CPQPOWER-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
41
Rows
41
Columns
485

pduIdentTable

table mandatory
.1.3.6.1.4.1.232.165.2.1.2 · 1 row entry · 9 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pduIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pduIdentTable'
The Aggregate Object with number of entries equal to
NumOfPdu and including the PduIdent group.
pduIdentEntry row .1.3.6.1.4.1.232.165.2.1.2.1
The ident table entry containing the name,
model, manufacturer, firmware version, part number, etc.
Indexes
Column Syntax OID
pduIdentIndexmandatory
Index for the PduIdentEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.2.1.2.1.1
pduNamemandatory
The string identify the device.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.2.1.2.1.2
pduModelmandatory
The Device Model.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.2.1.2.1.3
The Device Manufacturer Name (e.g. Hewlett-Packard).
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.2.1.2.1.4
The firmware revision level of the device.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.2.1.2.1.5
pduPartNumbermandatory
The device part number.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.2.1.2.1.6
The device serial number.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.2.1.2.1.7
pduStatusmandatory
The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of
failed(4) indicates the devic…
Enumeration
Enumerated Values:
1other
2ok
3degraded
4failed
.1.3.6.1.4.1.232.165.2.1.2.1.8
This object indicates whether or not the device is controllable.
Enumeration
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.232.165.2.1.2.1.9

pduInputTable

table mandatory
.1.3.6.1.4.1.232.165.2.2.1 · 1 row entry · 3 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pduInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pduInputTable'
The Aggregate Object with number of entries equal to
NumOfPdu and including the PduInput group.
pduInputEntry row .1.3.6.1.4.1.232.165.2.2.1.1
The input table entry containing the voltage and
current for the PDU
Indexes
Column Syntax OID
pduInputIndexmandatory
Index for the PduInputEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.2.2.1.1.1
inputVoltagemandatory
The measured input voltage from the PDU meters in volts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.2.2.1.1.2
inputCurrentmandatory
The measured input current from the PDU meters in hundredths of Amp.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.2.2.1.1.3

pduOutputTable

table mandatory
.1.3.6.1.4.1.232.165.2.3.1 · 1 row entry · 5 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pduOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pduOutputTable'
The Aggregate Object with number of entries equal to
NumOfPdu and including the PduInput group.
pduOutputEntry row .1.3.6.1.4.1.232.165.2.3.1.1
The input table entry containing the name,
heat load, current load, power load, firmware, etc.
Indexes
Column Syntax OID
Index for the PduOutputEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.2.3.1.1.1
pduOutputLoadmandatory
The device output load in percent of rated capacity. A value of -1 will be
returned if the heat load is unable to be measured.
Integer32
Constraints:
range: 0-200
.1.3.6.1.4.1.232.165.2.3.1.1.2
pduOutputHeatmandatory
The total heat load measured on the PDU in BTUs. A value of -1 will be
returned if the heat load is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.2.3.1.1.3
The total power load measured on the PDU in watts. A value of -1 will be
returned if the power load is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.2.3.1.1.4
The number of breakers for the device. This variable indicates the number
of rows in the breakers table.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.2.3.1.1.5

pduOutputBreakerTable

table mandatory
.1.3.6.1.4.1.232.165.2.3.2 · 1 row entry · 5 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pduOutputBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pduOutputBreakerTable'
List of breaker table entries.  The number of entries is given by pduOutputNumBreakers .
pduOutputBreakerEntry row .1.3.6.1.4.1.232.165.2.3.2.1
An entry containing information applicable to an breaker.
Column Syntax OID
breakerIndexmandatory
The breaker identifier.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.2.3.2.1.1
The breaker voltage in volts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.2.3.2.1.2
The breaker current draw in hundredths of Amp.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.2.3.2.1.3
The breaker load in percent.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.2.3.2.1.4
breakerStatusmandatory
This object indicates the status of the breaker. A value of normal(1)
indicates the breaker is operating normally. A value of overloadWarning(2)
indicates the breaker has an overload warning. A value of overloadCriti…
Enumeration
Enumerated Values:
1normal
2overloadWarning
3overloadCritical
4voltageRangeWarning
5voltageRangeCritical
.1.3.6.1.4.1.232.165.2.3.2.1.5

upsInputTable

table mandatory
.1.3.6.1.4.1.232.165.3.3.4 · 1 row entry · 4 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk upsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsInputTable'
The Aggregate Object with number of entries equal to
NumPhases and including the UpsInput group.
upsInputEntry row .1.3.6.1.4.1.232.165.3.3.4.1
The input table entry containing the current, voltage, etc.
Indexes
Column Syntax OID
upsInputPhasemandatory
The number of the phase. Serves as index for input table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.232.165.3.3.4.1.1
The measured input voltage from the UPS meters in volts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.3.3.4.1.2
The measured input current from the UPS meters in amps.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.3.3.4.1.3
upsInputWattsmandatory
The measured input real power in watts. Most UPSs do not report
this XCP data
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.3.3.4.1.4

upsOutputTable

table mandatory
.1.3.6.1.4.1.232.165.3.4.4 · 1 row entry · 4 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk upsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsOutputTable'
The Aggregate Object with number of entries equal to NumPhases
and including the UpsOutput group.
upsOutputEntry row .1.3.6.1.4.1.232.165.3.4.4.1
Output Table Entry containing voltage, current, etc.
Indexes
Column Syntax OID
The number {1..3} of the output phase.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.232.165.3.4.4.1.1
The measured output voltage from the UPS metering in volts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.3.4.4.1.2
The measured UPS output current in amps.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.3.4.4.1.3
The measured real output power in watts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.3.4.4.1.4

upsBypassTable

table mandatory
.1.3.6.1.4.1.232.165.3.5.3 · 1 row entry · 2 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk upsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsBypassTable'
upsBypassEntry row .1.3.6.1.4.1.232.165.3.5.3.1
Entry in the UpsBypassTable.
Indexes
Column Syntax OID
The Bypass Phase, index for the table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.232.165.3.5.3.1.1
The measured UPS bypass voltage in volts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.3.5.3.1.2

upsContactsTable

table mandatory
.1.3.6.1.4.1.232.165.3.6.8 · 1 row entry · 4 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk upsContactsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsContactsTable'
A list of Contact Sensing table entries.  
The number of entries is given by the value of 
UpsEnvNumContacts.
upsContactsTableEntry row .1.3.6.1.4.1.232.165.3.6.8.1
An entry containing information applicable
to a particular Contact input.
Indexes
Column Syntax OID
The Contact identifier; identical to the Contact Number.
Integer32
Constraints:
range: 1-1024
.1.3.6.1.4.1.232.165.3.6.8.1.1
The normal state for this contact. The 'other'
state is the Active state for generating the UpstdContactActiveNotice
trap. If anyChange(3) is selected, then this trap is sent
any time the contact changes to either Ope…
Enumerationr/w
Enumerated Values:
1normallyOpen
2normallyClosed
3anyChange
4notUsed
.1.3.6.1.4.1.232.165.3.6.8.1.2
The current state of the Contact input;
the value is based on the open/closed input state
and the setting for UpsContactType.
When entering the openWithNotice(3) and closedWithNotice(4)
states, no entries added to the…
Enumeration
Enumerated Values:
1open
2closed
3openWithNotice
4closedWithNotice
.1.3.6.1.4.1.232.165.3.6.8.1.3
A label identifying the Contact. This object should be
set by the administrator.
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.3.6.8.1.4

upsRecepTable

table mandatory
.1.3.6.1.4.1.232.165.3.10.2 · 1 row entry · 7 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk upsRecepTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsRecepTable'
The Aggregate Object with number of entries equal to
NumReceptacles and including the UpsRecep group.
upsRecepEntry row .1.3.6.1.4.1.232.165.3.10.2.1
The Recep table entry, etc.
Indexes
Column Syntax OID
upsRecepIndexmandatory
The number of the Receptacle. Serves as index for Receptacle table.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.232.165.3.10.2.1.1
The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown.
Enumeration
Enumerated Values:
1on
2off
3pendingOff
4pendingOn
5unknown
.1.3.6.1.4.1.232.165.3.10.2.1.2
The Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to
turn off after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abor…
Integer32r/w
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.232.165.3.10.2.1.3
The Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to
turn on after the number of seconds (0 is immediately).
Setting it to -1 will cause an attempt to abort …
Integer32r/w
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.232.165.3.10.2.1.4
The delay after going On Battery until the Receptacle is
automatically turned Off. A value of -1 means that this Output should
never be turned Off automatically, but must be turned Off only by command.
Values from 0 …
Integer32r/w
Constraints:
range: -1-32767
.1.3.6.1.4.1.232.165.3.10.2.1.5
Seconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never
be turned On automatically, but only when specifically commanded to d…
Integer32r/w
Constraints:
range: -1-32767
.1.3.6.1.4.1.232.165.3.10.2.1.6
Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.
Unlike UpsRecepOffDelaySecs, which might o…
Integer32r/w
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.3.10.2.1.7

pdrPanelTable

table mandatory
.1.3.6.1.4.1.232.165.4.2.1 · 1 row entry · 16 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdrPanelTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdrPanelTable'
Aggregate Object with number of entries equal to
pdrNumPanels
pdrPanelEntry row .1.3.6.1.4.1.232.165.4.2.1.1
The panel table entry containing all power parameters
for each panel.
Indexes
Column Syntax OID
pdrPanelIndexmandatory
Index for the pdrPanelEntry table.
Integer32
Constraints:
range: 0-10
.1.3.6.1.4.1.232.165.4.2.1.1.1
The present frequency reading for the panel voltage.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.2
pdrPanelPowermandatory
The present power of the panel.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.3
The present rated current of the panel.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.4
The accumulated KWH for this panel since the beginning of this
calendar month or since the last reset.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.5
The accumulated KWH for this panel since the beginning of this
calendar year or since the last reset.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.6
The accumulated KWH for this panel since it was put into service
or since the last reset.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.7
The measured panel output voltage.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.8
The measured panel output voltage.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.9
The measured panel output voltage.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.10
The measured panel output current.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.11
The measured panel output current.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.12
The measured panel output current.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.2.1.1.13
pdrPanelLoadAmandatory
The percentage of load is the ratio of each output
current to the rated output current to the panel.
Integer32
Constraints:
range: 0-200
.1.3.6.1.4.1.232.165.4.2.1.1.14
pdrPanelLoadBmandatory
The percentage of load is the ratio of each output
current to the rated output current to the panel.
Integer32
Constraints:
range: 0-200
.1.3.6.1.4.1.232.165.4.2.1.1.15
pdrPanelLoadCmandatory
The percentage of load is the ratio of each output
current to the rated output current to the panel.
Integer32
Constraints:
range: 0-200
.1.3.6.1.4.1.232.165.4.2.1.1.16

pdrBreakerTable

table mandatory
.1.3.6.1.4.1.232.165.4.3.1 · 1 row entry · 14 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdrBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdrBreakerTable'
List of breaker table entries.  The number of entries 
is given by pdrNumBreakers for this panel.
pdrBreakerEntry row .1.3.6.1.4.1.232.165.4.3.1.1
An entry containing information applicable to a
particular output breaker of a particular panel.
Column Syntax OID
The index of breakers. 42 breakers in each panel,
arranged in odd and even columns
Integer32
Constraints:
range: 0-200
.1.3.6.1.4.1.232.165.4.3.1.1.1
The index of panel that these breakers are installed on.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.2
The position of this breaker in the panel, 1-phase breaker
or n-m breaker for 2-phase or n-m-k breaker for 3-phase.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.3
The number of phase for this particular breaker.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.4
The sequence of this breaker. i.e. 1 for single phase
1,2 for 2-phase or 1,2,3 for 3-phase.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.5
The rated current in Amps for this particular breaker.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.6
The accumulated KWH for this breaker since the beginning of this
calendar month or since the last reset.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.7
The accumulated KWH for this breaker since the beginning of this
calendar year or since the last reset.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.8
The accumulated KWH for this breaker since it was put into service
or since the last reset.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.9
The measured output current for this breaker Current.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.10
The ratio of output current over rated
current for each breaker.
Integer32
Constraints:
range: 0-200
.1.3.6.1.4.1.232.165.4.3.1.1.11
The power for this breaker in Watts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.12
The percentage of Warning set for this breaker.
Integer32
Constraints:
range: 0-200
.1.3.6.1.4.1.232.165.4.3.1.1.13
The percentage of Overload set for this breaker.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.4.3.1.1.14

mpduIdentTable

table mandatory
.1.3.6.1.4.1.232.165.5.1.2 · 1 row entry · 41 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk mpduIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::mpduIdentTable'
Indexed by mpduNumMPDU. So aggregate objects for each entry equal to mpduNumMPDU 
before go to the next entry. i.e if 4 MPDU detected, display 4 indexes, 4 
Manufacturers, 4 Models..., start with 1.
mpduIdentEntry row .1.3.6.1.4.1.232.165.5.1.2.1
The table entry containing the identifications of each MPDU as well
as names of PDR panel, location of MPDU in a Data Center.
Indexes
Column Syntax OID
Index for the MpduIdentEntry table. Start with 1
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.5.1.2.1.1
The Core PDU manufacturer. StringLength=[21]
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.2
mpduModelmandatory
The Core PDU model, marketing name. StringLength=[40].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.3
mpduNamemandatory
The Core PDU name, descriptive name or hostname. StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.4
The Core PDU firmware version(s). StringLength=[12].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.5
The Core PDU hardware version. StringLength=[8].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.6
The Core PDU part number. StringLength=[21].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.7
The PDU external serial number. StringLength=[21].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.8
mpduUUIDmandatory
The PDU's UUID equals PN add SN then canonical conversion. StringLength=[37].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.9
mpduIPmandatory
The PDU's assigned IP. StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.10
The Core PDU MAC address. StringLength=[18].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.11
The Core PDU Control Status: master or slave units.
StringLength=[31].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.12
mpduRegionmandatory
The PDU's Region: NA, Intl, Japan... StringLength=[7].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.13
mpduTypemandatory
The PDU's Type: Delta, Wye, single, Wye+lowline.
StringLength=[24].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.14
The PDU's Power Rating in KVA (Name Plate). Value is presented
in 1/100 of the KVA. i.e. 1750 means 17.50 KVA
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.15
The PDU's Input Current Rating in A (Name Plate)
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.16
mpduInputPlugmandatory
The PDU's Input Plug: IEC60309 516P6,NEMA L15-30P...
StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.17
The number of breakers used in each MPDU (6 by default).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.18
mpduNumOutletmandatory
The number of outlets of each MPDU (6 by default).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.19
mpduUHeightmandatory
The MPDU U Height 1U or 2 U (1U by default).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.20
Status of Core PDU in paired or not: Stand-alone or Redundant.
StringLength=[12].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.21
total number of detected Smart Sticks connecting to each PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.22
mpduPanelNamemandatory
Name of Panel that was entered by customer in GUI.
StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.23
Name of breakers or Panel Position entered by customer in GUI.
StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.24
Breaker rating of the PDR Panel.
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.25
it would be A, B, Red, or White...
StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.26
mpduFloorNamemandatory
Name of building floor entered by customer in GUI.
StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.27
mpduRoomNamemandatory
Name of the room entered by customer in GUI. StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.28
mpduRowmandatory
Data Center Row entered by customer in GUI.
StringLength=[11].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.29
Position in Row entered by customer in GUI. Null will be returned
if not detected. StringLength=[11].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.30
mpduRackNamemandatory
Name of the Rack entered by customer in GUI. Null will be returned
if not detected. StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.31
Rack Type (22U, 42U, 50U...). Null will be returned if not detected.
StringLength=[3].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.32
mpduRackIDmandatory
An unique ID to identify a rack, i.e. Rack SN. Null will be returned if
not detected. StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.33
mpduUPositionmandatory
PDU Rack bottom U Start position, core U position. Null will be returned if not detected.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.34
UUID of the PDU paired with this one. Null will be returned if not detected.
StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.35
IP address of the PDU paired with this one. Null will be returned if not detected.
StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.36
0=Left 0U side area or rack frame, 1= Right 0U side area or rack frame, 2= front RETMA rail,
3=back RETMA rail) - spatial location. A value of -1 will be returned if not detected.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.37
The total power for the whole iPDU in Watts. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.38
The total power for the whole iPDU in VA. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.39
The whole iPDU's load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value
of -1 will be returned if the current is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.1.2.1.40
value is either America(208V), Japan(202V) or blank for International Model
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.1.2.1.41

mpduOutputTable

table mandatory
.1.3.6.1.4.1.232.165.5.2.1 · 1 row entry · 13 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk mpduOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::mpduOutputTable'
Indexed by mpduNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU 
multiplies mpduNumOutlet) before go to the next entry. i.e if 4 MPDU detected, 
display 6x4 indexes, 6x4 OutputStatus, 6x4 OutputBreakerRating...start with 1.
mpduOutputEntry row .1.3.6.1.4.1.232.165.5.2.1.1
The output table entry containing the voltage, current, PF,
percent load, VA, Watts for the Modular PDU.
Column Syntax OID
Index for the MpduOutputEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.5.2.1.1.1
The overall status of the device: off, on, problem. StringLength=[7].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.2.1.1.2
The rating of each MPDU Output in Ampere.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.3
A smart cord device detected: False, True. StringLength=[5].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.2.1.1.4
The MPDU's each output load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value
of -1 will be returned if the current is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.5
The measured output voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value
of -1 will be returned if the voltage is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.6
The measured output current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value
of -1 will be returned if the current is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.7
The total VA load (VI) measured on the PDU in VA. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.8
The total power load measured on the PDU in Watts. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.9
The power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable
to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.10
Report the User-set threshhold limit for Warning in percentage
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.11
Report the User-set threshhold limit for Critical in percentage
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.12
Support Billing Grade Energy Metering in Watt-Hour. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.2.1.1.13

mpduDeviceIdentTable

table mandatory
.1.3.6.1.4.1.232.165.5.3.1 · 1 row entry · 20 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk mpduDeviceIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::mpduDeviceIdentTable'
Indexed by mpduNumOutlet. So aggregate objects for each entry equal 
to (mpduNumMPDU multiplies mpduNumOutlet) before go to the next entry. 
i.e if 4 MPDU detected, display 6x4 indexes, 6x4 mpduDeviceStatus, 6x4 
DeviceUIDStatus...start with 1.
mpduDeviceIdentEntry row .1.3.6.1.4.1.232.165.5.3.1.1
The ident table entry containing the name, model,
manufacturer, firmware version, part number... for
each smart device, null value for unknown device.
Column Syntax OID
Index is based on the total number of Smart Extension Bars plus
smart devices (with smart power cord i.e. blades) detected.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.5.3.1.1.1
The overall status of the device: off, on, problem. StringLength=[8].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.2
The overall status of the device UID: off, on, blink. StringLength=[8].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.3
The number of outlets of detected the device. This variable
indicates the number of rows in the breakers table. Default is 5
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.3.1.1.4
The Unit height of ext bar or device. Some device supports non-integer.
Present value x100, when read back, divided by 100 to get 2 decimal points.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.3.1.1.5
The device's Power Rating in VA. Null will be returned if not detected.
StringLength=[8].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.6
The Device Manufacturer Name (e.g. Hewlett-Packard).
Null will be returned if not detected. StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.7
The Device's Type: Ext Bar, server, or network device...
StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.8
The Device Model is Managed or Non-managed Ext Bar.
Null will be returned if not detected. StringLength=[24].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.9
The string identify the Device. i.e. 'BAR#1' (descriptive name)
Null will be returned if not detected. StringLength=[32].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.10
The firmware revision level of Sm Ext Bar. Null will be returned if
not detected. StringLength=[8].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.11
The hardware version of Sm Ext Bar. Null will be returned if not
detected. StringLength=[8].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.12
The device's part number. Null will be returned if not detected.
StringLength=[21].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.13
The device's serial number. Null will be returned if not detected.
StringLength=[21].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.14
The device's UUID. Null will be returned if not detected.
StringLength=[37].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.15
mpduDeviceIPmandatory
The device's IP Address. Null will be returned if not detected.
StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.16
mpduDeviceMACmandatory
The device mgmt processor MAC Address. Null will be returned if
not detected. StringLength=[18].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.3.1.1.17
Device power supply logical slot number.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.3.1.1.18
Device U start position.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.3.1.1.19
Read device detection threshold between 10 and 50mA.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.3.1.1.20

mpduSmExtBarOutletTable

table mandatory
.1.3.6.1.4.1.232.165.5.4.1 · 1 row entry · 20 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk mpduSmExtBarOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::mpduSmExtBarOutletTable'
Indexed by mpduDeviceNumOutlet. So aggregate objects for each entry equal to 
(mpduNumMPDU multiplies mpduNumOutlet multiplies mpduDeviceNumOutlet) before 
go to the next entry. i.e if 4 MPDU detected, display 5x6x4 indexes, 5x6x4
mpduSmExtBarOutletStatus, 5x6x4 mpduSmExtBarOutletUIDStatus...start with 1.
mpduSmExtBarOutletEntry row .1.3.6.1.4.1.232.165.5.4.1.1
Entries contain status, measurements for each outlet (no PowerVA)
Display null if it can't be measured or no device detected.
Column Syntax OID
The Index of Smart Extension Bar.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.5.4.1.1.1
The overall status of the Smart Extension Bar's outlet: off, on, problem...
StringLength=[3].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.4.1.1.2
The overall status of the Smart Extension Bar's UID: off, on, blink...
StringLength=[8].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.4.1.1.3
Sm Ext Bar Outlet's Rating in Amp. A value of -1 will be returned
if the stick is unable to detect. StringLength=[8].
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.4
The SM Ext Bar voltage in volts. Value is presented 1/10 of the Volt
i.e. 2098 means 209.8 V. A value of -1 will be returned if the voltage is unable
to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.5
The SM Ext Bar current draw in Amps. Value is presented in 1/100 of the Ampere
i.e. 127 means 1.27 A. A value of -1 will be returned if the current is unable
to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.6
The Sm Ext Bar's Power measured in Watts. A value of -1 will be returned if the
power is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.7
The outlet's power factor in 0.01 unit. It is presented in 1/100 of the unit.
i.e. 98 means 0.98. A value of -1 will be returned if the voltage is unable
to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.8
The Device (Blade/Server/Storage) Name that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[50].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.4.1.1.9
The Device (Blade/Server/Storage) UUID that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[37].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.4.1.1.10
The Device (Blade/Server/Storage) Model that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[40].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.4.1.1.11
The Device (Blade/Server/Storage) IP of iLO that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.4.1.1.12
Boolean values of 0 or 1. 1 means this Sm Ext Bar Outlet is able to get information
from a blade with smart power supply (auto discovery is enabled)...
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.13
The Device (Blade/Server/Storage) MAC address that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[18].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.4.1.1.14
The Device (Blade/Server/Storage) Serial Number that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[21].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.5.4.1.1.15
The Device (Blade/Server/Storage) Power Supply' Slot Number that connects to this
Sm Ext Bar Outlet. A value of -1 will be returned if not detected.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.16
Device U start position. A value of -1 will be returned if not detected.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.17
Device U height. Enter -1 if not detected. Some device supports non-integer.
Present value x100, when read back, divided by 100 to get 2 decimal points.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.18
0=Left 0U side area or rack frame, 1= Right 0U side area or rack frame, 2= front RETMA rail,
3=back RETMA rail) - spatial location. A value of -1 will be returned if not detected.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.19
The Sm Ext Bar's Power measured in Watt-Hour support Billing Grade Energy Metering.
A value of -1 will be returned if the power is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.5.4.1.1.20

oupsInputTable

table mandatory
.1.3.6.1.4.1.232.165.6.3.4 · 1 row entry · 4 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk oupsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::oupsInputTable'
Aggregate Object with number of entries equal to
NumPhases and including the UpsInput group.
oupsInputEntry row .1.3.6.1.4.1.232.165.6.3.4.1
The input table entry containing the current, voltage, etc.
Indexes
Column Syntax OID
The number of the phase. Serves as index for input table.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.232.165.6.3.4.1.1
The measured input voltage from the UPS meters in volts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.6.3.4.1.2
The measured input current from the UPS meters in amps.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.6.3.4.1.3
The measured input power in watts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.6.3.4.1.4

oupsOutputTable

table mandatory
.1.3.6.1.4.1.232.165.6.4.4 · 1 row entry · 5 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk oupsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::oupsOutputTable'
The Aggregate Object with number of entries equal to NumPhases
and including the UpsOutput group.
oupsOutputEntry row .1.3.6.1.4.1.232.165.6.4.4.1
Output Table Entry containing voltage, current, etc.
Indexes
Column Syntax OID
The number {1..3} of the output phase.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.232.165.6.4.4.1.1
The measured output voltage from the UPS metering in volts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.6.4.4.1.2
The measured UPS output current in amps.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.6.4.4.1.3
The measured real output power in watts.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.6.4.4.1.4
The UPS output load per phase in percentage of rated capacity.
Integer32
Constraints:
range: 0-200
.1.3.6.1.4.1.232.165.6.4.4.1.5

pdu2IdentTable

table mandatory
.1.3.6.1.4.1.232.165.7.1.2 · 1 row entry · 12 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2IdentTable'
Aggregate Object with number of entries equal to pdu2NumberPDU .
pdu2IdentEntry row .1.3.6.1.4.1.232.165.7.1.2.1
The ident table entry containing the name, model, manufacturer,
firmware version, part number, etc.
Indexes
Column Syntax OID
Index for the Pdu2IdentEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.7.1.2.1.1
pdu2Namemandatory
The string identify the device in daisy chain. Example PDU A.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.2
pdu2Modelmandatory
The Device Model.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.3
The Device Manufacturer Name (e.g. Hewlett-Packard).
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.4
The firmware revision level of the device.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.5
The device part number. Example AF400A.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.6
The device serial number, 10- or 16-digit.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.7
pdu2Statusmandatory
The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of
failed(4) indicates the devic…
Enumeration
Enumerated Values:
1other
2ok
3degraded
4failed
.1.3.6.1.4.1.232.165.7.1.2.1.8
This object indicates whether or not the device is controllable.
Enumeration
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.232.165.7.1.2.1.9
The number of input phase on this pdu 1,2,3.
Integer32
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.10
The number of groups (breakers) on this pdu.
Integer32
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.11
The number of outlets in this PDU.
Integer32
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.1.2.1.12

pdu2InputTable

table mandatory
.1.3.6.1.4.1.232.165.7.2.1 · 1 row entry · 9 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2InputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2InputTable'
Aggregate Object with number of entries equal to pdu2NumberPDU .
pdu2InputEntry row .1.3.6.1.4.1.232.165.7.2.1.1
The ident table entry containing the VA, Watts, WH, etc.
Indexes
Column Syntax OID
pdu2InputTypemandatory
Type of input - single phase, split phase, three phase delta, or three
phase wye.
Enumeration
Enumerated Values:
1singlePhase
2splitPhase
3threePhaseDelta
4threePhaseWye
.1.3.6.1.4.1.232.165.7.2.1.1.1
The measured input frequency from the PDU meters in tenths of Hz.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.7.2.1.1.2
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
Enumeration
Enumerated Values:
1good
2outOfRange
.1.3.6.1.4.1.232.165.7.2.1.1.3
A total input VA of all phases. Units are VA. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.1.1.4
A total input Watts of all phases. Units are Watts. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.1.1.5
A total input Watt-Hour value for all phases. Units are WH. This value can be reset to 0
using GUI. In that case, the pdu2InputPowerWattHourTimer will be reset as well
A negative value indicates that this object is …
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.1.1.6
A Timestamp of when the Total Input WH was last reset.
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.232.165.7.2.1.1.7
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920.
A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.1.1.8
An input VAR value. Units are VAR. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.1.1.9

pdu2InputPhaseTable

table mandatory
.1.3.6.1.4.1.232.165.7.2.2 · 1 row entry · 25 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2InputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2InputPhaseTable'
Aggregate Object with number of entries equal to number of PDUs (pdu2NumberPDU) and
number of input phase (pdu2InputPhaseCount).
pdu2InputPhaseEntry row .1.3.6.1.4.1.232.165.7.2.2.1
The input table entry containing the voltage, current, frequency, power for each phase.
Entries are given with number of pdu and number of input phase 1, 2, or 3.
Column Syntax OID
Index for the Pdu2InputEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.7.2.2.1.1
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, or phase 3 to phase 1.
Enumeration
Enumerated Values:
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
.1.3.6.1.4.1.232.165.7.2.2.1.2
An input voltage measurement value. Units are millivolts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.3
Status of the measured input voltage relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.7.2.2.1.4
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.7.2.2.1.5
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.7.2.2.1.6
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.7.2.2.1.7
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.7.2.2.1.8
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3.
Enumeration
Enumerated Values:
1singlePhase
2neutral
3phase1
4phase2
5phase3
.1.3.6.1.4.1.232.165.7.2.2.1.9
Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are milliamps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.10
An input current measurement value. Units are milliamps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.11
Status of the measured input current relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.7.2.2.1.12
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.2.2.1.13
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.2.2.1.14
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.2.2.1.15
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.2.2.1.16
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.17
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.18
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3.
Enumeration
Enumerated Values:
1singlePhase
2neutral
3phase1
4phase2
5phase3
.1.3.6.1.4.1.232.165.7.2.2.1.19
An input VA value. Units are VA. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.20
An input Watts value. Units are Watts. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.21
A Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0
using GUI. In that case, the pdu2InputPhasePowerWattHourTimer will be reset as well
A negative value indicates that this object is…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.22
Timestamp of when input Watt-hours (inputWh) was last reset.
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.232.165.7.2.2.1.23
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.24
An input VAR value. Units are VAR. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.2.2.1.25

pdu2GroupTable

table mandatory
.1.3.6.1.4.1.232.165.7.3.1 · 1 row entry · 27 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2GroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2GroupTable'
Aggregate Object with number of entries equal to number of PDUs
and number of breakers (pdu2GroupCount).
pdu2GroupEntry row .1.3.6.1.4.1.232.165.7.3.1.1
The input table entry containing the name, voltages, currents, power, etc.
Column Syntax OID
Index for the Pdu2GroupEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.7.3.1.1.1
pdu2GroupNamemandatory
A descriptive name for the group.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.7.3.1.1.2
pdu2GroupTypemandatory
The type of the group. (5) has no breaker
Enumeration
Enumerated Values:
2breaker1pole
3breaker2pole
4breaker3pole
5outletSection
.1.3.6.1.4.1.232.165.7.3.1.1.3
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, or phase 3 to phase 1.
Enumeration
Enumerated Values:
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
.1.3.6.1.4.1.232.165.7.3.1.1.4
Units are millivolts.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.5
Status of the measured group voltage relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.7.3.1.1.6
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.7.3.1.1.7
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.7.3.1.1.8
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.7.3.1.1.9
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.7.3.1.1.10
Rated current capacity of the group. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown (it
will always be unknown for custom groups).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.11
A group current measurement value. Units are milliamps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.12
Status of the measured group current relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.7.3.1.1.13
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.3.1.1.14
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.3.1.1.15
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.3.1.1.16
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.3.1.1.17
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.18
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.19
A group VA value. Units are VA. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.20
A group Watts value. Units are Watts. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.21
A Watt-Hour value for each section. Units are WH. This value can be reset to 0
using GUI. In that case, the pdu2GroupPowerWattHourTimer will be reset as well.
A negative value indicates that this object is not ava…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.22
Timestamp of when group Watt-hours (groupWh) was last reset.
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.232.165.7.3.1.1.23
A group PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920.
A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.24
A group VAR value. Units are VAR. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.3.1.1.25
The number of outlets in each group (breaker).
Integer32
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.7.3.1.1.26
Only applicable to groups with breaker. Indicates whether a breaker is turned
off or on.
Enumeration
Enumerated Values:
1notApplicable
2breakerOn
3breakerOff
.1.3.6.1.4.1.232.165.7.3.1.1.27

pdu2EnvProbeTable

table mandatory
.1.3.6.1.4.1.232.165.7.4.1 · 1 row entry · 4 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2EnvProbeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2EnvProbeTable'
A list of environment probe (1 per PDU) for temperature, humidity, and contacts.  
The number of entries is given by number of PDUs in daisy chain.
pdu2EnvProbeEntry row .1.3.6.1.4.1.232.165.7.4.1.1
Aggregate entries equal to number of PDUs.
Indexes
Column Syntax OID
Scale used to return temperature objects.
Enumeration
Enumerated Values:
1celsius
2fahrenheit
.1.3.6.1.4.1.232.165.7.4.1.1.1
Max number of temperature measurements (1 per probe).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.4.1.1.2
Max number of humidity measurements (1 per probe).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.4.1.1.3
Max number of contact sensors (1 per probe).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.4.1.1.4

pdu2TemperatureTable

table mandatory
.1.3.6.1.4.1.232.165.7.4.2 · 1 row entry · 9 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2TemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2TemperatureTable'
A list of temperature probe measurements.  The number of entries are
given by number of pdu and pdu2TemperatureCount.
pdu2TemperatureEntry row .1.3.6.1.4.1.232.165.7.4.2.1
An entry for a temperature measurement.
Column Syntax OID
A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.232.165.7.4.2.1.1
A descriptive name for the temperature probe.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.7.4.2.1.2
Indicates whether a probe is connected or not.
Enumeration
Enumerated Values:
1disconnected
2connected
3bad
.1.3.6.1.4.1.232.165.7.4.2.1.3
Units are in tenths of a degree (either Fahrenheit or Celsius).
Divide by ten to get degrees.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.4.2.1.4
Status of the measured temperature relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.7.4.2.1.5
Lower warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-150000
.1.3.6.1.4.1.232.165.7.4.2.1.6
Lower critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-150000
.1.3.6.1.4.1.232.165.7.4.2.1.7
Upper warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-150000
.1.3.6.1.4.1.232.165.7.4.2.1.8
Upper critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-150000
.1.3.6.1.4.1.232.165.7.4.2.1.9

pdu2HumidityTable

table mandatory
.1.3.6.1.4.1.232.165.7.4.3 · 1 row entry · 9 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2HumidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2HumidityTable'
A list of humidity probe measurements.  The number of entries are
given by number of pdu and pdu2HumidityCount.
pdu2HumidityEntry row .1.3.6.1.4.1.232.165.7.4.3.1
An entry for a humidity measurement.
Column Syntax OID
A unique value for each humidity probe measurement. Its value
ranges from 1 to pdu2HumidityCount per pdu.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.232.165.7.4.3.1.1
A descriptive name for the humidity probe.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.7.4.3.1.2
Indicates whether a probe is connected or not.
Enumeration
Enumerated Values:
1disconnected
2connected
3bad
.1.3.6.1.4.1.232.165.7.4.3.1.3
Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.4.3.1.4
Status of the measured humidity relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.7.4.3.1.5
Lower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-1000
.1.3.6.1.4.1.232.165.7.4.3.1.6
Lower critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-1000
.1.3.6.1.4.1.232.165.7.4.3.1.7
Upper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-1000
.1.3.6.1.4.1.232.165.7.4.3.1.8
Upper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-1000
.1.3.6.1.4.1.232.165.7.4.3.1.9

pdu2ContactTable

table mandatory
.1.3.6.1.4.1.232.165.7.4.4 · 1 row entry · 4 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2ContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2ContactTable'
A list of contact sensors.  The number of entries are
given by number of pdu and pdu2ContactCount.
pdu2ContactEntry row .1.3.6.1.4.1.232.165.7.4.4.1
An entry for a contact sensor
Column Syntax OID
A unique value for each contact sensor. Its value ranges from 1 to
contactCount.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.232.165.7.4.4.1.1
A descriptive name for the contact sensor.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.7.4.4.1.2
Indicates whether a probe is connected or not.
Will not be returned if the contact sensor is internal to the ePDU,
in that case only contactState should be read.
Enumeration
Enumerated Values:
1disconnected
2connected
3bad
.1.3.6.1.4.1.232.165.7.4.4.1.3
The state of the contact sensor.
Enumeration
Enumerated Values:
1contactOpen
2contactClosed
3contactBad
.1.3.6.1.4.1.232.165.7.4.4.1.4

pdu2OutletTable

table mandatory
.1.3.6.1.4.1.232.165.7.5.1 · 1 row entry · 18 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2OutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2OutletTable'
Aggregate Object with number of entries equal to Number of PDU (pdu2IdentIndex)
and Number of outlet per PDU (pdu2OutletIndex).
pdu2OutletEntry row .1.3.6.1.4.1.232.165.7.5.1.1
The Outlet table entry containing the type, voltage, current etc.
Column Syntax OID
Index for each outlet, value from 1 to the number of outlets per PDU.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.7.5.1.1.1
A descriptive name for the outlet.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.7.5.1.1.2
Type of this outlet - C13, C19.
Enumeration
Enumerated Values:
1iecC13
2iecC19
10uk
11french
12schuko
20nema515
21nema51520
22nema520
23nemaL520
24nemaL530
25nema615
26nema620
27nemaL620
28nemaL630
29nemaL715
30rf203p277
.1.3.6.1.4.1.232.165.7.5.1.1.3
Rated current capacity of this outlet. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.4
A outlet current measurement value. Units are milliamps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.5
Status of the measured outlet current relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.7.5.1.1.6
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.5.1.1.7
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.5.1.1.8
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.5.1.1.9
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.7.5.1.1.10
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.11
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.12
pdu2OutletVAmandatory
A outlet VA value. Units are VA. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.13
A outlet Watts value. Units are Watts. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.14
pdu2OutletWhmandatory
A Watt-Hour value for each outlet. Units are WH.
This object is writable so that it can be reset to 0. When it is
written to, the pdu2OutletWhTimer will be reset updated as well
A negative value indicates that thi…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.15
Timestamp (date and time) of outlet Watt-hours was last reset.
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.232.165.7.5.1.1.16
An outlet PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.17
pdu2OutletVARmandatory
An outlet VAR value. Units are VAR. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.7.5.1.1.18

pdu2OutletControlTable

table mandatory
.1.3.6.1.4.1.232.165.7.5.2 · 1 row entry · 9 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu2OutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2OutletControlTable'
Aggregate Object with number of entries equal to Number of PDU (pdu2IdentIndex) 
and Number of outlets per PDU (pdu2OutletIndex).
pdu2OutletControlEntry row .1.3.6.1.4.1.232.165.7.5.2.1
The Outlet table entry containing the type, voltage, current etc.
Column Syntax OID
current state of a control outlet.
Enumeration
Enumerated Values:
1off
2on
3pendingOff
4pendingOn
.1.3.6.1.4.1.232.165.7.5.2.1.1
When write, once issued, the outlet will turn Off immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet Off command
When read, returns -1 if no command is pending, or the curr…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.7.5.2.1.2
When write, once issued, the outlet will turn On immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet On command
When read, returns -1 if no command is pending, or the curren…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.7.5.2.1.3
When write, for outlets that are On prior to this Reboot command, they will
switch Off immediately when the command is issued, remain Off for
outletControlRebootOffTime seconds, and then turn back On.
For outlets tha…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.7.5.2.1.4
Determines the outlet state when power is applied to the unit.
1 : not restart at device startup
2 : should sequence back ON in line with outletControlSequenceTime
3 : should take the state the outlet had when power was…
Enumerationr/w
Enumerated Values:
1off
2on
3lastState
.1.3.6.1.4.1.232.165.7.5.2.1.5
Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on
delay. Set to -1 to exclude this outlet from Global Sequence …
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.7.5.2.1.6
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.7.5.2.1.7
Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled
2 : control On/Off disabled.
Enumerationr/w
Enumerated Values:
1switchable
2notSwitchable
.1.3.6.1.4.1.232.165.7.5.2.1.8
Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first
then write it to the command pdu2OutletControlOf…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.7.5.2.1.9

hpduIdentTable

table mandatory
.1.3.6.1.4.1.232.165.9.1.2 · 1 row entry · 17 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk hpduIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::hpduIdentTable'
Indexed by 1 Hpdu unit.
hpduIdentEntry row .1.3.6.1.4.1.232.165.9.1.2.1
The table entry containing the identifications of HPDU
Indexes
Column Syntax OID
Index for the MpduIdentEntry table. Start with 1
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.9.1.2.1.1
The Core PDU manufacturer. StringLength=[21]
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.2
hpduModelmandatory
The Core PDU model, marketing name. StringLength=[40].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.3
hpduNamemandatory
The Core PDU name, descriptive name or hostname. StringLength=[16].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.4
The Core PDU firmware version(s). StringLength=[12].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.5
The Core PDU hardware version. StringLength=[8].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.6
The Core PDU part number. StringLength=[21].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.7
The PDU external serial number. StringLength=[21].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.8
hpduUUIDmandatory
The PDU's UUID equals PN add SN, canonical conversion. StringLength=[37].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.9
hpduTypemandatory
The PDU's Type: Delta, Wye, single, Wye+lowline.
StringLength=[24].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.10
The PDU's Power Rating in KVA (Name Plate). Value is presented
in 1/100 of the KVA. i.e. 1750 means 17.50 KVA
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.11
The PDU's Input Current Rating in A (Name Plate)
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.12
value is either America(208V), Japan(202V) or blank for International Model
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.13
The number of outlets with breakers of each hpdu.
Integer32
Constraints:
range: 0-10
.1.3.6.1.4.1.232.165.9.1.2.1.14
The number of measured outlets (with CT, VT) of each hpdu.
Integer32
Constraints:
range: 0-10
.1.3.6.1.4.1.232.165.9.1.2.1.15
hpduFanStatusmandatory
Report fan status: OK or FAIL
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.1.2.1.16
The internal temperature in Celcius. Value is presented in 1/10 of a degree i.e. 251 is 25.1. A value
of -1 will be returned if the temperature is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.1.2.1.17

hpduInputTable

table mandatory
.1.3.6.1.4.1.232.165.9.2.1 · 1 row entry · 13 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk hpduInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::hpduInputTable'
Indexed by hpduNumPhase.
hpduInputEntry row .1.3.6.1.4.1.232.165.9.2.1.1
The Input table entry containing the voltage, current, PF,
percent load, VA, Watts for the HPDU.
Indexes
Column Syntax OID
Index for the hpduInputEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.9.2.1.1.1
The overall status of the Input: off, on, problem. StringLength=[7].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.2.1.1.2
The rating of each hpdu Input in Ampere.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.3
The measured Input voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value
of -1 will be returned if the voltage is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.4
The measured Input current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value
of -1 will be returned if the current is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.5
The total Input Power measured in VA. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.6
The total Input power measured in Watts. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.7
The Input power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable
to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.8
Report the User-setting Input threshhold limit for Warning in percentage
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.9
Report the User-setting Input threshhold limit for Critical in percentage
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.10
Support Billing Grade Energy Metering in Watt-Hour. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.11
Display the date and time that starts to accumulate the per Load segment energy in WH.
Date and Time can be set by user on GUI.
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.2.1.1.12
Total hours of collecting measurement data. A value
of -1 will be returned if the value is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.2.1.1.13

hpduOutletTable

table mandatory
.1.3.6.1.4.1.232.165.9.3.1 · 1 row entry · 14 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk hpduOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::hpduOutletTable'
Indexed by hpduNumMonitoredOutlet and hpduNumPhase . So aggregate objects for each entry 
equal to (hpduNumMonitoredOutlet x hpduNumPhase). Start with 1.
hpduOutletEntry row .1.3.6.1.4.1.232.165.9.3.1.1
The Outlet table entry containing the voltage, current, PF,
percent load, VA, Watts for the Modular PDU.
Column Syntax OID
Index for the hpduOutletEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.9.3.1.1.1
The overall status of the breaker: off, on, problem. StringLength=[7].
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.3.1.1.2
The rating of each hpdu Outlet in Ampere.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.3
The hpdu's each Outlet load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value
of -1 will be returned if the current is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.4
The measured Outlet voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value
of -1 will be returned if the voltage is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.5
The measured Outlet current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value
of -1 will be returned if the current is unable to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.6
The total VA load (VI) measured on the PDU in VA. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.7
The total power load measured on the PDU in Watts. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.8
The power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable
to be measured.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.9
Report the User-set threshhold limit for Warning in percentage
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.10
Report the User-set threshhold limit for Critical in percentage
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.11
Support Billing Grade Energy Metering in Watt-Hour. A value
of -1 will be returned if the power is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.12
Display the date and time that starts to accumulate the per Load segment energy in WH.
Date and Time can be set by user on GUI.
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.9.3.1.1.13
Total hours of collecting measurement data. A value
of -1 will be returned if the value is unable to be calculated.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.9.3.1.1.14

pdu3IdentTable

table mandatory
.1.3.6.1.4.1.232.165.11.1.2 · 1 row entry · 16 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3IdentTable'
Aggregate Object with number of entries equal to pdu3NumberPDU .
pdu3IdentEntry row .1.3.6.1.4.1.232.165.11.1.2.1
The ident table entry containing the name, model, manufacturer,
firmware version, part number, etc.
Indexes
Column Syntax OID
Index for the Pdu3IdentEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.11.1.2.1.1
pdu3Namemandatory
The string identify the device in daisy chain. Example PDU A.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.2
pdu3Modelmandatory
The Device Model.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.3
The Device Manufacturer Name (e.g. Hewlett-Packard).
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.4
The firmware revision level of the device.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.5
Timestamp of when the PDU firmware was last updated
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.11.1.2.1.6
The device part number. Example AF400A.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.7
The device serial number, 10- or 16-digit.
OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.8
pdu3Statusmandatory
The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of
failed(4) indicates the devic…
Enumeration
Enumerated Values:
1other
2ok
3degraded
4failed
.1.3.6.1.4.1.232.165.11.1.2.1.9
This object indicates whether or not the device is controllable.
Enumeration
Enumerated Values:
1yes
2no
.1.3.6.1.4.1.232.165.11.1.2.1.10
The number of input phase on this pdu 1,2,3.
Integer32
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.11
The number of groups (breakers) on this pdu.
Integer32
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.12
The number of outlets in this PDU.
Integer32
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.1.2.1.13
The assigned MAC address for this PDU.
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.11.1.2.1.14
The current IPv4 Address.
A value of 0.0.0.0 indicates an error or an unset option.
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.11.1.2.1.15
The current IPv6 Address.
A vale of 0.0.0.0.0.0 indicates an error or an unset option.
RFC1213-MIBDisplayString .1.3.6.1.4.1.232.165.11.1.2.1.16

pdu3ConfigTable

table mandatory
.1.3.6.1.4.1.232.165.11.1.3 · 1 row entry · 11 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3ConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3ConfigTable'
Aggregate Object with number of entries equal to pdu3NumberPDU .
pdu3ConfigEntry row .1.3.6.1.4.1.232.165.11.1.3.1
Read Configuration data from the PDU being queried.
Indexes
Column Syntax OID
The index of PDU configuration entry.
Integer32
Constraints:
range: 0-20
.1.3.6.1.4.1.232.165.11.1.3.1.1
pdu3ConfigSshmandatory
Setting this OID to off(0) will disable the SSH conneciton.
Setting this OID to on(1) will enable the SSH connection.
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.232.165.11.1.3.1.2
Setting this OID to off(0) will disable the FTPS connection.
Setting this OID to on(1) will enable the FTPS connection.
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.232.165.11.1.3.1.3
Setting this OID to off(0) will disable the HTTP connection.
Setting this OID to on(1) will enable the HTTP connection.
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.232.165.11.1.3.1.4
Setting this OID to off(0) will disable the HTTPS connection.
Setting this OID to on(1) will enable the HTTPS connection.
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.232.165.11.1.3.1.5
Setting this OID to IPv4(1) will enable the IPv4 configuration.
Setting this OID to IPv6(2) will enable the IPv6 configuration.
Setting this OID to IPv4&IPv6(3) will enable both IPv4 and IPv6 configuration.
Enumeration
Enumerated Values:
1iPv4
2iPv6
3iPv4IPv6
.1.3.6.1.4.1.232.165.11.1.3.1.6
Setting this OID to off(0) will disable the Redfish API.
Setting this OID to on(1) will enable the Redfish API.
Enumerationr/w
Enumerated Values:
0off
1on
.1.3.6.1.4.1.232.165.11.1.3.1.7
Indicates the intended physical orientation of OLED display.
displayNormal(1) indicates normal orientation.
displayReverse(2) indicates upside down orientation.
Enumerationr/w
Enumerated Values:
1displayNormal
2displayReverse
.1.3.6.1.4.1.232.165.11.1.3.1.8
Setting this OID to reset(2) will cause the device energy meter value
to be reset to zero. Getting this OID in models that support this feature
will do nothing and return the noOperation(1) value. Models that do not
su…
Enumerationr/w
Enumerated Values:
1noOperation
2reset
3notSupported
.1.3.6.1.4.1.232.165.11.1.3.1.9
Getting this OID will return noOperation(0).
Getting this OID to reset(1) will reset NMC.
Enumerationr/w
Enumerated Values:
0noOperation
1reset
.1.3.6.1.4.1.232.165.11.1.3.1.10
Setting this OID to daisychain(0) will enable daisychain mode.
Enumerationr/w
Enumerated Values:
0daisychain
.1.3.6.1.4.1.232.165.11.1.3.1.11

pdu3InputTable

table mandatory
.1.3.6.1.4.1.232.165.11.2.1 · 1 row entry · 10 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3InputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3InputTable'
Aggregate Object with number of entries equal to pdu3NumberPDU .
pdu3InputEntry row .1.3.6.1.4.1.232.165.11.2.1.1
The ident table entry containing the VA, Watts, WH, etc.
Indexes
Column Syntax OID
pdu3InputTypemandatory
Type of input - single phase, split phase, three phase delta, or three
phase wye.
Enumeration
Enumerated Values:
1singlePhase
2splitPhase
3threePhaseDelta
4threePhaseWye
.1.3.6.1.4.1.232.165.11.2.1.1.1
The measured input frequency from the PDU meters in tenths of Hz.
Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.232.165.11.2.1.1.2
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
Enumeration
Enumerated Values:
1good
2outOfRange
.1.3.6.1.4.1.232.165.11.2.1.1.3
A total input VA of all phases. Units are 0.001 VA. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.1.1.4
A total input Watts of all phases. Units are 0.001 Watts. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.1.1.5
A total input Watt-Hour value for all phases. Units are KWh. This value is accumulated since PDU in service.
A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.1.1.6
A Timestamp of when the Total Input WH was last reset.
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.232.165.11.2.1.1.7
A total input Watt-Hour value for all phases. Units are 0.001 Wh. This value can be reset to 0
using GUI. In that case, the pdu3InputPowerWattHourTimer will be reset as well
A negative value indicates that this obje…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.1.1.8
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920.
A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.1.1.9
An input VAR value. Units are 0.001 VAR. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.1.1.10

pdu3InputPhaseTable

table mandatory
.1.3.6.1.4.1.232.165.11.2.2 · 1 row entry · 24 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3InputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3InputPhaseTable'
Aggregate Object with number of entries equal to number of PDUs (pdu3NumberPDU) and
number of input phase (pdu3InputPhaseCount).
pdu3InputPhaseEntry row .1.3.6.1.4.1.232.165.11.2.2.1
The input table entry containing the voltage, current, frequency, power for each phase.
Entries are given with number of pdu and number of input phase 1, 2, or 3.
Column Syntax OID
Index for the Pdu3InputEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.11.2.2.1.1
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, or phase 3 to phase 1.
Enumeration
Enumerated Values:
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
.1.3.6.1.4.1.232.165.11.2.2.1.2
An input voltage measurement value. Return value is divided by 10.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.3
Status of the measured input voltage relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.11.2.2.1.4
Lower warning threshold. Return value is divided by 10. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.11.2.2.1.5
Lower critical threshold. Return value is divided by 10. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.11.2.2.1.6
Upper warning threshold. Return value is divided by 10. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.11.2.2.1.7
Upper critical threshold. Return value is divided by 10. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.11.2.2.1.8
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3.
Enumeration
Enumerated Values:
1singlePhase
2neutral
3phase1
4phase2
5phase3
.1.3.6.1.4.1.232.165.11.2.2.1.9
Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Return value is divided by 100.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.10
An input current measurement value. Return value is divided by 100.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.11
Status of the measured input current relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.11.2.2.1.12
Lower warning threshold. Return value is divided by 100. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.11.2.2.1.13
Lower critical threshold. Return value is divided by 100. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.11.2.2.1.14
Upper warning threshold. Return value is divided by 100. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.11.2.2.1.15
Upper critical threshold. Return value is divided by 100. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.11.2.2.1.16
Current percent load, based on the rated current capacity. Units are
percentage, for example 80.9 % will be returned as 809. A negative
value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.17
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3.
Enumeration
Enumerated Values:
1singlePhase
2neutral
3phase1
4phase2
5phase3
.1.3.6.1.4.1.232.165.11.2.2.1.18
An input VA value. Units are VA. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.19
An input Watts value. Units are Watts. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.20
A kWatt-Hour value for each Input phase. Units are kWh. This value can be reset to 0
using GUI. In that case, the pdu3InputPhasePowerWattHourTimer will be reset as well
A negative value indicates that this object …
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.21
Timestamp of when input phase kWatt-hours (kWh) was last reset.
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.232.165.11.2.2.1.22
An input PF value. Return value is divided by 100, for example a power factor
of 0.95 would be returned as 95. A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.23
An input VA Reactive value. Units are in VAR. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.2.2.1.24

pdu3GroupTable

table mandatory
.1.3.6.1.4.1.232.165.11.3.1 · 1 row entry · 26 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3GroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3GroupTable'
Aggregate Object with number of entries equal to number of PDUs
and number of breakers (pdu3GroupCount).
pdu3GroupEntry row .1.3.6.1.4.1.232.165.11.3.1.1
The input table entry containing the name, voltages, currents, power, etc.
Column Syntax OID
Index for the Pdu3GroupEntry table.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.11.3.1.1.1
pdu3GroupNamemandatory
A descriptive name for the group.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.11.3.1.1.2
pdu3GroupTypemandatory
The type of the group. (5) has no breaker
Enumeration
Enumerated Values:
2breaker1pole
3breaker2pole
4breaker3pole
5outletSection
.1.3.6.1.4.1.232.165.11.3.1.1.3
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, or phase 3 to phase 1.
Enumeration
Enumerated Values:
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
.1.3.6.1.4.1.232.165.11.3.1.1.4
Return value is divided by 10 to get one decimal point, unit is in Volt.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.5
Status of the measured group voltage relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.11.3.1.1.6
Lower warning threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.11.3.1.1.7
Lower critical threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.11.3.1.1.8
Upper warning threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.11.3.1.1.9
Upper critical threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available.
Integer32
Constraints:
range: -1-500000
.1.3.6.1.4.1.232.165.11.3.1.1.10
Rated current capacity of the group. Return value is divided by 100 to get two decimal points,
unit is in Amps. A negative value indicates that the hardware current capacity is unknown (it
will always be unknown for…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.11
A group current measurement value. Return value is divided by 100 to get two decimal points.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.12
Status of the measured group current relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.11.3.1.1.13
Lower warning threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.11.3.1.1.14
Lower critical threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.11.3.1.1.15
Upper warning threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.11.3.1.1.16
Upper critical threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-100000
.1.3.6.1.4.1.232.165.11.3.1.1.17
Current percent load, based on the rated current capacity. Units are
percentage, for example 80.9 % will be returned as 809. A negative
value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.18
A group VA value. Units are VA. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.19
A group power value. Units are Watts. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.20
An energy consumption value for each load segment. Units are kWh. This value can be reset to 0
using GUI. In that case, the pdu3GroupPowerWattHourTimer will be reset as well.
A negative value indicates that this o…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.21
Timestamp when group kilo Watt-hours (group kWh) is reset.
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.232.165.11.3.1.1.22
A group PF value. Return value is divided by 100, for example a power factor of 0.95 would be returned as 95.
A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.23
A measurement for group/load segment power reactive. Units are VAR. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.3.1.1.24
The number of outlets in each group (breaker).
Integer32
Constraints:
range: 0-63
.1.3.6.1.4.1.232.165.11.3.1.1.25
Only applicable to groups with breaker. Indicates whether a breaker is turned
off or on.
Enumeration
Enumerated Values:
1notApplicable
2breakerOn
3breakerOff
.1.3.6.1.4.1.232.165.11.3.1.1.26

pdu3EnvProbeTable

table mandatory
.1.3.6.1.4.1.232.165.11.4.1 · 1 row entry · 4 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3EnvProbeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3EnvProbeTable'
A list of environment probe (1 per PDU) for temperature, humidity, and contacts.  
The number of entries is given by number of PDUs in daisy chain.
pdu3EnvProbeEntry row .1.3.6.1.4.1.232.165.11.4.1.1
Aggregate entries equal to number of PDUs.
Indexes
Column Syntax OID
Scale used to return temperature objects.
Enumeration
Enumerated Values:
1celsius
2fahrenheit
.1.3.6.1.4.1.232.165.11.4.1.1.1
Max number of temperature measurements (1 per probe).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.4.1.1.2
Max number of humidity measurements (1 per probe).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.4.1.1.3
Max number of contact sensors (1 per probe).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.4.1.1.4

pdu3TemperatureTable

table mandatory
.1.3.6.1.4.1.232.165.11.4.2 · 1 row entry · 9 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3TemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3TemperatureTable'
A list of temperature probe measurements.  The number of entries are
given by number of pdu and pdu3TemperatureCount.
pdu3TemperatureEntry row .1.3.6.1.4.1.232.165.11.4.2.1
An entry for a temperature measurement.
Column Syntax OID
A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.232.165.11.4.2.1.1
A descriptive name for the temperature probe.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.11.4.2.1.2
Indicates whether a probe is connected or not.
Enumeration
Enumerated Values:
1disconnected
2connected
3bad
.1.3.6.1.4.1.232.165.11.4.2.1.3
Units are in tenths of a degree (either Fahrenheit or Celsius).
Return value is divided by 10 to get degrees.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.4.2.1.4
Status of the measured temperature relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.11.4.2.1.5
Lower warning threshold. Return value is divided by 10 to get degree. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-150000
.1.3.6.1.4.1.232.165.11.4.2.1.6
Lower critical threshold. Return value is divided by 10 to get degree. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-150000
.1.3.6.1.4.1.232.165.11.4.2.1.7
Upper warning threshold. Return value is divided by 10 to get degree. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-150000
.1.3.6.1.4.1.232.165.11.4.2.1.8
Upper critical threshold. Return value is divided by 10 to get degree. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-150000
.1.3.6.1.4.1.232.165.11.4.2.1.9

pdu3HumidityTable

table mandatory
.1.3.6.1.4.1.232.165.11.4.3 · 1 row entry · 9 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3HumidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3HumidityTable'
A list of humidity probe measurements.  The number of entries are
given by number of pdu and pdu3HumidityCount.
pdu3HumidityEntry row .1.3.6.1.4.1.232.165.11.4.3.1
An entry for a humidity measurement.
Column Syntax OID
A unique value for each humidity probe measurement. Its value
ranges from 1 to pdu3HumidityCount per pdu.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.232.165.11.4.3.1.1
A descriptive name for the humidity probe.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.11.4.3.1.2
Indicates whether a probe is connected or not.
Enumeration
Enumerated Values:
1disconnected
2connected
3bad
.1.3.6.1.4.1.232.165.11.4.3.1.3
Units are tenths of a percent relative humidity. Return value is divided by 10 to get %RH.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.4.3.1.4
Status of the measured humidity relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.11.4.3.1.5
Lower warning threshold. Return value is divided by 10 to get %RH. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-1000
.1.3.6.1.4.1.232.165.11.4.3.1.6
Lower critical threshold. Return value is divided by 10 to get %RH. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-1000
.1.3.6.1.4.1.232.165.11.4.3.1.7
Upper warning threshold. Return value is divided by 10 to get %RH. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-1000
.1.3.6.1.4.1.232.165.11.4.3.1.8
Upper critical threshold. Return value is divided by 10 to get %RH. A negative value
indicates that this object is not available.
Integer32
Constraints:
range: -1-1000
.1.3.6.1.4.1.232.165.11.4.3.1.9

pdu3ContactTable

table mandatory
.1.3.6.1.4.1.232.165.11.4.4 · 1 row entry · 4 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3ContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3ContactTable'
A list of contact sensors.  The number of entries are
given by number of pdu and pdu3ContactCount.
pdu3ContactEntry row .1.3.6.1.4.1.232.165.11.4.4.1
An entry for a contact sensor
Column Syntax OID
A unique value for each contact sensor. Its value ranges from 1 to
contactCount.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.232.165.11.4.4.1.1
A descriptive name for the contact sensor.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.11.4.4.1.2
Indicates whether a probe is connected or not.
Will not be returned if the contact sensor is internal to the ePDU,
in that case only contactState should be read.
Enumeration
Enumerated Values:
1disconnected
2connected
3bad
.1.3.6.1.4.1.232.165.11.4.4.1.3
The state of the contact sensor.
Enumeration
Enumerated Values:
1contactOpen
2contactClosed
3contactBad
.1.3.6.1.4.1.232.165.11.4.4.1.4

pdu3OutletTable

table mandatory
.1.3.6.1.4.1.232.165.11.5.1 · 1 row entry · 17 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3OutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3OutletTable'
Aggregate Object with number of entries equal to Number of PDU (pdu3IdentIndex)
and Number of outlet per PDU (pdu3OutletIndex).
pdu3OutletEntry row .1.3.6.1.4.1.232.165.11.5.1.1
The Outlet table entry containing the type, voltage, current etc.
Column Syntax OID
Index for each outlet, value from 1 to the number of outlets per PDU.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.232.165.11.5.1.1.1
A descriptive name for the outlet.
OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.232.165.11.5.1.1.2
Type of this outlet - C13, C19.
Enumeration
Enumerated Values:
1iecC13
2iecC19
10uk
11french
12schuko
20nema515
21nema51520
22nema520
23nemaL520
24nemaL530
25nema615
26nema620
27nemaL620
28nemaL630
29nemaL715
30rf203p277
.1.3.6.1.4.1.232.165.11.5.1.1.3
Rated current capacity of this outlet. Return value is divided by 100 to get amps. A negative
value indicates that the hardware current capacity is unknown.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.5.1.1.4
A outlet current measurement value. Return value is divided by 100 to get amps.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.5.1.1.5
Status of the measured outlet active power relative to the configured thresholds.
Enumeration
Enumerated Values:
1good
2lowWarning
3lowCritical
4highWarning
5highCritical
.1.3.6.1.4.1.232.165.11.5.1.1.6
Lower warning threshold. Units are Watts(W). A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-10000
.1.3.6.1.4.1.232.165.11.5.1.1.7
Lower critical threshold. Units are Watts(W). A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-10000
.1.3.6.1.4.1.232.165.11.5.1.1.8
Upper warning threshold. Units are Watts(W). A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-10000
.1.3.6.1.4.1.232.165.11.5.1.1.9
Upper critical threshold. Units are Watts(W). A negative value indicates
that this object is not available.
Integer32
Constraints:
range: -1-10000
.1.3.6.1.4.1.232.165.11.5.1.1.10
Current percent load, based on the rated current capacity. Units are
percentage, for example 80.5% will be returned as 805. A negative
value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.5.1.1.11
pdu3OutletVAmandatory
A outlet power VA value. Units are VA. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.5.1.1.12
A outlet power in Watts value. Units are Watts. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.5.1.1.13
pdu3OutletWhmandatory
An energy in kWatt-Hour value for each outlet. Units are kWh.
This object is writable so that it can be reset to 0. When it is
written to, the pdu3OutletWhTimer will be reset updated as well
A negative value indic…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.5.1.1.14
Timestamp (date and time) of outlet energy in kWh is reset.
OctetString
Constraints:
range: 0-22
.1.3.6.1.4.1.232.165.11.5.1.1.15
An outlet PF value. Return value is divided by 100, for example a power factor
of 0.95 would be returned as 95. A negative value indicates that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.5.1.1.16
pdu3OutletVARmandatory
An outlet power reactive in VAR value. Units are VAR. A negative value indicates
that this object is not available.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.232.165.11.5.1.1.17

pdu3OutletControlTable

table mandatory
.1.3.6.1.4.1.232.165.11.5.2 · 1 row entry · 9 columns
Uses the hp variant from /opt/observium/mibs/hp.
Command help
Walk pdu3OutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3OutletControlTable'
Aggregate Object with number of entries equal to Number of PDU (pdu3IdentIndex) 
and Number of outlets per PDU (pdu3OutletIndex).
pdu3OutletControlEntry row .1.3.6.1.4.1.232.165.11.5.2.1
The Outlet table entry containing the type, voltage, current etc.
Column Syntax OID
current state of a control outlet.
Enumeration
Enumerated Values:
1off
2on
3pendingOff
4pendingOn
.1.3.6.1.4.1.232.165.11.5.2.1.1
When write, once issued, the outlet will turn Off immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet Off command
When read, returns -1 if no command is pending, or the curr…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.11.5.2.1.2
When write, once issued, the outlet will turn On immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet On command
When read, returns -1 if no command is pending, or the curren…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.11.5.2.1.3
When write, for outlets that are On prior to this Reboot command, they will
switch Off immediately when the command is issued, remain Off for
outletControlRebootOffTime seconds, and then turn back On.
For outlets tha…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.11.5.2.1.4
Determines the outlet state when power is applied to the unit.
1 : not restart at device startup
2 : should sequence back ON in line with outletControlSequenceTime
3 : should take the state the outlet had when power was…
Enumerationr/w
Enumerated Values:
1off
2on
3lastState
.1.3.6.1.4.1.232.165.11.5.2.1.5
Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on
delay. Set to -1 to exclude this outlet from Global Sequence …
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.11.5.2.1.6
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.11.5.2.1.7
Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled
2 : control On/Off disabled.
Enumerationr/w
Enumerated Values:
1switchable
2notSwitchable
.1.3.6.1.4.1.232.165.11.5.2.1.8
Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first
then write it to the command pdu3OutletControlOf…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.232.165.11.5.2.1.9