hwLvdBranchOperStatus
EMAP-MIB ·
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.99
Object
column Enumeration
State of the site LVD uint. It is an enumeration type: If the enumeration value is 1, the site LVD uint is in the normal state; If the enumeration value is 2, the power-off uint disconnect for low voltage; If the enumeration value is 3, the power-off uint disconnect bakeground; If the enumeration value is 4, the power-off uint local disconnect manually; If the enumeration value is 5, the power-off uint disconnect for under temperature; If the enumeration value is 6, the power-off uint disconnect for over temperature; If the enumeration value is 7, the ower-off uint disconnect for time; If the enumeration value is 8, the power-off uint disconnect for capacity; If the enumeration value is 9, the power-off uint disconnect for force; If the enumeration value is 10, the power-off uint disconnect for maintenance; If the enumeration value is 254, the power-off uint alarm resume; If the enumeration value is 255, it indicates LVD uint operation status unknown.
Context
- MIB
- EMAP-MIB
- OID
.1.3.6.1.4.1.2011.6.164.1.7.2.1.1.99- Type
- column
- Access
- readonly
- Status
- current
- Parent
- hwLvdBranchEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwLvdBranchOperStatus'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwLvdBranchOperStatus.<hwLvdBranchIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'EMAP-MIB::hwLvdBranchOperStatus'
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | normal |
2 | lowVoltOff |
3 | backgroundOff |
4 | localManualOff |
5 | lowTempOff |
6 | highTempOff |
7 | timeOff |
8 | capacityOff |
9 | forceOff |
10 | maintenanceOff |
254 | alarmResume |
255 | unknown |