upsRecepAutoOffDelay
CPQPOWER-MIB ·
.1.3.6.1.4.1.232.165.3.10.2.1.5
Object
column
mandatory
r/w
Integer32
The delay after going On Battery until the Receptacle is automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 to 30 are valid, but probably innappropriate. The AutoOffDelay can be used to prioritize loads in the event of a prolonged power outage; less critical loads will turn off earlier to extend battery time for the more critical loads. If the utility power is restored before the AutoOff delay counts down to 0 on an outlet, that outlet will not turn Off.
Context
- MIB
- CPQPOWER-MIB
- OID
.1.3.6.1.4.1.232.165.3.10.2.1.5- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- upsRecepEntry
Syntax
Integer32
Values & Constraints
Object Constraints
range: -1-32767