waterCoolUnitSensorValue
CPQWCRM-MIB ·
.1.3.6.1.4.1.232.167.2.4.5.2.1.5
Object
Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex)
If msg index = 1, 5 or 6
This value represents the actual Server Intake Temperature.
If msg index = 2:
This value represents the bit coded warning condition
Bit 0: Top Fan Module Failed
Bit 1: Middle Fan Module Failed
Bit 2: Bottom Fan Module Failed
Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed
Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed
Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed
Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed
Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed
Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed
Bit 9: Air Temperature Sensor Failed
Bit 10: Top Fan not installed
Bit 11: Middle Fan not installed
Bit 12: Bottom Fan not installed
Bit 13: Waterflow low
Bit 14: Water Unit Temperature Input Out of Range
Bit 15: Water Unit Temperature Output Out of Range
Bit 16: Waterflow Sensor Value Out of Range
Bit 17: Water Valve Failed
Bit 18: Leakdetector Failed
Bit 19: Heat Load Warning
Bit 20: The Condensation Pump has exceeded the max. number of cycles
Bit 21: The Condensation Pump has exceeded the max. Running Time
Bit 27: Dewpoint warning
Bit 28: Humidity sensor failed
Bit 29: Front door access sensor failed
Bit 30: Rear door access sensor failed
If msg index = 3:
This value represents the bit coded alarm condition
Bit 0: Leakage Detected
Bit 1: Comm. Failure IIC
Bit 5: Front and Rear Door Opened
Context
- MIB
- CPQWCRM-MIB
- OID
.1.3.6.1.4.1.232.167.2.4.5.2.1.5- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- cpqWcrmWaterCoolUnitSensorEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQWCRM-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQWCRM-MIB::waterCoolUnitSensorValue'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'CPQWCRM-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQWCRM-MIB::waterCoolUnitSensorValue.<waterCoolUnitSensorIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'CPQWCRM-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'CPQWCRM-MIB::waterCoolUnitSensorValue'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647