it indicates that the fan is in normal state;
If the enumeration value is 2, it indicates that the fan is in fault state;
If the enume…
Enumeration
Enumerated Values:
1normal
2fault
3inexistent
255unknown
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.8
Fan1 speed,
Value range: 0 to 10000.
Unit: rpm.
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.9
Fan2 speed,
Value range: 0 to 10000.
Unit: rpm.
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.10
Fan3 speed,
Value range: 0 to 10000.
Unit: rpm.
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.11
Fan4 speed,
Value range: 0 to 10000.
Unit: rpm.
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.12
State of the fan. It is an enumeration type:
If the enumeration value is 1, it indicates that the Inverter is in the normal state;
If the enumeration value is 2, it indicates that the Inverter is in the fault state;
Enumeration
Enumerated Values:
1normal
2fault
254alarmResume
255unknow
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.99
RowStatus fo fan table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.10.2.1.1.100
.1.3.6.1.4.1.2011.6.164.1.10.2.2 · 1 row entry · 20 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwDcAirConditionTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwDcAirConditionTable'
hwDcAirConditionEntry row .1.3.6.1.4.1.2011.6.164.1.10.2.2.1
Indexes
Column Syntax OID
Dc aircondition table index
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.1
Dc aircondition device ID.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.2
Dc aircondition name, of the character string type, is used to specify Fans. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.3
State of the Dc aircondition ctrl mode. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in autoControl state;
If the enumeration value is 2, it indicates that the Dc a…
Enumerationr/w
Enumerated Values:
1autoControl
2manualControl
255unknown
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.4
State of the Dc aircondition control on or off. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in on state;
If the enumeration value is 2, it indicates that the Dc ai…
Enumerationr/w
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.5
State of the Dc aircondition run status. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in standby state;
If the enumeration value is 2, it indicates that the Dc airc…
Enumeration
Enumerated Values:
1standby
2run
3fault
255unknown
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.6
State of the Dc air compressor run status. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in standby state;
If the enumeration value is 2, it indicates that the Dc ai…
Enumeration
Enumerated Values:
1standby
2run
3fault
255unknown
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.7
Dc aircondition innr speed,
Value range: 0 to 60000.
Unit: rpm,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: 0-60000
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.8
Dc aircondition outer speed,
Value range: 0.0 to 60000.0.
Unit: rpm,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: 0-60000
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.9
Dc aircondition compressor run time,
Value range: 0 to 175200.
Unit: h,
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: 0-175200
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.10
Dc aircondition run time,
Value range: 0 to 175200.
Unit: H,
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: 0-175200
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.11
Dc aircondition enter channel temperature,
Value range:-500.0 to 1000.0.
Unit: degC.
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -500-1000
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.13
Dc aircondition power on temperature point,
Value range:-200 to 800.
Unit: degC.
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32r/w
Constraints:
range: -200-800
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.14
Dc aircondition power off temperature point,
Value range:-200 to 800
Unit: degC.
the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32r/w
Constraints:
range: -200-800
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.15
State of the Dc air energy saving status. It is an enumeration type:
If the enumeration value is 1, it indicates that the Dc aircondition is in disable state;
If the enumeration value is 2, it indicates that the Dc air…
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.17
Dc aircondition power on ac fail temperature point,
Value range:-200 to 800.
Unit: degC.
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32r/w
Constraints:
range: -200-800
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.18
Dc aircondition compressor start temperature point,
Value range:-200 to 800.
Unit: degC.
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32r/w
Constraints:
range: -200-800
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.19
DC Air Device address
And the value is an integer (1).
Unsigned32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.21
State of the dc aircondition. It is an enumeration type:
If the enumeration value is 1, it indicates that the Inverter is in the standby state;
If the enumeration value is 2, it indicates that the Inverter is in the ru…
Enumeration
Enumerated Values:
1standby
2run
3fault
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.99
RowStatus fo dc aircondition table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.10.2.2.1.100
.1.3.6.1.4.1.2011.6.164.1.11.2.1 · 1 row entry · 37 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteAcAmmeterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteAcAmmeterTable'
/
hwSiteAcAmmeterEntry row .1.3.6.1.4.1.2011.6.164.1.11.2.1.1
/
Column Syntax OID
Ac Ammeter table index,which value range:4096 to 20479. Lines of the device list are restricted by the quantity of AcAmmeter
Unsigned32
Constraints:
range: 4096-20479
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.1
Ac Ammeter device ID. Value range: 022'001 to 022'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 22001-22255
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.2
Ac Ammeter name, of the character string type, is used to specify Fans. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.3
Ac Ammeter frequency,
Value range: 0.00 to 1000.00.
Unit: Hz.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.4
Ac Ammeter phase a voltage,
Value range: 0.00 to 2000.00.
Unit: V.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-200000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.5
Ac Ammeter phase b voltage,
Value range: 0.00 to 2000.0.
Unit: V.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-200000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.6
Ac Ammeter phase c voltage,
Value range: 0.00 to 2000.0.
Unit: V.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-200000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.7
Ac Ammeter set channel number,
Value range: 1 to 4.
Unit: NA.
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32r/w
Constraints:
range: 1-4
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.8
Ac Ammeter clear communication failure . It is an enumeration type:
If the enumeration value is 1, it indicates that the ac ammeter clear communication failure alarm;
Enumerationr/w
Enumerated Values:
1clear
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.9
Ac Ammeter type, Value range: 0 to 65535. And the value is an integer(1).
Unsigned32
Constraints:
range: 0-65535
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.10
Ac Ammeter version, of the character string type, is used to specify Ac Ammeter. Users can not configure it.
OctetString
Constraints:
range: 0-56
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.11
Ac Ammeter phase a current of channel 1,
Value range: 0.00 to 1000.0.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.12
Ac Ammeter phase b current of channel 1,
Value range: 0.00 to 1000.0.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.13
Ac Ammeter phase c current of channel 1,
Value range: 0.00 to 1000.0.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.14
Ac Ammeter phase c current of channel 1,
Value range: -1000000.00 to 1000000.00.
Unit: kW.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is i…
Integer32
Constraints:
range: -100000000-100000000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.15
Ac Ammeter total power factor of channel 1,
Value range: -10.00 to 10.00.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.16
Ac Ammeter total active engry acc of channel 1,
Value range: 0.00 to 1000000000.00.
Unit: kWh.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value …
Unsigned32
Constraints:
range: 0-10000000000000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.17
Ac Ammeter phase a current of channel 2,
Value range: 0.00 to 1000.00.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.18
Ac Ammeter phase b current of channel 2,
Value range: 0.00 to 1000.00.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.19
Ac Ammeter phase c current of channel 2,
Value range: 0.00 to 1000.00.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.20
Ac Ammeter phase c current of channel 2,
Value range: -1000000.00 to 1000000.00.
Unit: kW.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is i…
Integer32
Constraints:
range: -100000000-100000000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.21
Ac Ammeter total power factor of channel 2,
Value range: -10.00 to 10.00.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.22
Ac Ammeter total active engry acc of channel 2,
Value range: 0.00 to 1000000000.00.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is…
Unsigned32
Constraints:
range: 0-100000000000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.23
Ac Ammeter phase a current of channel 3,
Value range: 0.00 to 1000.00.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.24
Ac Ammeter phase b current of channel 3,
Value range: 0.00 to 1000.00.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.25
Ac Ammeter phase c current of channel 3,
Value range: 0.00 to 1000.00.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.26
Ac Ammeter phase c current of channel 3,
Value range: -1000000.00 to 1000000.00.
Unit: kW.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is i…
Integer32
Constraints:
range: -100000000-100000000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.27
Ac Ammeter total power factor of channel 3,
Value range: -10.00 to 10.00.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.28
Ac Ammeter total active engry acc of channel 3,
Value range: 0.00 to 1000000000.00.
Unit: kWh.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value …
Unsigned32
Constraints:
range: 0-100000000000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.29
Ac Ammeter phase a current of channel 4,
Value range: 0 to 1000.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.30
Ac Ammeter phase b current of channel 4,
Value range: 0 to 1000.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.31
Ac Ammeter phase c current of channel 4,
Value range: 0 to 1000.
Unit: A.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.32
Ac Ammeter phase c current of channel 4,
Value range: -1000000 to 1000000.
Unit: kW.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -100000000-100000000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.33
Ac Ammeter total power factor of channel 4,
Value range: -10.00 to 10.00.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.34
Ac Ammeter total active engry acc of channel 4,
Value range: 0 to 1000000000.
Unit: kWh.
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inv…
Unsigned32
Constraints:
range: 0-100000000000
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.35
State of the Ac Ammeter. It is an enumeration type:
If the enumeration value is 1, it indicates that the Ac Ammeter is in the normal state;
If the enumeration value is 2, it indicates that the Ac Ammeter is in the faul…
Enumeration
Enumerated Values:
1normal
2fault
255unknown
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.99
RowStatus fo Ac Ammeter table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.11.2.1.1.100

hwDGTable

table
.1.3.6.1.4.1.2011.6.164.1.12.2.1 · 1 row entry · 23 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwDGTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwDGTable'
/
hwDGEntry row .1.3.6.1.4.1.2011.6.164.1.12.2.1.1
/
Indexes
Column Syntax OID
DG table index,which value range:1 to 256. Lines of the device list are restricted by the quantity of DG.
Integer32
Constraints:
range: 0-256
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.1
DG device ID. Value range: 023'001 to 023'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 23001-23255
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.2
Device name of the DG module, character string type, is used to specify the DG module. Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.3
Specific type of the DG module. It is an enumeration type:
If the enumeration value is 1, it indicates a intelligent DG module;
If the enumeration value is 2, it indicates a non_intelligent module;
If the enumeration …
Enumeration
Enumerated Values:
1intelligent
2non_intelligent
255unknown
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.4
A-phase voltage.
Value range: 0 to 500,
units: V,
and the value is accurate to one decimal place (.1).
Unsigned32
Constraints:
range: 0-5000
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.5
B-phase voltage.
Value range: 0 to 500,
units: V,
and the value is accurate to one decimal place (.1).
Unsigned32
Constraints:
range: 0-5000
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.6
C-phase voltage.
Value range: 0 to 500,
units: V,
and the value is accurate to one decimal place (.1).
Unsigned32
Constraints:
range: 0-5000
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.7
A-phase current.
Value range: 0 to 100,
units: A,
and the value is an integer (1).
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.8
B-phase current.
Value range: 0 to 100,
units: A,
and the value is an integer (1).
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.9
C-phase current.
Value range: 0 to 100,
units: A,
and the value is an integer (1).
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.10
DG output power.
Value range: 0 to 100,
units: kw,
and the value is one decimal space (.1).
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.11
The frequency of DG.
Value range: 5 to 120,
units: Hz,
and the value is one decimal space (.1).
Unsigned32
Constraints:
range: 50-1200
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.12
The voltage of DG battery.
Value range: 0 to 24,
units: V,
and the value is one decimal space (.1).
Unsigned32
Constraints:
range: 0-240
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.13
The total running time of DG,
Value range: 0 to 876000,
units: h,
and the value is one decimal space (.1).
Unsigned32
Constraints:
range: 0-8760000
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.14
A phase power factor of DG,
Value range: -1 to 1,
units: ,
and the value is two decimal space (.01).
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.15
B phase power factor of DG,
Value range: -1 to 1,
units: ,
and the value is two decimal space (.01).
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.16
C phase power factor of DG,
Value range: -1 to 1,
units: ,
and the value is two decimal space (.01).
Integer32
Constraints:
range: -100-100
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.17
The load rate of DG,
Value range: 0 to 100,
units: %,
and the value is one decimal space (.1).
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.18
Power-on or power-off of the DG module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the DG module:
If the NMS notifies the SNMP agent th…
Enumerationr/w
Enumerated Values:
1on
2off
255unknown
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.19
DG fault reset.
Enumerationr/w
Enumerated Values:
1reset
255unknown
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.20
DG maintenance confirm.
Enumerationr/w
Enumerated Values:
1reset
255unknown
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.21
State of the DG. It is an enumeration type:
If the enumeration value is 1, it indicates that the DG is in the normal state;
If the enumeration value is 2, it indicates that the DG is in the fault state;
If the enumer…
Enumeration
Enumerated Values:
1stop
2running
255unknown
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.99
RowStatus fo DG.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.12.2.1.1.100

hwSSUTable

table
.1.3.6.1.4.1.2011.6.164.1.13.2.1 · 1 row entry · 9 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSSUTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSSUTable'
/
hwSSUEntry row .1.3.6.1.4.1.2011.6.164.1.13.2.1.1
/
Indexes
Column Syntax OID
SSU table index,which value range:1 to 256. Lines of the device list are restricted by the quantity of SSU.
Integer32
Constraints:
range: 0-256
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.1
SSU device ID. Value range: 024'001 to 024'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 24001-24255
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.2
Device name of the SSU module, character string type, is used to specify the SSU module.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.3
The running status of the SSU module. It is an enumeration type:
If the enumeration value is 1, it indicates that the SSU module is power on ;
If the enumeration value is 2, it indicates that the SSU module is power of…
Enumeration
Enumerated Values:
1on
2off
255nullOper
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.4
The input voltage of SSU,
Value range: 0 to 200,
units: V,
and the value is one decimal space (.1).
Unsigned32
Constraints:
range: 0-2000
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.5
The output voltage of SSU,
Value range: 0 to 200,
units: V,
and the value is one decimal space (.1).
Unsigned32
Constraints:
range: 0-2000
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.6
The output current of SSU,
Value range: 0 to 1000,
units: A,
and the value is one decimal space (.1).
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.7
The address of SSU,
Value range: 0 to 100,
units: ,
and the value is an integer (1).
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.8
RowStatus fo SSU.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.13.2.1.1.100
.1.3.6.1.4.1.2011.6.164.1.14.2.1 · 1 row entry · 19 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteBatteryCabinetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteBatteryCabinetTable'
/
hwSiteBatteryCabinetEntry row .1.3.6.1.4.1.2011.6.164.1.14.2.1.1
/
Column Syntax OID
Battery Cabinet table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Battery Cabinet
Unsigned32
Constraints:
range: 4096-20479
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.1
Battery Cabinet device ID. Value range: 025'001 to 025'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 25000-25255
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.2
Battery Cabinet name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.3
Indoor vent temperature. It is an environment parameter collected in real time.
Value range: -40 to +100,
units: centigrade,
and the value is an integer (1).
If the value is -99999, it indicates that the temperatur…
Integer32
Constraints:
range: -40-100
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.4
Battery temperature. It is an environment parameter collected in real time.
Value range: -40 to +100,
units: centigrade,
and the value is an integer (1).
If the value is -99999, it indicates that the temperature sen…
Integer32
Constraints:
range: -40-100
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.5
Fan 1 speed,
Value range: 0.0 to 10000.0.
Unit: rpm,
the value is an integer (1).
If the value is -1, it indicates that the fan is not configured.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.6
Fan 2 speed,
Value range: 0.0 to 10000.0.
Unit: rpm,
the value is an integer (1).
If the value is -1, it indicates that the fan is not configured.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.7
Fan 3 speed,
Value range: 0.0 to 10000.0.
Unit: rpm,
the value is an integer (1).
If the value is -1, it indicates that the fan is not configured.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.8
Fan 4 speed,
Value range: 0.0 to 10000.0.
Unit: rpm,
the value is an integer (1).
If the value is -1, it indicates that the fan is not configured.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.9
State of the airconditioner. It is an enumeration type:
If the enumeration value is 1, it indicates that the airconditioner is in the standby state;
If the enumeration value is 2, it indicates that the airconditioner i…
Enumeration
Enumerated Values:
1standby
2run
3fault
255unknown
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.10
State of the compressor. It is an enumeration type:
If the enumeration value is 1, it indicates that the compressor is in the standby state;
If the enumeration value is 2, it indicates that the compressor is in the run…
Enumeration
Enumerated Values:
1standby
2run
3fault
255unknown
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.11
Internal Fan speed,
Value range: 0 to 10000.
Unit: rpm,
the value is an integer (1).
If the value is -1, it indicates that the fan is not configured.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.12
External Fan speed,
Value range: 0 to 10000.
Unit: rpm,
the value is an integer (1).
If the value is -1, it indicates that the temperature sensor is not configured.
Integer32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.13
Total runtime of the air conditioner.
Value units: hour (h),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.14
Total runtime of the compressor.
Value units: hour (h),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.15
Battery cabinet aircondition power on temperature point,
Value range:-20 to 80
Unit: degC.
and the value is an integer (1).
Integer32r/w
Constraints:
range: -20-80
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.16
Battery cabinet aircondition power off temperature point,
Value range:-20 to 80
Unit: degC.
and the value is an integer(1).
Integer32r/w
Constraints:
range: -20-80
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.17
State of the Battery Cabinet. It is an enumeration type:
If the enumeration value is 1, it indicates that the Inverter is in the normal state;
If the enumeration value is 2, it indicates that the Inverter is in the fau…
Enumeration
Enumerated Values:
1normal
2fault
255unknown
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.99
RowStatus fo Battery Cabinet table.
RowStatusr/w
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
Description.
.1.3.6.1.4.1.2011.6.164.1.14.2.1.1.100

hwEsduTable

table
.1.3.6.1.4.1.2011.6.164.1.15.2 · 1 row entry · 38 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwEsduTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwEsduTable'
/
hwEsduEntry row .1.3.6.1.4.1.2011.6.164.1.15.2.1
/
Indexes
Column Syntax OID
ESDU equip index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Battery Cabinet
Unsigned32
Constraints:
range: 3428-3443
.1.3.6.1.4.1.2011.6.164.1.15.2.1.1
Esdu device ID. Value range: 028,001 to 028,255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 28001-28255
.1.3.6.1.4.1.2011.6.164.1.15.2.1.2
/
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.15.2.1.3
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.4
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.5
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.6
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.7
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.8
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.9
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.10
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.11
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.12
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.13
Spare digital alarm state. It is an enumeration value.If the value of the node is 1, it indicates a high-tension alarm;If the value of the node is 2, it indicates a low-tension alarm;If the value of the node is 255, it …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.14
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.15
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.16
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.17
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.18
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.19
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.20
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.21
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.22
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.23
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.24
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.25
Spare digital alarm state. It is an enumeration value.
If the value of the node is 1, it indicates a high-tension alarm;
If the value of the node is 2, it indicates a low-tension alarm;
If the value of the node is 255, …
Enumerationr/w
Enumerated Values:
1close
2open
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.26
It indicates the digital input operation status. It is an enumeration value.
If the value of the node is 1, it indicates that the diesel of state is normal;
If the value of the node is 2, it indicates that the diesel of…
Enumeration
Enumerated Values:
1normal
2alarm
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.27
Temp1. It is an environment parameter collected in real time.
Value range: -40 to +80,
Unit: degC
and the value is an integer (1).
If the value is -1024, it indicates that the temperature sensor is not configured.
Integer32
Constraints:
range: -40-80
.1.3.6.1.4.1.2011.6.164.1.15.2.1.28
State of the site temp1 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state;
If the enumeration value is 2, it indicates that the temp1 sens…
Enumeration
Enumerated Values:
1normal
2tempHigh
3tempLow
4notInslot
5tempFault
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.31
Temp1. It is an environment parameter collected in real time.
Value range: -40 to +80,
units: centigrade (degC),
and the value is an integer (1).
If the value is -1024, it indicates that the temperature sensor is n…
Integer32
Constraints:
range: -40-80
.1.3.6.1.4.1.2011.6.164.1.15.2.1.32
Upper threshold of the temp1 alarm, can be configured by users.
Value range: 25 to 80,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value …
Integer32r/w
Constraints:
range: 25-80
.1.3.6.1.4.1.2011.6.164.1.15.2.1.33
Lower threshold of the temp1 alarm, can be configured by users.
Value range: -20 to 20,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Integer32r/w
Constraints:
range: -20-20
.1.3.6.1.4.1.2011.6.164.1.15.2.1.34
State of the site temp1 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp1 sensor is in the normal state;
If the enumeration value is 2, it indicates that the temp1 sens…
Enumeration
Enumerated Values:
1normal
2tempHigh
3tempLow
4notInslot
5tempFault
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.35
Temp2. It is an environment parameter collected in real time.
Value range: -40 to +80,
units: centigrade (degC),
and the value is an integer (1).
If the value is -1024, it indicates that the temperature sensor is n…
Integer32
Constraints:
range: -40-80
.1.3.6.1.4.1.2011.6.164.1.15.2.1.36
Upper threshold of the temp2 alarm, can be configured by users.
Value range: 25 to 80,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value …
Integer32r/w
Constraints:
range: 25-80
.1.3.6.1.4.1.2011.6.164.1.15.2.1.37
Lower threshold of the temp2 alarm, can be configured by users.
Value range: -20 to 20,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Integer32r/w
Constraints:
range: -20-20
.1.3.6.1.4.1.2011.6.164.1.15.2.1.38
State of the site temp2 sensor. It is an enumeration type:
If the enumeration value is 1, it indicates that the site temp2 sensor is in the normal state;
If the enumeration value is 2, it indicates that the temp2 sens…
Enumeration
Enumerated Values:
1normal
2tempHigh
3tempLow
4notInslot
5tempFault
254alarmResume
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.39
Door Sensor Connected; It is an enumeration value, and can be configured.
If the enumeration value is 1, it indicates Door Sensor is disable;
If the enumeration value is 2, it indicates Door Sensor is enalble;
If the e…
Enumerationr/w
Enumerated Values:
1disable
2enable
255unknown
.1.3.6.1.4.1.2011.6.164.1.15.2.1.40
.1.3.6.1.4.1.2011.6.164.1.17.1 · 1 row entry · 13 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwAcbGroupSampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbGroupSampTable'
/
hwAcbGroupSampEntry row .1.3.6.1.4.1.2011.6.164.1.17.1.1
/
Indexes
Column Syntax OID
The battery group equip Index.
Unsigned32
Constraints:
range: 0-256
.1.3.6.1.4.1.2011.6.164.1.17.1.1.1
The battery group equip ID no.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.17.1.1.2
The battery group equip name.
OctetString .1.3.6.1.4.1.2011.6.164.1.17.1.1.3
State of the Battery group unit running state. It is an enumeration type:
If the enumeration value is 1, it indicates the Battery is first on line,
If the enumeration value is 2, it indicates that Battery power off,
If …
Enumeration
Enumerated Values:
1firstOn
2powerOff
3float
4equal
5dicharge
6charge
7test
255unknown
.1.3.6.1.4.1.2011.6.164.1.17.1.1.4
The battery volt; Value range: 0 to 100,
units: V.
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.17.1.1.5
The battery current; Value range: -4000 to 4000,
units: A.
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -40000-40000
.1.3.6.1.4.1.2011.6.164.1.17.1.1.6
The battery total capacity; Value range: 0 to 10000,
units: Ah.
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.17.1.1.7
The battery total remain capacity; Value range:0 to 100,
units: %.
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.17.1.1.8
The battery temperature; Value range:-50 to 100,
units: degC.
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Integer32
Constraints:
range: -500-1000
.1.3.6.1.4.1.2011.6.164.1.17.1.1.9
The battery backup time; Value range: 0 to 256,
units: h.
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-2560
.1.3.6.1.4.1.2011.6.164.1.17.1.1.11
The esmu communicate number,
Value range: 0 to 100.
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.17.1.1.12
The battery soh: 0 to 100,
units: %.
and the value is accurate to one decimal place (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.17.1.1.13
The battery total discharge depth,
units: %.
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 10-1000
.1.3.6.1.4.1.2011.6.164.1.17.1.1.22
.1.3.6.1.4.1.2011.6.164.1.17.2 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwAcbGroupSetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbGroupSetTable'
/
hwAcbGroupSetEntry row .1.3.6.1.4.1.2011.6.164.1.17.2.1
/
Column Syntax OID
Battery cell number.
Value range: 1 to 32,
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 1-32
.1.3.6.1.4.1.2011.6.164.1.17.2.1.5
The battery total capacity,
units: wh.
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-10000
.1.3.6.1.4.1.2011.6.164.1.17.2.1.6
Battery equalcharge voltage, can be configued by users.
Value range: 42 to 58,
units: v,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is inval…
Unsigned32r/w
Constraints:
range: 420-580
.1.3.6.1.4.1.2011.6.164.1.17.2.1.11
Battery floatcharge voltage, can be configued by users.
Value range: 42 to 58,
units: v,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invali…
Unsigned32r/w
Constraints:
range: 420-580
.1.3.6.1.4.1.2011.6.164.1.17.2.1.12
Battery charge limited threhold , can be configued by users.
Value range: 0.05 to 2,
units: C10,
and the value is accurate to two decimal space (.01).
If the setting value is beyond the current support range, it will fa…
Unsigned32r/w
Constraints:
range: 5-200
.1.3.6.1.4.1.2011.6.164.1.17.2.1.13
Battery over charge current limited threhold , can be configued by users.
Value range: 0.15 to 1.2,
units: C10,
and the value is accurate to two decimal space (.01).
If the value is 2147483647(0x7FFFFFFF), it indicates …
Unsigned32r/w
Constraints:
range: 15-120
.1.3.6.1.4.1.2011.6.164.1.17.2.1.14
Upper threshold of the environment temperature alarm, can be configured by users.
Value range: 35 to 70,
units: centigrade (??C),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates tha…
Unsigned32r/w
Constraints:
range: 35-70
.1.3.6.1.4.1.2011.6.164.1.17.2.1.21
Lower threshold of the environment temperature alarm, can be configured by users.
Value range: -50 to 0,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates th…
Integer32r/w
Constraints:
range: -50-0
.1.3.6.1.4.1.2011.6.164.1.17.2.1.22
The lithium battery discharge depth for Acid Battery running; ,units: %.
Unsigned32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.17.2.1.26
Battery default charge limited threhold , can be configued by users.
Value range: 0.05 to 2,
units: C10,
and the value is accurate to two decimal space (.01).
If the setting value is beyond the current support rang…
Unsigned32r/w
Constraints:
range: 5-200
.1.3.6.1.4.1.2011.6.164.1.17.2.1.27
.1.3.6.1.4.1.2011.6.164.1.18.1 · 1 row entry · 5 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwAcbBaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbBaseTable'
/
hwAcbBaseEntry row .1.3.6.1.4.1.2011.6.164.1.18.1.1
/
Indexes
Column Syntax OID
The battery equip Index.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.18.1.1.1
The battery equip ID no.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.18.1.1.2
The battery equip name.
OctetStringr/w .1.3.6.1.4.1.2011.6.164.1.18.1.1.3
The battery communica address.
Unsigned32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.164.1.18.1.1.4
The Battery software version.
OctetString .1.3.6.1.4.1.2011.6.164.1.18.1.1.5
.1.3.6.1.4.1.2011.6.164.1.18.2 · 1 row entry · 49 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwAcbSampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbSampTable'
/
hwAcbSampEntry row .1.3.6.1.4.1.2011.6.164.1.18.2.1
/
Indexes
Column Syntax OID
voltage of the battery. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 60,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it in…
Unsigned32
Constraints:
range: 0-600
.1.3.6.1.4.1.2011.6.164.1.18.2.1.1
Current of the battery. It indicates the real-time statistics of the battery on the site.
Value range: -200 to 200,
unit: A,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Integer32
Constraints:
range: -2000-2000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.2
Battery charging state, indicates the charging and discharging information about the battery group. It is an enumeration type.
If the enumeration value is 1, it indicates a battery in the Offline state.
If the enumerat…
Enumeration
Enumerated Values:
1offline
2online
3sleep
4disconnect
5charge
6discharge
7standby
255unknown
.1.3.6.1.4.1.2011.6.164.1.18.2.1.3
Soh of the battery. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 100,
unit: %,
and the value is accurate to two decimal place (1).
If the value is 2147483647(0x7FFFFFFF), it indica…
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.18.2.1.4
Capacity of the battery.
Value range: 0 to 10000,
unit: Ah,
and the value is accurate to two decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-100000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.5
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.6
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.7
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.8
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.9
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.10
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.11
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.12
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.13
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.14
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.15
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.16
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.17
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.18
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.19
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.20
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.21
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.22
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.23
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.24
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.25
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.26
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.27
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.28
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.29
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.30
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.31
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.32
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.33
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.34
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.35
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.36
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.37
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.38
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.39
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.40
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.41
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.42
Temperature of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: -100 to 100,
units: centigrade(degC),
and the value is accurate to one decimal place (.1).
If the value is …
Integer32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.2011.6.164.1.18.2.1.43
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.44
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.45
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.46
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.47
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.48
Voltage of the battery cell. It indicates the real-time statistics of the battery on the site.
Value range: 0 to 5,
unit: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), i…
Unsigned32
Constraints:
range: 0-50
.1.3.6.1.4.1.2011.6.164.1.18.2.1.49
.1.3.6.1.4.1.2011.6.164.1.18.3 · 1 row entry · 2 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwAcbSetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAcbSetTable'
/
hwAcbSetEntry row .1.3.6.1.4.1.2011.6.164.1.18.3.1
/
Indexes
Column Syntax OID
Gyro Function Enable,
Restricted use in special areas. If the value of the device is within the range, but the setting fails, the function is not supported.
It is an enumeration value:
If the enumeration value is 1, i…
Enumerationr/w
Enumerated Values:
1disable
2enable
255unknown
.1.3.6.1.4.1.2011.6.164.1.18.3.1.5
Gyro Level of Sensitivity.
Restricted use in special areas. If the value of the device is within the range, but the setting fails, the function is not supported.
It is an enumeration value:
If the enumeration value is 1…
Enumerationr/w
Enumerated Values:
1low
2midium
3high
255unknown
.1.3.6.1.4.1.2011.6.164.1.18.3.1.6
.1.3.6.1.4.1.2011.6.164.1.20.1 · 1 row entry · 4 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteIboxTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteIboxTable'
/
hwSiteIboxEntry row .1.3.6.1.4.1.2011.6.164.1.20.1.1
/
Indexes
Column Syntax OID
ibox table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of ibox
Unsigned32
Constraints:
range: 560-575
.1.3.6.1.4.1.2011.6.164.1.20.1.1.1
ibox device ID. Value range: 029'001 to 029'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 29001-29255
.1.3.6.1.4.1.2011.6.164.1.20.1.1.2
Ibox name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.20.1.1.3
Number of Batteries.
Value range: 0 to 96,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32r/w
Constraints:
range: 0-96
.1.3.6.1.4.1.2011.6.164.1.20.1.1.4
.1.3.6.1.4.1.2011.6.164.1.21.1 · 1 row entry · 6 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteIbatTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteIbatTable'
/
hwSiteIbatEntry row .1.3.6.1.4.1.2011.6.164.1.21.1.1
/
Indexes
Column Syntax OID
ibox table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of ibox
Unsigned32
Constraints:
range: 24576-26112
.1.3.6.1.4.1.2011.6.164.1.21.1.1.1
ibat device ID. Value range: 030'001 to 031'537, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 30001-31537
.1.3.6.1.4.1.2011.6.164.1.21.1.1.2
Ibat name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.21.1.1.3
Ibat temperature. It is a ibat parameter collected in real time.
Value range: -50 to +125,
unit: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that ibox tem…
Integer32
Constraints:
range: -50-125
.1.3.6.1.4.1.2011.6.164.1.21.1.1.4
Ibat Voltage of the ibat. It is an inherent attribute.
Value range: 0 to 100,
Units: V,
and the value is accurate to one decimal place (.1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is in…
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.21.1.1.5
IbatResistance
Value range: 0 to 1000000,
units: (mohm),
and the value is accurate to two decimal place (.01).
Unsigned32
Constraints:
range: 0-100000000
.1.3.6.1.4.1.2011.6.164.1.21.1.1.6
.1.3.6.1.4.1.2011.6.164.1.22.1 · 1 row entry · 3 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteCommExBoardTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteCommExBoardTable'
/
hwSiteCommExBoardEntry row .1.3.6.1.4.1.2011.6.164.1.22.1.1
/
Column Syntax OID
Communication Expansion Board table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of Communication Expansion Board
Unsigned32
Constraints:
range: 1297-1301
.1.3.6.1.4.1.2011.6.164.1.22.1.1.1
Communication Expansion Board device ID. Value range: 032,256 to 033,249, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 32266-33049
.1.3.6.1.4.1.2011.6.164.1.22.1.1.2
Communication Expansion Board name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.22.1.1.3
.1.3.6.1.4.1.2011.6.164.1.23.1 · 1 row entry · 3 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteDGCommExBoardTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteDGCommExBoardTable'
/
hwSiteDGCommExBoardEntry row .1.3.6.1.4.1.2011.6.164.1.23.1.1
/
Column Syntax OID
DG Communication Expansion Board table index,which value is according to the actual subject. Lines of the device list are restricted by the quantity of DG Communication Expansion Board
Unsigned32
Constraints:
range: 2185-2185
.1.3.6.1.4.1.2011.6.164.1.23.1.1.1
DG Communication Expansion Board device ID. Value range: 034'001, in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 34001-34001
.1.3.6.1.4.1.2011.6.164.1.23.1.1.2
DG Communication Expansion Board name, of the character string type, is used to specify battery cabinet. Users can configure it.
Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.23.1.1.3
.1.3.6.1.4.1.2011.6.164.1.27.1 · 1 row entry · 3 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwElockEquipTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwElockEquipTable'
/
hwElockEquipEntry row .1.3.6.1.4.1.2011.6.164.1.27.1.1
/
Column Syntax OID
The elock equip Index.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.27.1.1.1
The elock equip ID no.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.27.1.1.2
The elock equip name.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.27.1.1.3
.1.3.6.1.4.1.2011.6.164.1.28.1 · 1 row entry · 10 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwTemHumEquipTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwTemHumEquipTable'
/
hwTemHumEquipEntry row .1.3.6.1.4.1.2011.6.164.1.28.1.1
/
Column Syntax OID
The tem_hum equip Index.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.28.1.1.1
The tem_hum equip ID no.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.28.1.1.2
The tem_hum equip name.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.28.1.1.3
the environment temperature.
units: centigrade (degC),
and the value is an integer (1).
Integer32
Constraints:
range: -20-80
.1.3.6.1.4.1.2011.6.164.1.28.1.1.4
environment temperature ,
units: %RH,
and the value is an integer (1).
Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.28.1.1.5
Upper threshold of the environment temperature alarm, can be configured by users.
Value range: 25 to 80,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicate…
Integer32r/w
Constraints:
range: 25-80
.1.3.6.1.4.1.2011.6.164.1.28.1.1.6
Lower threshold of the environment temperature alarm, can be configured by users.
Value range: -20 to 20,
units: centigrade (degC),
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indica…
Integer32r/w
Constraints:
range: -20-20
.1.3.6.1.4.1.2011.6.164.1.28.1.1.7
Upper threshold of the environment humility alarm, can be configured by users.
Value range: 0 to 100,
units: %RH,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.28.1.1.8
Lower threshold of the environment humility alarm, can be configured by users.
Value range: 0 to 100,
units: %RH,
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value…
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.2011.6.164.1.28.1.1.9
Device address
And the value is an integer (1).
Unsigned32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.164.1.28.1.1.10
.1.3.6.1.4.1.2011.6.164.1.29.1 · 1 row entry · 5 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwHeaterDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwHeaterDeviceTable'
hwHeaterDeviceEntry row .1.3.6.1.4.1.2011.6.164.1.29.1.1
Column Syntax OID
heater device table index.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.29.1.1.1
heater device equipid.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.29.1.1.2
heater device equipname.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.2011.6.164.1.29.1.1.3
heater start temperature;
Value range:-10 to 15.Unit: degC.
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
note: hwHeaterStartTemperature's set value …
Integer32r/w
Constraints:
range: -10-15
.1.3.6.1.4.1.2011.6.164.1.29.1.1.4
heater stop temperature;
Value range: 5 to 20.Unit: degC.
and the value is an integer (1).
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
note: hwHeaterStartTemperature's set value mus…
Integer32r/w
Constraints:
range: 5-20
.1.3.6.1.4.1.2011.6.164.1.29.1.1.5
.1.3.6.1.4.1.2011.6.164.1.31.1 · 1 row entry · 6 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteDMUSampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteDMUSampTable'
hwSiteDMUSampEntry row .1.3.6.1.4.1.2011.6.164.1.31.1.1
Indexes
Column Syntax OID
DMU table index,
which value range:1 to 256.
Lines of the device list are restricted by the quantity of DMU.
Unsigned32
Constraints:
range: 0-256
.1.3.6.1.4.1.2011.6.164.1.31.1.1.1
DMU device ID.
Value range: 033'001 to 033'255,
in which the first digits indicate the device type and the last three digits indicate the device SN.
Unsigned32
Constraints:
range: 33001-33255
.1.3.6.1.4.1.2011.6.164.1.31.1.1.2
Device name of the DMU module,
character string type, is used to specify the DMU module. Otherwise, the configured character can not be any other languages except English.
OctetString
Constraints:
range: 0-56
.1.3.6.1.4.1.2011.6.164.1.31.1.1.3
DC output voltage: 0 to 100,
units: V,
and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-1000
.1.3.6.1.4.1.2011.6.164.1.31.1.1.4
Load current: 0 to 30000,
units: A,
and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-300000
.1.3.6.1.4.1.2011.6.164.1.31.1.1.5
Total load consumption: 0 to 4294967295,
units: kWh,
and the value is one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
Unsigned32
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.2011.6.164.1.31.1.1.6
.1.3.6.1.4.1.2011.6.164.1.31.2 · 1 row entry · 12 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteDMUSetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteDMUSetTable'
hwSiteDMUSetEntry row .1.3.6.1.4.1.2011.6.164.1.31.2.1
Column Syntax OID
load1 lvd enable :It is an enumeration type:
If the enumeration value is 1, it means to disable the lvd control;
If the enumeration value is 2, it means to enable the lvd control
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2011.6.164.1.31.2.1.1
load1 lvd mode :It is an enumeration type:
If the enumeration value is 1, it means the voltage mode;
If the enumeration value is 2, it means the time mode
Enumerationr/w
Enumerated Values:
1voltagemode
2timemode
.1.3.6.1.4.1.2011.6.164.1.31.2.1.2
Low-voltage power-off voltage of the DMU unit can be configured by users.
Its value range: 36 to 56,
units: V,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicat…
Unsigned32r/w
Constraints:
range: 360-560
.1.3.6.1.4.1.2011.6.164.1.31.2.1.3
Low-voltage power-off recover of the DMU unit can be configured by users.
Its value range: 37.0 to 58.0,
unit: V,
and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indic…
Unsigned32r/w
Constraints:
range: 370-580
.1.3.6.1.4.1.2011.6.164.1.31.2.1.4
Low-voltage power-off disconnected time, It can be configured by users, and its value is an integer (1).
Here, if lvd mode is time mode, value range defines between 0 to 6000,
unit: minutes(min).
If the value is 2147…
Integer32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.2011.6.164.1.31.2.1.5
Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
Value range: 0 to 99,
unit: %,
and the value is accurate to one decimal place (.1). If the value is…
Integer32r/w
Constraints:
range: 0-99
.1.3.6.1.4.1.2011.6.164.1.31.2.1.6
load1 lvd enable :It is an enumeration type:
If the enumeration value is 1, it means to disable the lvd control;
If the enumeration value is 2, it means to enable the lvd control
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2011.6.164.1.31.2.1.7
load1 lvd mode :It is an enumeration type:
If the enumeration value is 1, it means the voltage mode;
If the enumeration value is 2, it means the time mode
Enumerationr/w
Enumerated Values:
1voltagemode
2timemode
.1.3.6.1.4.1.2011.6.164.1.31.2.1.8
Low-voltage power-off voltage of the DMU unit can be configured by users.
Its value range: 36 to 56,
units: V,
and the value is accurate to one decimal space (.1).
If the value is 2147483647(0x7FFFFFFF), it indicat…
Unsigned32r/w
Constraints:
range: 360-560
.1.3.6.1.4.1.2011.6.164.1.31.2.1.9
Low-voltage power-off recover of the DMU unit can be configured by users.
Its value range: 37.0 to 58.0,
unit: V,
and the value is accurate to one decimal space (.1). If the value is 2147483647(0x7FFFFFFF), it indic…
Unsigned32r/w
Constraints:
range: 370-580
.1.3.6.1.4.1.2011.6.164.1.31.2.1.10
Low-voltage power-off disconnected time, It can be configured by users, and its value is an integer (1).
Here, if lvd mode is time mode, value range defines between 0 to 6000,
unit: minutes(min).
If the value is 2147…
Integer32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.2011.6.164.1.31.2.1.11
Power-off unit control the power off, when Remaining capacity percentage of the battery strings is below the calue.
Value range: 0 to 99,
unit: %,
and the value is accurate to one decimal place (.1). If the value is …
Integer32r/w
Constraints:
range: 0-99
.1.3.6.1.4.1.2011.6.164.1.31.2.1.12
.1.3.6.1.4.1.2011.6.164.1.33.1 · 1 row entry · 3 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwAtsSampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwAtsSampTable'
hwAtsSampEntry row .1.3.6.1.4.1.2011.6.164.1.33.1.1
Indexes
Column Syntax OID
Table index of the running ATS modules
Unsigned32
Constraints:
range: 0-256
.1.3.6.1.4.1.2011.6.164.1.33.1.1.1
ATS module ID.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.2011.6.164.1.33.1.1.2
Device name of the ATS module
OctetString
Constraints:
range: 0-56
.1.3.6.1.4.1.2011.6.164.1.33.1.1.3
.1.3.6.1.4.1.2011.6.164.3.1 · 1 row entry · 14 columns
Uses the huawei variant from /opt/observium/mibs/huawei.
Command help
Walk hwSiteCameraTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSiteCameraTable'
/
hwSiteCameraEntry row .1.3.6.1.4.1.2011.6.164.3.1.1
/
Indexes
Column Syntax OID
the camera ip adress.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.1
camera connect port number.
Enumeration
Enumerated Values:
1nim1com1
2nim1com2
3nim2com1
4nim2com2
.1.3.6.1.4.1.2011.6.164.3.1.1.2
You can set the alarm type to obtain the historical picture of the camera-related alarm shooting.
Enumerationr/w
Enumerated Values:
1dooralarm
2smokealarm
3wateralarm
4motiondetectalarm
.1.3.6.1.4.1.2011.6.164.3.1.1.5
Associated alarm picture 1.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.6
Associated alarm picture 2.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.7
Associated alarm picture 3.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.8
Associated alarm picture 4.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.9
Associated alarm picture 5.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.10
Associated alarm picture 6.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.11
Associated alarm picture 7.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.12
Associated alarm picture 8.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.13
Associated alarm picture 9.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.14
Associated alarm picture 10.
OctetString .1.3.6.1.4.1.2011.6.164.3.1.1.15
Additional associated alarm pictures.