upsSecondsOnBattery
CS141-MIB ·
.1.3.6.1.2.1.33.1.2.2
Object
scalar secondsNonNegativeInteger
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
Context
- MIB
- CS141-MIB
- OID
.1.3.6.1.2.1.33.1.2.2- Type
- scalar
- Access
- readonly
- Status
- current
- Units
- seconds
- Parent
- upsBattery
- Groups
- 3
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'CS141-MIB' -M '/opt/observium/mibs/generex:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CS141-MIB::upsSecondsOnBattery.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'CS141-MIB' -M '/opt/observium/mibs/generex:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'CS141-MIB::upsSecondsOnBattery'
Syntax
secondsNonNegativeInteger
- Source
- NonNegativeInteger
- Base type
Integer32- Display format
d
Type Description
This data type is a non-negative value.
Values & Constraints
Type Constraints
range: 0..2147483647