hwSetLvdDisconnectedTime

EMAP-MIB · .1.3.6.1.4.1.2011.6.164.1.7.2.1.1.9

Object

column r/w Integer32
Low-voltage power-off disconnected time, It can be configured by users,
value range defines between 5 to 1000, 
unit: minutes(min) ??
and its value is an integer (1). 
Here, if battery manual test is standard mode, 
If the value is 2147483647(0x7FFFFFFF), it indicates that the value is invalid.
NOTE: Only the lvd in time power off mode, this parameter can be configured successfully.

Context

MIB
EMAP-MIB
OID
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.9
Type
column
Access
readwrite
Status
current
Parent
hwLvdBranchEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSetLvdDisconnectedTime'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwSetLvdDisconnectedTime.<hwLvdBranchIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'EMAP-MIB::hwSetLvdDisconnectedTime'

Syntax

Integer32

Values & Constraints

Object Constraints
range: 5-1000