hwBattStringOperStatus

EMAP-MIB · .1.3.6.1.4.1.2011.6.164.1.4.4.2.1.99

Object

column Enumeration
State of the site battery string module. It is an enumeration type: 
If the enumeration value is 1, it indicates that the site battery string is in the normal state; 
If the enumeration value is 2, it indicates that the battery string is over upper alarm threshold of temperature; 
If the enumeration value is 3, it indicates that the battery string is under lower alarm threshold of temperature;  
If the enumeration value is 4, it indicates that battery string loop has disconnected;  
If the enumeration value is 5, it indicates that the current of batery is over upper charging threshold;
If the enumeration value is 6, it indicates that the battery string is unbalance;  
If the enumeration value is 7, it indicates that battery string is discharge;  
If the enumeration value is 8, it indicates that battery string is fuseBreak;
If the enumeration value is 254, it indicates battery string alarm resume; 
If the enumeration value is 255, it indicates battery string operation status unknown.

Context

MIB
EMAP-MIB
OID
.1.3.6.1.4.1.2011.6.164.1.4.4.2.1.99
Type
column
Access
readonly
Status
current
Parent
hwBattStringOperEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwBattStringOperStatus'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EMAP-MIB::hwBattStringOperStatus.<hwBattStringOperIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'EMAP-MIB' -M '/opt/observium/mibs/huawei:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'EMAP-MIB::hwBattStringOperStatus'

Syntax

Enumeration

Values & Constraints

Enumerated Values
1normal
2tempHigh
3tempLow
4loopBreak
5overCurrent
6unbalance
7discharge
8fuseBreak
254alarmResume
255unknown