CPQPOWER-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
41
Rows
41
Columns
485
.1.3.6.1.4.1.232.165.2.1.2
·
1 row entry
·
9 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pduIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pduIdentTable'
The Aggregate Object with number of entries equal to NumOfPdu and including the PduIdent group.
The ident table entry containing the name,
model, manufacturer, firmware version, part number, etc.
model, manufacturer, firmware version, part number, etc.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
pduIdentIndexmandatory
Index for the PduIdentEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.2.1.2.1.1 |
||||||||
|
pduNamemandatory
The string identify the device.
|
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.2.1.2.1.2 |
||||||||
|
pduModelmandatory
The Device Model.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.2.1.2.1.3 |
||||||||
|
pduManufacturermandatory
The Device Manufacturer Name (e.g. Hewlett-Packard).
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.2.1.2.1.4 |
||||||||
|
pduFirmwareVersionmandatory
The firmware revision level of the device.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.2.1.2.1.5 |
||||||||
|
pduPartNumbermandatory
The device part number.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.2.1.2.1.6 |
||||||||
|
pduSerialNumbermandatory
The device serial number.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.2.1.2.1.7 |
||||||||
|
pduStatusmandatory
The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of failed(4) indicates the devic… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.2.1.2.1.8 |
||||||||
|
pduControllablemandatory
This object indicates whether or not the device is controllable.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.2.1.2.1.9 |
.1.3.6.1.4.1.232.165.2.2.1
·
1 row entry
·
3 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pduInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pduInputTable'
The Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
The input table entry containing the voltage and
current for the PDU
current for the PDU
Indexes
| Column | Syntax | OID |
|---|---|---|
|
pduInputIndexmandatory
Index for the PduInputEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.2.2.1.1.1 |
|
inputVoltagemandatory
The measured input voltage from the PDU meters in volts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.2.2.1.1.2 |
|
inputCurrentmandatory
The measured input current from the PDU meters in hundredths of Amp.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.2.2.1.1.3 |
.1.3.6.1.4.1.232.165.2.3.1
·
1 row entry
·
5 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pduOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pduOutputTable'
The Aggregate Object with number of entries equal to NumOfPdu and including the PduInput group.
The input table entry containing the name,
heat load, current load, power load, firmware, etc.
heat load, current load, power load, firmware, etc.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
pduOutputIndexmandatory
Index for the PduOutputEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.2.3.1.1.1 |
|
pduOutputLoadmandatory
The device output load in percent of rated capacity. A value of -1 will be
returned if the heat load is unable to be measured. |
Integer32 Constraints: range: 0-200 |
.1.3.6.1.4.1.232.165.2.3.1.1.2 |
|
pduOutputHeatmandatory
The total heat load measured on the PDU in BTUs. A value of -1 will be
returned if the heat load is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.2.3.1.1.3 |
|
pduOutputPowermandatory
The total power load measured on the PDU in watts. A value of -1 will be
returned if the power load is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.2.3.1.1.4 |
|
pduOutputNumBreakersmandatory
The number of breakers for the device. This variable indicates the number
of rows in the breakers table. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.2.3.1.1.5 |
.1.3.6.1.4.1.232.165.2.3.2
·
1 row entry
·
5 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pduOutputBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pduOutputBreakerTable'
List of breaker table entries. The number of entries is given by pduOutputNumBreakers .
An entry containing information applicable to an breaker.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
breakerIndexmandatory
The breaker identifier.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.2.3.2.1.1 |
||||||||||
|
breakerVoltagemandatory
The breaker voltage in volts.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.2.3.2.1.2 |
||||||||||
|
breakerCurrentmandatory
The breaker current draw in hundredths of Amp.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.2.3.2.1.3 |
||||||||||
|
breakerPercentLoadmandatory
The breaker load in percent.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.2.3.2.1.4 |
||||||||||
|
breakerStatusmandatory
This object indicates the status of the breaker. A value of normal(1)
indicates the breaker is operating normally. A value of overloadWarning(2) indicates the breaker has an overload warning. A value of overloadCriti… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.2.3.2.1.5 |
.1.3.6.1.4.1.232.165.3.3.4
·
1 row entry
·
4 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk upsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsInputTable'
The Aggregate Object with number of entries equal to NumPhases and including the UpsInput group.
The input table entry containing the current, voltage, etc.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
upsInputPhasemandatory
The number of the phase. Serves as index for input table.
|
Integer32 Constraints: range: 0-6 |
.1.3.6.1.4.1.232.165.3.3.4.1.1 |
|
upsInputVoltagemandatory
The measured input voltage from the UPS meters in volts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.3.3.4.1.2 |
|
upsInputCurrentmandatory
The measured input current from the UPS meters in amps.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.3.3.4.1.3 |
|
upsInputWattsmandatory
The measured input real power in watts. Most UPSs do not report
this XCP data |
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.3.3.4.1.4 |
.1.3.6.1.4.1.232.165.3.4.4
·
1 row entry
·
4 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk upsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsOutputTable'
The Aggregate Object with number of entries equal to NumPhases and including the UpsOutput group.
Output Table Entry containing voltage, current, etc.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
upsOutputPhasemandatory
The number {1..3} of the output phase.
|
Integer32 Constraints: range: 0-6 |
.1.3.6.1.4.1.232.165.3.4.4.1.1 |
|
upsOutputVoltagemandatory
The measured output voltage from the UPS metering in volts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.3.4.4.1.2 |
|
upsOutputCurrentmandatory
The measured UPS output current in amps.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.3.4.4.1.3 |
|
upsOutputWattsmandatory
The measured real output power in watts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.3.4.4.1.4 |
.1.3.6.1.4.1.232.165.3.5.3
·
1 row entry
·
2 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk upsBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsBypassTable'
Entry in the UpsBypassTable.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
upsBypassPhasemandatory
The Bypass Phase, index for the table.
|
Integer32 Constraints: range: 0-6 |
.1.3.6.1.4.1.232.165.3.5.3.1.1 |
|
upsBypassVoltagemandatory
The measured UPS bypass voltage in volts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.3.5.3.1.2 |
.1.3.6.1.4.1.232.165.3.6.8
·
1 row entry
·
4 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk upsContactsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsContactsTable'
A list of Contact Sensing table entries. The number of entries is given by the value of UpsEnvNumContacts.
An entry containing information applicable
to a particular Contact input.
to a particular Contact input.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
upsContactIndexmandatory
The Contact identifier; identical to the Contact Number.
|
Integer32 Constraints: range: 1-1024 |
.1.3.6.1.4.1.232.165.3.6.8.1.1 |
||||||||
|
upsContactTypemandatory
The normal state for this contact. The 'other'
state is the Active state for generating the UpstdContactActiveNotice trap. If anyChange(3) is selected, then this trap is sent any time the contact changes to either Ope… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.3.6.8.1.2 |
||||||||
|
upsContactStatemandatory
The current state of the Contact input;
the value is based on the open/closed input state and the setting for UpsContactType. When entering the openWithNotice(3) and closedWithNotice(4) states, no entries added to the… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.3.6.8.1.3 |
||||||||
|
upsContactDescrmandatory
A label identifying the Contact. This object should be
set by the administrator. |
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.3.6.8.1.4 |
.1.3.6.1.4.1.232.165.3.10.2
·
1 row entry
·
7 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk upsRecepTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::upsRecepTable'
The Aggregate Object with number of entries equal to NumReceptacles and including the UpsRecep group.
The Recep table entry, etc.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsRecepIndexmandatory
The number of the Receptacle. Serves as index for Receptacle table.
|
Integer32 Constraints: range: 1-64 |
.1.3.6.1.4.1.232.165.3.10.2.1.1 |
||||||||||
|
upsRecepStatusmandatory
The Recep Status 1=On/Close, 2=Off/Open, 3=On w/Pending Off,
4=Off w/Pending ON, 5=Unknown. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.3.10.2.1.2 |
||||||||||
|
upsRecepOffDelaySecsmandatory
The Delay until the Receptacle is turned Off. Setting
this value to other than -1 will cause the UPS output to turn off after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abor… |
Integer32r/w Constraints: range: -1-2147483647 |
.1.3.6.1.4.1.232.165.3.10.2.1.3 |
||||||||||
|
upsRecepOnDelaySecsmandatory
The Delay until the Receptacle is turned On. Setting
this value to other than -1 will cause the UPS output to turn on after the number of seconds (0 is immediately). Setting it to -1 will cause an attempt to abort … |
Integer32r/w Constraints: range: -1-2147483647 |
.1.3.6.1.4.1.232.165.3.10.2.1.4 |
||||||||||
|
upsRecepAutoOffDelaymandatory
The delay after going On Battery until the Receptacle is
automatically turned Off. A value of -1 means that this Output should never be turned Off automatically, but must be turned Off only by command. Values from 0 … |
Integer32r/w Constraints: range: -1-32767 |
.1.3.6.1.4.1.232.165.3.10.2.1.5 |
||||||||||
|
upsRecepAutoOnDelaymandatory
Seconds delay after the Outlet is signaled to turn On before the Output is
Automatically turned ON. A value of -1 means that this Output should never be turned On automatically, but only when specifically commanded to d… |
Integer32r/w Constraints: range: -1-32767 |
.1.3.6.1.4.1.232.165.3.10.2.1.6 |
||||||||||
|
upsRecepShedSecsWithRestartmandatory
Setting this value will cause the UPS output to turn off
after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike UpsRecepOffDelaySecs, which might o… |
Integer32r/w Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.3.10.2.1.7 |
.1.3.6.1.4.1.232.165.4.2.1
·
1 row entry
·
16 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdrPanelTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdrPanelTable'
Aggregate Object with number of entries equal to pdrNumPanels
The panel table entry containing all power parameters
for each panel.
for each panel.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
pdrPanelIndexmandatory
Index for the pdrPanelEntry table.
|
Integer32 Constraints: range: 0-10 |
.1.3.6.1.4.1.232.165.4.2.1.1.1 |
|
pdrPanelFrequencymandatory
The present frequency reading for the panel voltage.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.2 |
|
pdrPanelPowermandatory
The present power of the panel.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.3 |
|
pdrPanelRatedCurrentmandatory
The present rated current of the panel.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.4 |
|
pdrPanelMonthlyKWHmandatory
The accumulated KWH for this panel since the beginning of this
calendar month or since the last reset. |
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.5 |
|
pdrPanelYearlyKWHmandatory
The accumulated KWH for this panel since the beginning of this
calendar year or since the last reset. |
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.6 |
|
pdrPanelTotalKWHmandatory
The accumulated KWH for this panel since it was put into service
or since the last reset. |
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.7 |
|
pdrPanelVoltageAmandatory
The measured panel output voltage.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.8 |
|
pdrPanelVoltageBmandatory
The measured panel output voltage.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.9 |
|
pdrPanelVoltageCmandatory
The measured panel output voltage.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.10 |
|
pdrPanelCurrentAmandatory
The measured panel output current.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.11 |
|
pdrPanelCurrentBmandatory
The measured panel output current.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.12 |
|
pdrPanelCurrentCmandatory
The measured panel output current.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.2.1.1.13 |
|
pdrPanelLoadAmandatory
The percentage of load is the ratio of each output
current to the rated output current to the panel. |
Integer32 Constraints: range: 0-200 |
.1.3.6.1.4.1.232.165.4.2.1.1.14 |
|
pdrPanelLoadBmandatory
The percentage of load is the ratio of each output
current to the rated output current to the panel. |
Integer32 Constraints: range: 0-200 |
.1.3.6.1.4.1.232.165.4.2.1.1.15 |
|
pdrPanelLoadCmandatory
The percentage of load is the ratio of each output
current to the rated output current to the panel. |
Integer32 Constraints: range: 0-200 |
.1.3.6.1.4.1.232.165.4.2.1.1.16 |
.1.3.6.1.4.1.232.165.4.3.1
·
1 row entry
·
14 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdrBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdrBreakerTable'
List of breaker table entries. The number of entries is given by pdrNumBreakers for this panel.
An entry containing information applicable to a
particular output breaker of a particular panel.
particular output breaker of a particular panel.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
pdrBreakerIndexmandatory
The index of breakers. 42 breakers in each panel,
arranged in odd and even columns |
Integer32 Constraints: range: 0-200 |
.1.3.6.1.4.1.232.165.4.3.1.1.1 |
|
pdrBreakerPanelmandatory
The index of panel that these breakers are installed on.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.2 |
|
pdrBreakerNumPositionmandatory
The position of this breaker in the panel, 1-phase breaker
or n-m breaker for 2-phase or n-m-k breaker for 3-phase. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.3 |
|
pdrBreakerNumPhasesmandatory
The number of phase for this particular breaker.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.4 |
|
pdrBreakerNumSequencemandatory
The sequence of this breaker. i.e. 1 for single phase
1,2 for 2-phase or 1,2,3 for 3-phase. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.5 |
|
pdrBreakerRatedCurrentmandatory
The rated current in Amps for this particular breaker.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.6 |
|
pdrBreakerMonthlyKWHmandatory
The accumulated KWH for this breaker since the beginning of this
calendar month or since the last reset. |
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.7 |
|
pdrBreakerYearlyKWHmandatory
The accumulated KWH for this breaker since the beginning of this
calendar year or since the last reset. |
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.8 |
|
pdrBreakerTotalKWHmandatory
The accumulated KWH for this breaker since it was put into service
or since the last reset. |
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.9 |
|
pdrBreakerCurrentmandatory
The measured output current for this breaker Current.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.10 |
|
pdrBreakerCurrentPercentmandatory
The ratio of output current over rated
current for each breaker. |
Integer32 Constraints: range: 0-200 |
.1.3.6.1.4.1.232.165.4.3.1.1.11 |
|
pdrBreakerPowermandatory
The power for this breaker in Watts.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.12 |
|
pdrBreakerPercentWarningmandatory
The percentage of Warning set for this breaker.
|
Integer32 Constraints: range: 0-200 |
.1.3.6.1.4.1.232.165.4.3.1.1.13 |
|
pdrBreakerPercentOverloadmandatory
The percentage of Overload set for this breaker.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.4.3.1.1.14 |
.1.3.6.1.4.1.232.165.5.1.2
·
1 row entry
·
41 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk mpduIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::mpduIdentTable'
Indexed by mpduNumMPDU. So aggregate objects for each entry equal to mpduNumMPDU before go to the next entry. i.e if 4 MPDU detected, display 4 indexes, 4 Manufacturers, 4 Models..., start with 1.
The table entry containing the identifications of each MPDU as well
as names of PDR panel, location of MPDU in a Data Center.
as names of PDR panel, location of MPDU in a Data Center.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mpduIdentIndexmandatory
Index for the MpduIdentEntry table. Start with 1
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.5.1.2.1.1 |
|
mpduManufacturermandatory
The Core PDU manufacturer. StringLength=[21]
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.2 |
|
mpduModelmandatory
The Core PDU model, marketing name. StringLength=[40].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.3 |
|
mpduNamemandatory
The Core PDU name, descriptive name or hostname. StringLength=[16].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.4 |
|
mpduFirmwareVersionmandatory
The Core PDU firmware version(s). StringLength=[12].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.5 |
|
mpduHardwareVersionmandatory
The Core PDU hardware version. StringLength=[8].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.6 |
|
mpduPartNumbermandatory
The Core PDU part number. StringLength=[21].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.7 |
|
mpduSerialNumbermandatory
The PDU external serial number. StringLength=[21].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.8 |
|
mpduUUIDmandatory
The PDU's UUID equals PN add SN then canonical conversion. StringLength=[37].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.9 |
|
mpduIPmandatory
The PDU's assigned IP. StringLength=[16].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.10 |
|
mpduMACAddressmandatory
The Core PDU MAC address. StringLength=[18].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.11 |
|
mpduControlStatusmandatory
The Core PDU Control Status: master or slave units.
StringLength=[31]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.12 |
|
mpduRegionmandatory
The PDU's Region: NA, Intl, Japan... StringLength=[7].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.13 |
|
mpduTypemandatory
The PDU's Type: Delta, Wye, single, Wye+lowline.
StringLength=[24]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.14 |
|
mpduPowerRatingmandatory
The PDU's Power Rating in KVA (Name Plate). Value is presented
in 1/100 of the KVA. i.e. 1750 means 17.50 KVA |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.15 |
|
mpduInputRatingmandatory
The PDU's Input Current Rating in A (Name Plate)
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.16 |
|
mpduInputPlugmandatory
The PDU's Input Plug: IEC60309 516P6,NEMA L15-30P...
StringLength=[16]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.17 |
|
mpduNumBreakersmandatory
The number of breakers used in each MPDU (6 by default).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.18 |
|
mpduNumOutletmandatory
The number of outlets of each MPDU (6 by default).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.19 |
|
mpduUHeightmandatory
The MPDU U Height 1U or 2 U (1U by default).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.20 |
|
mpduRedundantStatusmandatory
Status of Core PDU in paired or not: Stand-alone or Redundant.
StringLength=[12]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.21 |
|
mpduNumSmartExtBarmandatory
total number of detected Smart Sticks connecting to each PDU.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.22 |
|
mpduPanelNamemandatory
Name of Panel that was entered by customer in GUI.
StringLength=[50]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.23 |
|
mpduPanelBreakerNamemandatory
Name of breakers or Panel Position entered by customer in GUI.
StringLength=[50]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.24 |
|
mpduPanelBreakerRatingmandatory
Breaker rating of the PDR Panel.
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.25 |
|
mpduACFeedNamemandatory
it would be A, B, Red, or White...
StringLength=[50]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.26 |
|
mpduFloorNamemandatory
Name of building floor entered by customer in GUI.
StringLength=[50]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.27 |
|
mpduRoomNamemandatory
Name of the room entered by customer in GUI. StringLength=[50].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.28 |
|
mpduRowmandatory
Data Center Row entered by customer in GUI.
StringLength=[11]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.29 |
|
mpduRowPositionmandatory
Position in Row entered by customer in GUI. Null will be returned
if not detected. StringLength=[11]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.30 |
|
mpduRackNamemandatory
Name of the Rack entered by customer in GUI. Null will be returned
if not detected. StringLength=[50]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.31 |
|
mpduRackHeightmandatory
Rack Type (22U, 42U, 50U...). Null will be returned if not detected.
StringLength=[3]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.32 |
|
mpduRackIDmandatory
An unique ID to identify a rack, i.e. Rack SN. Null will be returned if
not detected. StringLength=[50]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.33 |
|
mpduUPositionmandatory
PDU Rack bottom U Start position, core U position. Null will be returned if not detected.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.34 |
|
mpduPairedPDUUUIDmandatory
UUID of the PDU paired with this one. Null will be returned if not detected.
StringLength=[50]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.35 |
|
mpduPairedPDUIPmandatory
IP address of the PDU paired with this one. Null will be returned if not detected.
StringLength=[16]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.36 |
|
mpduInstalledLocationmandatory
0=Left 0U side area or rack frame, 1= Right 0U side area or rack frame, 2= front RETMA rail,
3=back RETMA rail) - spatial location. A value of -1 will be returned if not detected. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.37 |
|
mpduTotalPowerWattmandatory
The total power for the whole iPDU in Watts. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.38 |
|
mpduTotalPowerVAmandatory
The total power for the whole iPDU in VA. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.39 |
|
mpduTotalPercentLoadmandatory
The whole iPDU's load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value of -1 will be returned if the current is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.1.2.1.40 |
|
mpduRegionalNominalVoltagemandatory
value is either America(208V), Japan(202V) or blank for International Model
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.1.2.1.41 |
.1.3.6.1.4.1.232.165.5.2.1
·
1 row entry
·
13 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk mpduOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::mpduOutputTable'
Indexed by mpduNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet) before go to the next entry. i.e if 4 MPDU detected, display 6x4 indexes, 6x4 OutputStatus, 6x4 OutputBreakerRating...start with 1.
The output table entry containing the voltage, current, PF,
percent load, VA, Watts for the Modular PDU.
percent load, VA, Watts for the Modular PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mpduOutputIndexmandatory
Index for the MpduOutputEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.5.2.1.1.1 |
|
mpduOutputStatusmandatory
The overall status of the device: off, on, problem. StringLength=[7].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.2.1.1.2 |
|
mpduOutputBreakerRatingmandatory
The rating of each MPDU Output in Ampere.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.3 |
|
mpduOutputSmartDevicemandatory
A smart cord device detected: False, True. StringLength=[5].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.2.1.1.4 |
|
mpduOutputPercentLoadmandatory
The MPDU's each output load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value of -1 will be returned if the current is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.5 |
|
mpduOutputVoltagemandatory
The measured output voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value of -1 will be returned if the voltage is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.6 |
|
mpduOutputCurrentmandatory
The measured output current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value of -1 will be returned if the current is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.7 |
|
mpduOutputPowerVAmandatory
The total VA load (VI) measured on the PDU in VA. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.8 |
|
mpduOutputPowerWattmandatory
The total power load measured on the PDU in Watts. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.9 |
|
mpduOutputPowerFactormandatory
The power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.10 |
|
mpduOutputWarningThresholdmandatory
Report the User-set threshhold limit for Warning in percentage
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.11 |
|
mpduOutputCriticalThresholdmandatory
Report the User-set threshhold limit for Critical in percentage
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.12 |
|
mpduOutputPowerWattHourmandatory
Support Billing Grade Energy Metering in Watt-Hour. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.2.1.1.13 |
.1.3.6.1.4.1.232.165.5.3.1
·
1 row entry
·
20 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk mpduDeviceIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::mpduDeviceIdentTable'
Indexed by mpduNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet) before go to the next entry. i.e if 4 MPDU detected, display 6x4 indexes, 6x4 mpduDeviceStatus, 6x4 DeviceUIDStatus...start with 1.
The ident table entry containing the name, model,
manufacturer, firmware version, part number... for
each smart device, null value for unknown device.
manufacturer, firmware version, part number... for
each smart device, null value for unknown device.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mpduDeviceIdentIndexmandatory
Index is based on the total number of Smart Extension Bars plus
smart devices (with smart power cord i.e. blades) detected. |
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.5.3.1.1.1 |
|
mpduDeviceStatusmandatory
The overall status of the device: off, on, problem. StringLength=[8].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.2 |
|
mpduDeviceUIDStatusmandatory
The overall status of the device UID: off, on, blink. StringLength=[8].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.3 |
|
mpduDeviceNumOutletmandatory
The number of outlets of detected the device. This variable
indicates the number of rows in the breakers table. Default is 5 |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.3.1.1.4 |
|
mpduDeviceUHeightmandatory
The Unit height of ext bar or device. Some device supports non-integer.
Present value x100, when read back, divided by 100 to get 2 decimal points. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.3.1.1.5 |
|
mpduDevicePowerRatingmandatory
The device's Power Rating in VA. Null will be returned if not detected.
StringLength=[8]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.6 |
|
mpduDeviceManufacturermandatory
The Device Manufacturer Name (e.g. Hewlett-Packard).
Null will be returned if not detected. StringLength=[16]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.7 |
|
mpduDeviceTypemandatory
The Device's Type: Ext Bar, server, or network device...
StringLength=[16]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.8 |
|
mpduDeviceModelmandatory
The Device Model is Managed or Non-managed Ext Bar.
Null will be returned if not detected. StringLength=[24]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.9 |
|
mpduDeviceNamemandatory
The string identify the Device. i.e. 'BAR#1' (descriptive name)
Null will be returned if not detected. StringLength=[32]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.10 |
|
mpduDeviceFirmwareVersionmandatory
The firmware revision level of Sm Ext Bar. Null will be returned if
not detected. StringLength=[8]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.11 |
|
mpduDeviceHardwareVersionmandatory
The hardware version of Sm Ext Bar. Null will be returned if not
detected. StringLength=[8]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.12 |
|
mpduDevicePartNumbermandatory
The device's part number. Null will be returned if not detected.
StringLength=[21]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.13 |
|
mpduDeviceSerialNumbermandatory
The device's serial number. Null will be returned if not detected.
StringLength=[21]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.14 |
|
mpduDeviceUUIDmandatory
The device's UUID. Null will be returned if not detected.
StringLength=[37]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.15 |
|
mpduDeviceIPmandatory
The device's IP Address. Null will be returned if not detected.
StringLength=[16]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.16 |
|
mpduDeviceMACmandatory
The device mgmt processor MAC Address. Null will be returned if
not detected. StringLength=[18]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.3.1.1.17 |
|
mpduDevicePSUSlotNomandatory
Device power supply logical slot number.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.3.1.1.18 |
|
mpduDeviceUPositionmandatory
Device U start position.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.3.1.1.19 |
|
mpduDeviceDetectionThresholdmandatory
Read device detection threshold between 10 and 50mA.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.3.1.1.20 |
.1.3.6.1.4.1.232.165.5.4.1
·
1 row entry
·
20 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk mpduSmExtBarOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::mpduSmExtBarOutletTable'
Indexed by mpduDeviceNumOutlet. So aggregate objects for each entry equal to (mpduNumMPDU multiplies mpduNumOutlet multiplies mpduDeviceNumOutlet) before go to the next entry. i.e if 4 MPDU detected, display 5x6x4 indexes, 5x6x4 mpduSmExtBarOutletStatus, 5x6x4 mpduSmExtBarOutletUIDStatus...start with 1.
Entries contain status, measurements for each outlet (no PowerVA)
Display null if it can't be measured or no device detected.
Display null if it can't be measured or no device detected.
| Column | Syntax | OID |
|---|---|---|
|
mpduSmExtBarOutletIndexmandatory
The Index of Smart Extension Bar.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.5.4.1.1.1 |
|
mpduSmExtBarOutletStatusmandatory
The overall status of the Smart Extension Bar's outlet: off, on, problem...
StringLength=[3]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.4.1.1.2 |
|
mpduSmExtBarOutletUIDStatusmandatory
The overall status of the Smart Extension Bar's UID: off, on, blink...
StringLength=[8]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.4.1.1.3 |
|
mpduSmExtBarOutletRatingmandatory
Sm Ext Bar Outlet's Rating in Amp. A value of -1 will be returned
if the stick is unable to detect. StringLength=[8]. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.4 |
|
mpduSmExtBarOutletVoltagemandatory
The SM Ext Bar voltage in volts. Value is presented 1/10 of the Volt
i.e. 2098 means 209.8 V. A value of -1 will be returned if the voltage is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.5 |
|
mpduSmExtBarOutletCurrentmandatory
The SM Ext Bar current draw in Amps. Value is presented in 1/100 of the Ampere
i.e. 127 means 1.27 A. A value of -1 will be returned if the current is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.6 |
|
mpduSmExtBarOutletPowerWattmandatory
The Sm Ext Bar's Power measured in Watts. A value of -1 will be returned if the
power is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.7 |
|
mpduSmExtBarOutletPowerFactormandatory
The outlet's power factor in 0.01 unit. It is presented in 1/100 of the unit.
i.e. 98 means 0.98. A value of -1 will be returned if the voltage is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.8 |
|
mpduSmExtBarOutletDeviceNamemandatory
The Device (Blade/Server/Storage) Name that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[50]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.4.1.1.9 |
|
mpduSmExtBarOutletDeviceUUIDmandatory
The Device (Blade/Server/Storage) UUID that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[37]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.4.1.1.10 |
|
mpduSmExtBarOutletDeviceProductmandatory
The Device (Blade/Server/Storage) Model that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[40]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.4.1.1.11 |
|
mpduSmExtBarOutletDeviceIPmandatory
The Device (Blade/Server/Storage) IP of iLO that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[16]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.4.1.1.12 |
|
mpduSmExtBarOutletAutoDiscoveredmandatory
Boolean values of 0 or 1. 1 means this Sm Ext Bar Outlet is able to get information
from a blade with smart power supply (auto discovery is enabled)... |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.13 |
|
mpduSmExtBarOutletDeviceMACmandatory
The Device (Blade/Server/Storage) MAC address that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[18]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.4.1.1.14 |
|
mpduSmExtBarOutletDeviceSNmandatory
The Device (Blade/Server/Storage) Serial Number that connects to this
Sm Ext Bar Outlet. Null will be returned if not detected. StringLength=[21]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.5.4.1.1.15 |
|
mpduSmExtBarOutletDevicePSSlotNomandatory
The Device (Blade/Server/Storage) Power Supply' Slot Number that connects to this
Sm Ext Bar Outlet. A value of -1 will be returned if not detected. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.16 |
|
mpduSmExtBarOutletDeviceUPositionmandatory
Device U start position. A value of -1 will be returned if not detected.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.17 |
|
mpduSmExtBarOutletDeviceUHeightmandatory
Device U height. Enter -1 if not detected. Some device supports non-integer.
Present value x100, when read back, divided by 100 to get 2 decimal points. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.18 |
|
0=Left 0U side area or rack frame, 1= Right 0U side area or rack frame, 2= front RETMA rail,
3=back RETMA rail) - spatial location. A value of -1 will be returned if not detected. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.19 |
|
mpduSmExtBarOutletPowerWattHourmandatory
The Sm Ext Bar's Power measured in Watt-Hour support Billing Grade Energy Metering.
A value of -1 will be returned if the power is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.5.4.1.1.20 |
.1.3.6.1.4.1.232.165.6.3.4
·
1 row entry
·
4 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk oupsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::oupsInputTable'
Aggregate Object with number of entries equal to NumPhases and including the UpsInput group.
The input table entry containing the current, voltage, etc.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
oupsInputPhasemandatory
The number of the phase. Serves as index for input table.
|
Integer32 Constraints: range: 0-6 |
.1.3.6.1.4.1.232.165.6.3.4.1.1 |
|
oupsInputVoltagemandatory
The measured input voltage from the UPS meters in volts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.6.3.4.1.2 |
|
oupsInputCurrentmandatory
The measured input current from the UPS meters in amps.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.6.3.4.1.3 |
|
oupsInputWattsmandatory
The measured input power in watts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.6.3.4.1.4 |
.1.3.6.1.4.1.232.165.6.4.4
·
1 row entry
·
5 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk oupsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::oupsOutputTable'
The Aggregate Object with number of entries equal to NumPhases and including the UpsOutput group.
Output Table Entry containing voltage, current, etc.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
oupsOutputPhasemandatory
The number {1..3} of the output phase.
|
Integer32 Constraints: range: 0-6 |
.1.3.6.1.4.1.232.165.6.4.4.1.1 |
|
oupsOutputVoltagemandatory
The measured output voltage from the UPS metering in volts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.6.4.4.1.2 |
|
oupsOutputCurrentmandatory
The measured UPS output current in amps.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.6.4.4.1.3 |
|
oupsOutputWattsmandatory
The measured real output power in watts.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.6.4.4.1.4 |
|
oupsOutputLoadPerPhasemandatory
The UPS output load per phase in percentage of rated capacity.
|
Integer32 Constraints: range: 0-200 |
.1.3.6.1.4.1.232.165.6.4.4.1.5 |
.1.3.6.1.4.1.232.165.7.1.2
·
1 row entry
·
12 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2IdentTable'
Aggregate Object with number of entries equal to pdu2NumberPDU .
The ident table entry containing the name, model, manufacturer,
firmware version, part number, etc.
firmware version, part number, etc.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
pdu2IdentIndexmandatory
Index for the Pdu2IdentEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.7.1.2.1.1 |
||||||||
|
pdu2Namemandatory
The string identify the device in daisy chain. Example PDU A.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.2 |
||||||||
|
pdu2Modelmandatory
The Device Model.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.3 |
||||||||
|
pdu2Manufacturermandatory
The Device Manufacturer Name (e.g. Hewlett-Packard).
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.4 |
||||||||
|
pdu2FirmwareVersionmandatory
The firmware revision level of the device.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.5 |
||||||||
|
pdu2PartNumbermandatory
The device part number. Example AF400A.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.6 |
||||||||
|
pdu2SerialNumbermandatory
The device serial number, 10- or 16-digit.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.7 |
||||||||
|
pdu2Statusmandatory
The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of failed(4) indicates the devic… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.1.2.1.8 |
||||||||
|
pdu2Controllablemandatory
This object indicates whether or not the device is controllable.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.1.2.1.9 |
||||||||
|
pdu2InputPhaseCountmandatory
The number of input phase on this pdu 1,2,3.
|
Integer32 Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.10 |
||||||||
|
pdu2GroupCountmandatory
The number of groups (breakers) on this pdu.
|
Integer32 Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.11 |
||||||||
|
pdu2OutletCountmandatory
The number of outlets in this PDU.
|
Integer32 Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.1.2.1.12 |
.1.3.6.1.4.1.232.165.7.2.1
·
1 row entry
·
9 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2InputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2InputTable'
Aggregate Object with number of entries equal to pdu2NumberPDU .
The ident table entry containing the VA, Watts, WH, etc.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
pdu2InputTypemandatory
Type of input - single phase, split phase, three phase delta, or three
phase wye. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.2.1.1.1 |
||||||||
|
pdu2InputFrequencymandatory
The measured input frequency from the PDU meters in tenths of Hz.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.7.2.1.1.2 |
||||||||
|
pdu2InputFrequencyStatusmandatory
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.2.1.1.3 |
||||||||
|
pdu2InputPowerVAmandatory
A total input VA of all phases. Units are VA. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.1.1.4 |
||||||||
|
pdu2InputPowerWattsmandatory
A total input Watts of all phases. Units are Watts. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.1.1.5 |
||||||||
|
pdu2InputPowerWattHourmandatory
A total input Watt-Hour value for all phases. Units are WH. This value can be reset to 0
using GUI. In that case, the pdu2InputPowerWattHourTimer will be reset as well A negative value indicates that this object is … |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.1.1.6 |
||||||||
|
pdu2InputPowerWattHourTimermandatory
A Timestamp of when the Total Input WH was last reset.
|
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.232.165.7.2.1.1.7 |
||||||||
|
pdu2InputPowerFactormandatory
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.1.1.8 |
||||||||
|
pdu2InputPowerVARmandatory
An input VAR value. Units are VAR. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.1.1.9 |
.1.3.6.1.4.1.232.165.7.2.2
·
1 row entry
·
25 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2InputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2InputPhaseTable'
Aggregate Object with number of entries equal to number of PDUs (pdu2NumberPDU) and number of input phase (pdu2InputPhaseCount).
The input table entry containing the voltage, current, frequency, power for each phase.
Entries are given with number of pdu and number of input phase 1, 2, or 3.
Entries are given with number of pdu and number of input phase 1, 2, or 3.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu2InputPhaseIndexmandatory
Index for the Pdu2InputEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.7.2.2.1.1 |
||||||||||||||
|
pdu2InputPhaseVoltageMeasTypemandatory
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.2.2.1.2 |
||||||||||||||
|
pdu2InputPhaseVoltagemandatory
An input voltage measurement value. Units are millivolts.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.3 |
||||||||||||||
|
pdu2InputPhaseVoltageThStatusmandatory
Status of the measured input voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.2.2.1.4 |
||||||||||||||
|
pdu2InputPhaseVoltageThLowerWarningmandatory
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.7.2.2.1.5 |
||||||||||||||
|
pdu2InputPhaseVoltageThLowerCriticalmandatory
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.7.2.2.1.6 |
||||||||||||||
|
pdu2InputPhaseVoltageThUpperWarningmandatory
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.7.2.2.1.7 |
||||||||||||||
|
pdu2InputPhaseVoltageThUpperCriticalmandatory
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.7.2.2.1.8 |
||||||||||||||
|
pdu2InputPhaseCurrentMeasTypemandatory
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.2.2.1.9 |
||||||||||||||
|
pdu2InputPhaseCurrentRatingmandatory
Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are milliamps. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.10 |
||||||||||||||
|
pdu2InputPhaseCurrentmandatory
An input current measurement value. Units are milliamps.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.11 |
||||||||||||||
|
pdu2InputPhaseCurrentThStatusmandatory
Status of the measured input current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.2.2.1.12 |
||||||||||||||
|
pdu2InputPhaseCurrentThLowerWarningmandatory
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.2.2.1.13 |
||||||||||||||
|
pdu2InputPhaseCurrentThLowerCriticalmandatory
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.2.2.1.14 |
||||||||||||||
|
pdu2InputPhaseCurrentThUpperWarningmandatory
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.2.2.1.15 |
||||||||||||||
|
pdu2InputPhaseCurrentThUpperCriticalmandatory
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.2.2.1.16 |
||||||||||||||
|
pdu2InputPhaseCurrentCrestFactormandatory
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.17 |
||||||||||||||
|
pdu2InputPhaseCurrentPercentLoadmandatory
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.18 |
||||||||||||||
|
pdu2InputPhasePowerMeasTypemandatory
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.2.2.1.19 |
||||||||||||||
|
pdu2InputPhasePowerVAmandatory
An input VA value. Units are VA. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.20 |
||||||||||||||
|
pdu2InputPhasePowerWattsmandatory
An input Watts value. Units are Watts. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.21 |
||||||||||||||
|
pdu2InputPhasePowerWattHourmandatory
A Watt-Hour value for each Input phase. Units are WH. This value can be reset to 0
using GUI. In that case, the pdu2InputPhasePowerWattHourTimer will be reset as well A negative value indicates that this object is… |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.22 |
||||||||||||||
|
pdu2InputPhasePowerWattHourTimermandatory
Timestamp of when input Watt-hours (inputWh) was last reset.
|
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.232.165.7.2.2.1.23 |
||||||||||||||
|
pdu2InputPhasePowerFactormandatory
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.24 |
||||||||||||||
|
pdu2InputPhasePowerVARmandatory
An input VAR value. Units are VAR. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.2.2.1.25 |
.1.3.6.1.4.1.232.165.7.3.1
·
1 row entry
·
27 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2GroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2GroupTable'
Aggregate Object with number of entries equal to number of PDUs and number of breakers (pdu2GroupCount).
The input table entry containing the name, voltages, currents, power, etc.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu2GroupIndexmandatory
Index for the Pdu2GroupEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.7.3.1.1.1 |
||||||||||||||
|
pdu2GroupNamemandatory
A descriptive name for the group.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.7.3.1.1.2 |
||||||||||||||
|
pdu2GroupTypemandatory
The type of the group. (5) has no breaker
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.3.1.1.3 |
||||||||||||||
|
pdu2GroupVoltageMeasTypemandatory
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.3.1.1.4 |
||||||||||||||
|
pdu2GroupVoltagemandatory
Units are millivolts.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.5 |
||||||||||||||
|
pdu2GroupVoltageThStatusmandatory
Status of the measured group voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.3.1.1.6 |
||||||||||||||
|
pdu2GroupVoltageThLowerWarningmandatory
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.7.3.1.1.7 |
||||||||||||||
|
pdu2GroupVoltageThLowerCriticalmandatory
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.7.3.1.1.8 |
||||||||||||||
|
pdu2GroupVoltageThUpperWarningmandatory
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.7.3.1.1.9 |
||||||||||||||
|
pdu2GroupVoltageThUpperCriticalmandatory
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.7.3.1.1.10 |
||||||||||||||
|
pdu2groupCurrentRatingmandatory
Rated current capacity of the group. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups). |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.11 |
||||||||||||||
|
pdu2GroupCurrentmandatory
A group current measurement value. Units are milliamps.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.12 |
||||||||||||||
|
pdu2GroupCurrentThStatusmandatory
Status of the measured group current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.3.1.1.13 |
||||||||||||||
|
pdu2GroupCurrentThLowerWarningmandatory
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.3.1.1.14 |
||||||||||||||
|
pdu2GroupCurrentThLowerCriticalmandatory
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.3.1.1.15 |
||||||||||||||
|
pdu2GroupCurrentThUpperWarningmandatory
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.3.1.1.16 |
||||||||||||||
|
pdu2GroupCurrentThUpperCriticalmandatory
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.3.1.1.17 |
||||||||||||||
|
pdu2GroupCurrentCrestFactormandatory
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.18 |
||||||||||||||
|
pdu2GroupCurrentPercentLoadmandatory
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.19 |
||||||||||||||
|
pdu2GroupPowerVAmandatory
A group VA value. Units are VA. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.20 |
||||||||||||||
|
pdu2GroupPowerWattsmandatory
A group Watts value. Units are Watts. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.21 |
||||||||||||||
|
pdu2GroupPowerWattHourmandatory
A Watt-Hour value for each section. Units are WH. This value can be reset to 0
using GUI. In that case, the pdu2GroupPowerWattHourTimer will be reset as well. A negative value indicates that this object is not ava… |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.22 |
||||||||||||||
|
pdu2GroupPowerWattHourTimermandatory
Timestamp of when group Watt-hours (groupWh) was last reset.
|
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.232.165.7.3.1.1.23 |
||||||||||||||
|
pdu2GroupPowerFactormandatory
A group PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.24 |
||||||||||||||
|
pdu2GroupPowerVARmandatory
A group VAR value. Units are VAR. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.3.1.1.25 |
||||||||||||||
|
pdu2GroupOutletCountmandatory
The number of outlets in each group (breaker).
|
Integer32 Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.7.3.1.1.26 |
||||||||||||||
|
pdu2GroupBreakerStatusmandatory
Only applicable to groups with breaker. Indicates whether a breaker is turned
off or on. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.3.1.1.27 |
.1.3.6.1.4.1.232.165.7.4.1
·
1 row entry
·
4 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2EnvProbeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2EnvProbeTable'
A list of environment probe (1 per PDU) for temperature, humidity, and contacts. The number of entries is given by number of PDUs in daisy chain.
Aggregate entries equal to number of PDUs.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
pdu2TemperatureScalemandatory
Scale used to return temperature objects.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.4.1.1.1 |
||||
|
pdu2TemperatureCountmandatory
Max number of temperature measurements (1 per probe).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.4.1.1.2 |
||||
|
pdu2HumidityCountmandatory
Max number of humidity measurements (1 per probe).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.4.1.1.3 |
||||
|
pdu2ContactCountmandatory
Max number of contact sensors (1 per probe).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.4.1.1.4 |
.1.3.6.1.4.1.232.165.7.4.2
·
1 row entry
·
9 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2TemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2TemperatureTable'
A list of temperature probe measurements. The number of entries are given by number of pdu and pdu2TemperatureCount.
An entry for a temperature measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu2TemperatureIndexmandatory
A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.232.165.7.4.2.1.1 |
||||||||||
|
pdu2TemperatureNamemandatory
A descriptive name for the temperature probe.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.7.4.2.1.2 |
||||||||||
|
pdu2TemperatureProbeStatusmandatory
Indicates whether a probe is connected or not.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.4.2.1.3 |
||||||||||
|
pdu2TemperatureValuemandatory
Units are in tenths of a degree (either Fahrenheit or Celsius).
Divide by ten to get degrees. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.4.2.1.4 |
||||||||||
|
pdu2TemperatureThStatusmandatory
Status of the measured temperature relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.4.2.1.5 |
||||||||||
|
pdu2TemperatureThLowerWarningmandatory
Lower warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-150000 |
.1.3.6.1.4.1.232.165.7.4.2.1.6 |
||||||||||
|
pdu2TemperatureThLowerCriticalmandatory
Lower critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-150000 |
.1.3.6.1.4.1.232.165.7.4.2.1.7 |
||||||||||
|
pdu2TemperatureThUpperWarningmandatory
Upper warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-150000 |
.1.3.6.1.4.1.232.165.7.4.2.1.8 |
||||||||||
|
pdu2TemperatureThUpperCriticalmandatory
Upper critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-150000 |
.1.3.6.1.4.1.232.165.7.4.2.1.9 |
.1.3.6.1.4.1.232.165.7.4.3
·
1 row entry
·
9 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2HumidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2HumidityTable'
A list of humidity probe measurements. The number of entries are given by number of pdu and pdu2HumidityCount.
An entry for a humidity measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu2HumidityIndexmandatory
A unique value for each humidity probe measurement. Its value
ranges from 1 to pdu2HumidityCount per pdu. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.232.165.7.4.3.1.1 |
||||||||||
|
pdu2HumidityNamemandatory
A descriptive name for the humidity probe.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.7.4.3.1.2 |
||||||||||
|
pdu2HumidityProbeStatusmandatory
Indicates whether a probe is connected or not.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.4.3.1.3 |
||||||||||
|
pdu2HumidityValuemandatory
Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.4.3.1.4 |
||||||||||
|
pdu2HumidityThStatusmandatory
Status of the measured humidity relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.4.3.1.5 |
||||||||||
|
pdu2HumidityThLowerWarningmandatory
Lower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-1000 |
.1.3.6.1.4.1.232.165.7.4.3.1.6 |
||||||||||
|
pdu2HumidityThLowerCriticalmandatory
Lower critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-1000 |
.1.3.6.1.4.1.232.165.7.4.3.1.7 |
||||||||||
|
pdu2HumidityThUpperWarningmandatory
Upper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-1000 |
.1.3.6.1.4.1.232.165.7.4.3.1.8 |
||||||||||
|
pdu2HumidityThUpperCriticalmandatory
Upper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-1000 |
.1.3.6.1.4.1.232.165.7.4.3.1.9 |
.1.3.6.1.4.1.232.165.7.4.4
·
1 row entry
·
4 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2ContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2ContactTable'
A list of contact sensors. The number of entries are given by number of pdu and pdu2ContactCount.
An entry for a contact sensor
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
pdu2ContactIndexmandatory
A unique value for each contact sensor. Its value ranges from 1 to
contactCount. |
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.232.165.7.4.4.1.1 |
||||||
|
pdu2ContactNamemandatory
A descriptive name for the contact sensor.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.7.4.4.1.2 |
||||||
|
pdu2ContactProbeStatusmandatory
Indicates whether a probe is connected or not.
Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be read. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.4.4.1.3 |
||||||
|
pdu2ContactStatemandatory
The state of the contact sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.4.4.1.4 |
.1.3.6.1.4.1.232.165.7.5.1
·
1 row entry
·
18 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2OutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2OutletTable'
Aggregate Object with number of entries equal to Number of PDU (pdu2IdentIndex) and Number of outlet per PDU (pdu2OutletIndex).
The Outlet table entry containing the type, voltage, current etc.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu2OutletIndexmandatory
Index for each outlet, value from 1 to the number of outlets per PDU.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.7.5.1.1.1 |
||||||||||||||||||||||||||||||||
|
pdu2OutletNamemandatory
A descriptive name for the outlet.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.7.5.1.1.2 |
||||||||||||||||||||||||||||||||
|
pdu2OutletTypemandatory
Type of this outlet - C13, C19.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.5.1.1.3 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentRatingmandatory
Rated current capacity of this outlet. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.4 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentmandatory
A outlet current measurement value. Units are milliamps.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.5 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentThStatusmandatory
Status of the measured outlet current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.5.1.1.6 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentThLowerWarningmandatory
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.5.1.1.7 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentThLowerCriticalmandatory
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.5.1.1.8 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentThUpperWarningmandatory
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.5.1.1.9 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentThUpperCriticalmandatory
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.7.5.1.1.10 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentCrestFactormandatory
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.11 |
||||||||||||||||||||||||||||||||
|
pdu2OutletCurrentPercentLoadmandatory
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.12 |
||||||||||||||||||||||||||||||||
|
pdu2OutletVAmandatory
A outlet VA value. Units are VA. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.13 |
||||||||||||||||||||||||||||||||
|
pdu2OutletWattsmandatory
A outlet Watts value. Units are Watts. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.14 |
||||||||||||||||||||||||||||||||
|
pdu2OutletWhmandatory
A Watt-Hour value for each outlet. Units are WH.
This object is writable so that it can be reset to 0. When it is written to, the pdu2OutletWhTimer will be reset updated as well A negative value indicates that thi… |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.15 |
||||||||||||||||||||||||||||||||
|
pdu2OutletWhTimermandatory
Timestamp (date and time) of outlet Watt-hours was last reset.
|
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.232.165.7.5.1.1.16 |
||||||||||||||||||||||||||||||||
|
pdu2OutletPowerFactormandatory
An outlet PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.17 |
||||||||||||||||||||||||||||||||
|
pdu2OutletVARmandatory
An outlet VAR value. Units are VAR. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.7.5.1.1.18 |
.1.3.6.1.4.1.232.165.7.5.2
·
1 row entry
·
9 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu2OutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu2OutletControlTable'
Aggregate Object with number of entries equal to Number of PDU (pdu2IdentIndex) and Number of outlets per PDU (pdu2OutletIndex).
The Outlet table entry containing the type, voltage, current etc.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
pdu2OutletControlStatusmandatory
current state of a control outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.5.2.1.1 |
||||||||
|
pdu2OutletControlOffCmdmandatory
When write, once issued, the outlet will turn Off immediately.
0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet Off command When read, returns -1 if no command is pending, or the curr… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.7.5.2.1.2 |
||||||||
|
pdu2OutletControlOnCmdmandatory
When write, once issued, the outlet will turn On immediately.
0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet On command When read, returns -1 if no command is pending, or the curren… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.7.5.2.1.3 |
||||||||
|
pdu2OutletControlRebootCmdmandatory
When write, for outlets that are On prior to this Reboot command, they will
switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets tha… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.7.5.2.1.4 |
||||||||
|
pdu2OutletControlPowerOnStatemandatory
Determines the outlet state when power is applied to the unit.
1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequenceTime 3 : should take the state the outlet had when power was… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.5.2.1.5 |
||||||||
|
pdu2OutletControlSequenceDelaymandatory
Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on delay. Set to -1 to exclude this outlet from Global Sequence … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.7.5.2.1.6 |
||||||||
|
pdu2OutletControlRebootOffTimemandatory
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
|
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.7.5.2.1.7 |
||||||||
|
pdu2OutletControlSwitchablemandatory
Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled 2 : control On/Off disabled. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.7.5.2.1.8 |
||||||||
|
pdu2OutletControlShutoffDelaymandatory
Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first then write it to the command pdu2OutletControlOf… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.7.5.2.1.9 |
.1.3.6.1.4.1.232.165.9.1.2
·
1 row entry
·
17 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk hpduIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::hpduIdentTable'
Indexed by 1 Hpdu unit.
The table entry containing the identifications of HPDU
Indexes
| Column | Syntax | OID |
|---|---|---|
|
hpduIdentIndexmandatory
Index for the MpduIdentEntry table. Start with 1
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.9.1.2.1.1 |
|
hpduManufacturermandatory
The Core PDU manufacturer. StringLength=[21]
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.2 |
|
hpduModelmandatory
The Core PDU model, marketing name. StringLength=[40].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.3 |
|
hpduNamemandatory
The Core PDU name, descriptive name or hostname. StringLength=[16].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.4 |
|
hpduFirmwareVersionmandatory
The Core PDU firmware version(s). StringLength=[12].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.5 |
|
hpduHardwareVersionmandatory
The Core PDU hardware version. StringLength=[8].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.6 |
|
hpduPartNumbermandatory
The Core PDU part number. StringLength=[21].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.7 |
|
hpduSerialNumbermandatory
The PDU external serial number. StringLength=[21].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.8 |
|
hpduUUIDmandatory
The PDU's UUID equals PN add SN, canonical conversion. StringLength=[37].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.9 |
|
hpduTypemandatory
The PDU's Type: Delta, Wye, single, Wye+lowline.
StringLength=[24]. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.10 |
|
hpduPowerRatingmandatory
The PDU's Power Rating in KVA (Name Plate). Value is presented
in 1/100 of the KVA. i.e. 1750 means 17.50 KVA |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.11 |
|
hpduInputRatingmandatory
The PDU's Input Current Rating in A (Name Plate)
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.12 |
|
hpduRegionalNominalVoltagemandatory
value is either America(208V), Japan(202V) or blank for International Model
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.13 |
|
hpduNumOutputBreakersmandatory
The number of outlets with breakers of each hpdu.
|
Integer32 Constraints: range: 0-10 |
.1.3.6.1.4.1.232.165.9.1.2.1.14 |
|
hpduNumMonitoredOutletmandatory
The number of measured outlets (with CT, VT) of each hpdu.
|
Integer32 Constraints: range: 0-10 |
.1.3.6.1.4.1.232.165.9.1.2.1.15 |
|
hpduFanStatusmandatory
Report fan status: OK or FAIL
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.1.2.1.16 |
|
hpduTemperaturemandatory
The internal temperature in Celcius. Value is presented in 1/10 of a degree i.e. 251 is 25.1. A value
of -1 will be returned if the temperature is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.1.2.1.17 |
.1.3.6.1.4.1.232.165.9.2.1
·
1 row entry
·
13 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk hpduInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::hpduInputTable'
Indexed by hpduNumPhase.
The Input table entry containing the voltage, current, PF,
percent load, VA, Watts for the HPDU.
percent load, VA, Watts for the HPDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
hpduInputIndexmandatory
Index for the hpduInputEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.9.2.1.1.1 |
|
hpduInputStatusmandatory
The overall status of the Input: off, on, problem. StringLength=[7].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.2.1.1.2 |
|
hpduInputBreakerRatingmandatory
The rating of each hpdu Input in Ampere.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.3 |
|
hpduInputVoltagemandatory
The measured Input voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value of -1 will be returned if the voltage is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.4 |
|
hpduInputCurrentmandatory
The measured Input current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value of -1 will be returned if the current is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.5 |
|
hpduInputPowerVAmandatory
The total Input Power measured in VA. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.6 |
|
hpduInputPowerWattmandatory
The total Input power measured in Watts. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.7 |
|
hpduInputPowerFactormandatory
The Input power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.8 |
|
hpduInputWarningThresholdmandatory
Report the User-setting Input threshhold limit for Warning in percentage
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.9 |
|
hpduInputCriticalThresholdmandatory
Report the User-setting Input threshhold limit for Critical in percentage
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.10 |
|
hpduInputPowerWattHourmandatory
Support Billing Grade Energy Metering in Watt-Hour. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.11 |
|
hpduInputTotalEnergySincemandatory
Display the date and time that starts to accumulate the per Load segment energy in WH.
Date and Time can be set by user on GUI. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.2.1.1.12 |
|
hpduInputEnergyMeteringTotalHoursmandatory
Total hours of collecting measurement data. A value
of -1 will be returned if the value is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.2.1.1.13 |
.1.3.6.1.4.1.232.165.9.3.1
·
1 row entry
·
14 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk hpduOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::hpduOutletTable'
Indexed by hpduNumMonitoredOutlet and hpduNumPhase . So aggregate objects for each entry equal to (hpduNumMonitoredOutlet x hpduNumPhase). Start with 1.
The Outlet table entry containing the voltage, current, PF,
percent load, VA, Watts for the Modular PDU.
percent load, VA, Watts for the Modular PDU.
| Column | Syntax | OID |
|---|---|---|
|
hpduOutletIndexmandatory
Index for the hpduOutletEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.9.3.1.1.1 |
|
hpduOutletStatusmandatory
The overall status of the breaker: off, on, problem. StringLength=[7].
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.3.1.1.2 |
|
hpduOutletBreakerRatingmandatory
The rating of each hpdu Outlet in Ampere.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.3 |
|
hpduOutletPercentLoadmandatory
The hpdu's each Outlet load in percent of rated capacity. Value is
presented in 1/10 of the percentage i.e. 125 is 12.5%. A value of -1 will be returned if the current is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.4 |
|
hpduOutletVoltagemandatory
The measured Outlet voltage from the PDU meters in volts. Value is
presented in 1/10 of the Volt i.e. 2095 is 209.5 V. A value of -1 will be returned if the voltage is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.5 |
|
hpduOutletCurrentmandatory
The measured Outlet current from the PDU meters in amps. Value is
presented in 1/100 of the Ampere i.e. 175 is 1.75 A. A value of -1 will be returned if the current is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.6 |
|
hpduOutletPowerVAmandatory
The total VA load (VI) measured on the PDU in VA. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.7 |
|
hpduOutletPowerWattmandatory
The total power load measured on the PDU in Watts. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.8 |
|
hpduOutletPowerFactormandatory
The power factor is presented in 1/100 of the unit i.e.
98 is 0.98. A value of -1 will be returned if the power factor is unable to be measured. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.9 |
|
hpduOutletWarningThresholdmandatory
Report the User-set threshhold limit for Warning in percentage
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.10 |
|
hpduOutletCriticalThresholdmandatory
Report the User-set threshhold limit for Critical in percentage
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.11 |
|
hpduOutletPowerWattHourmandatory
Support Billing Grade Energy Metering in Watt-Hour. A value
of -1 will be returned if the power is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.12 |
|
hpduOutletTotalEnergySincemandatory
Display the date and time that starts to accumulate the per Load segment energy in WH.
Date and Time can be set by user on GUI. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.9.3.1.1.13 |
|
hpduOutletEnergyMeteringTotalHoursmandatory
Total hours of collecting measurement data. A value
of -1 will be returned if the value is unable to be calculated. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.9.3.1.1.14 |
.1.3.6.1.4.1.232.165.11.1.2
·
1 row entry
·
16 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3IdentTable'
Aggregate Object with number of entries equal to pdu3NumberPDU .
The ident table entry containing the name, model, manufacturer,
firmware version, part number, etc.
firmware version, part number, etc.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
pdu3IdentIndexmandatory
Index for the Pdu3IdentEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.11.1.2.1.1 |
||||||||
|
pdu3Namemandatory
The string identify the device in daisy chain. Example PDU A.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.2 |
||||||||
|
pdu3Modelmandatory
The Device Model.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.3 |
||||||||
|
pdu3Manufacturermandatory
The Device Manufacturer Name (e.g. Hewlett-Packard).
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.4 |
||||||||
|
pdu3FirmwareVersionmandatory
The firmware revision level of the device.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.5 |
||||||||
|
pdu3FirmwareVersionTimeStampmandatory
Timestamp of when the PDU firmware was last updated
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.11.1.2.1.6 |
||||||||
|
pdu3PartNumbermandatory
The device part number. Example AF400A.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.7 |
||||||||
|
pdu3SerialNumbermandatory
The device serial number, 10- or 16-digit.
|
OctetString Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.8 |
||||||||
|
pdu3Statusmandatory
The overall status of the device. A value of OK(2) indicates the device is operating normally.
A value of degraded(3) indicates the device is operating with warning indicators. A value of failed(4) indicates the devic… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.2.1.9 |
||||||||
|
pdu3Controllablemandatory
This object indicates whether or not the device is controllable.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.2.1.10 |
||||||||
|
pdu3InputPhaseCountmandatory
The number of input phase on this pdu 1,2,3.
|
Integer32 Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.11 |
||||||||
|
pdu3GroupCountmandatory
The number of groups (breakers) on this pdu.
|
Integer32 Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.12 |
||||||||
|
pdu3OutletCountmandatory
The number of outlets in this PDU.
|
Integer32 Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.1.2.1.13 |
||||||||
|
pdu3MACAddressmandatory
The assigned MAC address for this PDU.
|
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.11.1.2.1.14 |
||||||||
|
pdu3IPv4Addressmandatory
The current IPv4 Address.
A value of 0.0.0.0 indicates an error or an unset option. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.11.1.2.1.15 |
||||||||
|
pdu3IPv6Addressmandatory
The current IPv6 Address.
A vale of 0.0.0.0.0.0 indicates an error or an unset option. |
RFC1213-MIBDisplayString | .1.3.6.1.4.1.232.165.11.1.2.1.16 |
.1.3.6.1.4.1.232.165.11.1.3
·
1 row entry
·
11 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3ConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3ConfigTable'
Aggregate Object with number of entries equal to pdu3NumberPDU .
Read Configuration data from the PDU being queried.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
pdu3ConfigIndexmandatory
The index of PDU configuration entry.
|
Integer32 Constraints: range: 0-20 |
.1.3.6.1.4.1.232.165.11.1.3.1.1 |
||||||
|
pdu3ConfigSshmandatory
Setting this OID to off(0) will disable the SSH conneciton.
Setting this OID to on(1) will enable the SSH connection. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.2 |
||||||
|
pdu3ConfigFtpsmandatory
Setting this OID to off(0) will disable the FTPS connection.
Setting this OID to on(1) will enable the FTPS connection. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.3 |
||||||
|
pdu3ConfigHttpmandatory
Setting this OID to off(0) will disable the HTTP connection.
Setting this OID to on(1) will enable the HTTP connection. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.4 |
||||||
|
pdu3ConfigHttpsmandatory
Setting this OID to off(0) will disable the HTTPS connection.
Setting this OID to on(1) will enable the HTTPS connection. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.5 |
||||||
|
pdu3ConfigIPv4IPv6Switchmandatory
Setting this OID to IPv4(1) will enable the IPv4 configuration.
Setting this OID to IPv6(2) will enable the IPv6 configuration. Setting this OID to IPv4&IPv6(3) will enable both IPv4 and IPv6 configuration. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.6 |
||||||
|
pdu3ConfigRedfishAPImandatory
Setting this OID to off(0) will disable the Redfish API.
Setting this OID to on(1) will enable the Redfish API. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.7 |
||||||
|
pdu3ConfigOledDispalyOrientationmandatory
Indicates the intended physical orientation of OLED display.
displayNormal(1) indicates normal orientation. displayReverse(2) indicates upside down orientation. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.8 |
||||||
|
pdu3ConfigEnergyResetmandatory
Setting this OID to reset(2) will cause the device energy meter value
to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not su… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.9 |
||||||
|
pdu3ConfigNetworkManagementCardResetmandatory
Getting this OID will return noOperation(0).
Getting this OID to reset(1) will reset NMC. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.10 |
||||||
|
pdu3ConfigDaisyChainStatusmandatory
Setting this OID to daisychain(0) will enable daisychain mode.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.1.3.1.11 |
.1.3.6.1.4.1.232.165.11.2.1
·
1 row entry
·
10 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3InputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3InputTable'
Aggregate Object with number of entries equal to pdu3NumberPDU .
The ident table entry containing the VA, Watts, WH, etc.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
pdu3InputTypemandatory
Type of input - single phase, split phase, three phase delta, or three
phase wye. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.2.1.1.1 |
||||||||
|
pdu3InputFrequencymandatory
The measured input frequency from the PDU meters in tenths of Hz.
|
Integer32 Constraints: range: 0-2147483647 |
.1.3.6.1.4.1.232.165.11.2.1.1.2 |
||||||||
|
pdu3InputFrequencyStatusmandatory
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.2.1.1.3 |
||||||||
|
pdu3InputPowerVAmandatory
A total input VA of all phases. Units are 0.001 VA. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.1.1.4 |
||||||||
|
pdu3InputPowerWattsmandatory
A total input Watts of all phases. Units are 0.001 Watts. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.1.1.5 |
||||||||
|
pdu3InputTotalEnergymandatory
A total input Watt-Hour value for all phases. Units are KWh. This value is accumulated since PDU in service.
A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.1.1.6 |
||||||||
|
pdu3InputPowerWattHourTimermandatory
A Timestamp of when the Total Input WH was last reset.
|
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.232.165.11.2.1.1.7 |
||||||||
|
pdu3InputResettableEnergymandatory
A total input Watt-Hour value for all phases. Units are 0.001 Wh. This value can be reset to 0
using GUI. In that case, the pdu3InputPowerWattHourTimer will be reset as well A negative value indicates that this obje… |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.1.1.8 |
||||||||
|
pdu3InputPowerFactormandatory
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.1.1.9 |
||||||||
|
pdu3InputPowerVARmandatory
An input VAR value. Units are 0.001 VAR. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.1.1.10 |
.1.3.6.1.4.1.232.165.11.2.2
·
1 row entry
·
24 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3InputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3InputPhaseTable'
Aggregate Object with number of entries equal to number of PDUs (pdu3NumberPDU) and number of input phase (pdu3InputPhaseCount).
The input table entry containing the voltage, current, frequency, power for each phase.
Entries are given with number of pdu and number of input phase 1, 2, or 3.
Entries are given with number of pdu and number of input phase 1, 2, or 3.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu3InputPhaseIndexmandatory
Index for the Pdu3InputEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.11.2.2.1.1 |
||||||||||||||
|
pdu3InputPhaseVoltageMeasTypemandatory
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.2.2.1.2 |
||||||||||||||
|
pdu3InputPhaseVoltagemandatory
An input voltage measurement value. Return value is divided by 10.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.3 |
||||||||||||||
|
pdu3InputPhaseVoltageThStatusmandatory
Status of the measured input voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.2.2.1.4 |
||||||||||||||
|
pdu3InputPhaseVoltageThLowerWarningmandatory
Lower warning threshold. Return value is divided by 10. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.11.2.2.1.5 |
||||||||||||||
|
pdu3InputPhaseVoltageThLowerCriticalmandatory
Lower critical threshold. Return value is divided by 10. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.11.2.2.1.6 |
||||||||||||||
|
pdu3InputPhaseVoltageThUpperWarningmandatory
Upper warning threshold. Return value is divided by 10. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.11.2.2.1.7 |
||||||||||||||
|
pdu3InputPhaseVoltageThUpperCriticalmandatory
Upper critical threshold. Return value is divided by 10. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.11.2.2.1.8 |
||||||||||||||
|
pdu3InputPhaseCurrentMeasTypemandatory
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.2.2.1.9 |
||||||||||||||
|
pdu3InputPhaseCurrentRatingmandatory
Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Return value is divided by 100. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.10 |
||||||||||||||
|
pdu3InputPhaseCurrentmandatory
An input current measurement value. Return value is divided by 100.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.11 |
||||||||||||||
|
pdu3InputPhaseCurrentThStatusmandatory
Status of the measured input current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.2.2.1.12 |
||||||||||||||
|
pdu3InputPhaseCurrentThLowerWarningmandatory
Lower warning threshold. Return value is divided by 100. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.11.2.2.1.13 |
||||||||||||||
|
pdu3InputPhaseCurrentThLowerCriticalmandatory
Lower critical threshold. Return value is divided by 100. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.11.2.2.1.14 |
||||||||||||||
|
pdu3InputPhaseCurrentThUpperWarningmandatory
Upper warning threshold. Return value is divided by 100. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.11.2.2.1.15 |
||||||||||||||
|
pdu3InputPhaseCurrentThUpperCriticalmandatory
Upper critical threshold. Return value is divided by 100. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.11.2.2.1.16 |
||||||||||||||
|
pdu3InputPhaseCurrentPercentLoadmandatory
Current percent load, based on the rated current capacity. Units are
percentage, for example 80.9 % will be returned as 809. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.17 |
||||||||||||||
|
pdu3InputPhasePowerMeasTypemandatory
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.2.2.1.18 |
||||||||||||||
|
pdu3InputPhasePowerVAmandatory
An input VA value. Units are VA. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.19 |
||||||||||||||
|
pdu3InputPhasePowerWattsmandatory
An input Watts value. Units are Watts. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.20 |
||||||||||||||
|
pdu3InputPhasePowerWattHourmandatory
A kWatt-Hour value for each Input phase. Units are kWh. This value can be reset to 0
using GUI. In that case, the pdu3InputPhasePowerWattHourTimer will be reset as well A negative value indicates that this object … |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.21 |
||||||||||||||
|
pdu3InputPhasePowerWattHourTimermandatory
Timestamp of when input phase kWatt-hours (kWh) was last reset.
|
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.232.165.11.2.2.1.22 |
||||||||||||||
|
pdu3InputPhasePowerFactormandatory
An input PF value. Return value is divided by 100, for example a power factor
of 0.95 would be returned as 95. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.23 |
||||||||||||||
|
pdu3InputPhasePowerVARmandatory
An input VA Reactive value. Units are in VAR. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.2.2.1.24 |
.1.3.6.1.4.1.232.165.11.3.1
·
1 row entry
·
26 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3GroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3GroupTable'
Aggregate Object with number of entries equal to number of PDUs and number of breakers (pdu3GroupCount).
The input table entry containing the name, voltages, currents, power, etc.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu3GroupIndexmandatory
Index for the Pdu3GroupEntry table.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.11.3.1.1.1 |
||||||||||||||
|
pdu3GroupNamemandatory
A descriptive name for the group.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.11.3.1.1.2 |
||||||||||||||
|
pdu3GroupTypemandatory
The type of the group. (5) has no breaker
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.3.1.1.3 |
||||||||||||||
|
pdu3GroupVoltageMeasTypemandatory
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.3.1.1.4 |
||||||||||||||
|
pdu3GroupVoltagemandatory
Return value is divided by 10 to get one decimal point, unit is in Volt.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.5 |
||||||||||||||
|
pdu3GroupVoltageThStatusmandatory
Status of the measured group voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.3.1.1.6 |
||||||||||||||
|
pdu3GroupVoltageThLowerWarningmandatory
Lower warning threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.11.3.1.1.7 |
||||||||||||||
|
pdu3GroupVoltageThLowerCriticalmandatory
Lower critical threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.11.3.1.1.8 |
||||||||||||||
|
pdu3GroupVoltageThUpperWarningmandatory
Upper warning threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.11.3.1.1.9 |
||||||||||||||
|
pdu3GroupVoltageThUpperCriticalmandatory
Upper critical threshold. Return value is divided by 10 to get one decimal point,
unit is in Volt. A negative value indicates that this object is not available. |
Integer32 Constraints: range: -1-500000 |
.1.3.6.1.4.1.232.165.11.3.1.1.10 |
||||||||||||||
|
pdu3groupCurrentRatingmandatory
Rated current capacity of the group. Return value is divided by 100 to get two decimal points,
unit is in Amps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown for… |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.11 |
||||||||||||||
|
pdu3GroupCurrentmandatory
A group current measurement value. Return value is divided by 100 to get two decimal points.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.12 |
||||||||||||||
|
pdu3GroupCurrentThStatusmandatory
Status of the measured group current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.3.1.1.13 |
||||||||||||||
|
pdu3GroupCurrentThLowerWarningmandatory
Lower warning threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.11.3.1.1.14 |
||||||||||||||
|
pdu3GroupCurrentThLowerCriticalmandatory
Lower critical threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.11.3.1.1.15 |
||||||||||||||
|
pdu3GroupCurrentThUpperWarningmandatory
Upper warning threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.11.3.1.1.16 |
||||||||||||||
|
pdu3GroupCurrentThUpperCriticalmandatory
Upper critical threshold. Return value is divided by 100 to get two decimal points. A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-100000 |
.1.3.6.1.4.1.232.165.11.3.1.1.17 |
||||||||||||||
|
pdu3GroupCurrentPercentLoadmandatory
Current percent load, based on the rated current capacity. Units are
percentage, for example 80.9 % will be returned as 809. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.18 |
||||||||||||||
|
pdu3GroupPowerVAmandatory
A group VA value. Units are VA. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.19 |
||||||||||||||
|
pdu3GroupPowerWattsmandatory
A group power value. Units are Watts. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.20 |
||||||||||||||
|
pdu3GroupPowerWattHourmandatory
An energy consumption value for each load segment. Units are kWh. This value can be reset to 0
using GUI. In that case, the pdu3GroupPowerWattHourTimer will be reset as well. A negative value indicates that this o… |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.21 |
||||||||||||||
|
pdu3GroupPowerWattHourTimermandatory
Timestamp when group kilo Watt-hours (group kWh) is reset.
|
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.232.165.11.3.1.1.22 |
||||||||||||||
|
pdu3GroupPowerFactormandatory
A group PF value. Return value is divided by 100, for example a power factor of 0.95 would be returned as 95.
A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.23 |
||||||||||||||
|
pdu3GroupPowerVARmandatory
A measurement for group/load segment power reactive. Units are VAR. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.3.1.1.24 |
||||||||||||||
|
pdu3GroupOutletCountmandatory
The number of outlets in each group (breaker).
|
Integer32 Constraints: range: 0-63 |
.1.3.6.1.4.1.232.165.11.3.1.1.25 |
||||||||||||||
|
pdu3GroupBreakerStatusmandatory
Only applicable to groups with breaker. Indicates whether a breaker is turned
off or on. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.3.1.1.26 |
.1.3.6.1.4.1.232.165.11.4.1
·
1 row entry
·
4 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3EnvProbeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3EnvProbeTable'
A list of environment probe (1 per PDU) for temperature, humidity, and contacts. The number of entries is given by number of PDUs in daisy chain.
Aggregate entries equal to number of PDUs.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
pdu3TemperatureScalemandatory
Scale used to return temperature objects.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.4.1.1.1 |
||||
|
pdu3TemperatureCountmandatory
Max number of temperature measurements (1 per probe).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.4.1.1.2 |
||||
|
pdu3HumidityCountmandatory
Max number of humidity measurements (1 per probe).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.4.1.1.3 |
||||
|
pdu3ContactCountmandatory
Max number of contact sensors (1 per probe).
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.4.1.1.4 |
.1.3.6.1.4.1.232.165.11.4.2
·
1 row entry
·
9 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3TemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3TemperatureTable'
A list of temperature probe measurements. The number of entries are given by number of pdu and pdu3TemperatureCount.
An entry for a temperature measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu3TemperatureIndexmandatory
A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.232.165.11.4.2.1.1 |
||||||||||
|
pdu3TemperatureNamemandatory
A descriptive name for the temperature probe.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.11.4.2.1.2 |
||||||||||
|
pdu3TemperatureProbeStatusmandatory
Indicates whether a probe is connected or not.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.4.2.1.3 |
||||||||||
|
pdu3TemperatureValuemandatory
Units are in tenths of a degree (either Fahrenheit or Celsius).
Return value is divided by 10 to get degrees. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.4.2.1.4 |
||||||||||
|
pdu3TemperatureThStatusmandatory
Status of the measured temperature relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.4.2.1.5 |
||||||||||
|
pdu3TemperatureThLowerWarningmandatory
Lower warning threshold. Return value is divided by 10 to get degree. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-150000 |
.1.3.6.1.4.1.232.165.11.4.2.1.6 |
||||||||||
|
pdu3TemperatureThLowerCriticalmandatory
Lower critical threshold. Return value is divided by 10 to get degree. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-150000 |
.1.3.6.1.4.1.232.165.11.4.2.1.7 |
||||||||||
|
pdu3TemperatureThUpperWarningmandatory
Upper warning threshold. Return value is divided by 10 to get degree. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-150000 |
.1.3.6.1.4.1.232.165.11.4.2.1.8 |
||||||||||
|
pdu3TemperatureThUpperCriticalmandatory
Upper critical threshold. Return value is divided by 10 to get degree. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-150000 |
.1.3.6.1.4.1.232.165.11.4.2.1.9 |
.1.3.6.1.4.1.232.165.11.4.3
·
1 row entry
·
9 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3HumidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3HumidityTable'
A list of humidity probe measurements. The number of entries are given by number of pdu and pdu3HumidityCount.
An entry for a humidity measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu3HumidityIndexmandatory
A unique value for each humidity probe measurement. Its value
ranges from 1 to pdu3HumidityCount per pdu. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.232.165.11.4.3.1.1 |
||||||||||
|
pdu3HumidityNamemandatory
A descriptive name for the humidity probe.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.11.4.3.1.2 |
||||||||||
|
pdu3HumidityProbeStatusmandatory
Indicates whether a probe is connected or not.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.4.3.1.3 |
||||||||||
|
pdu3HumidityValuemandatory
Units are tenths of a percent relative humidity. Return value is divided by 10 to get %RH.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.4.3.1.4 |
||||||||||
|
pdu3HumidityThStatusmandatory
Status of the measured humidity relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.4.3.1.5 |
||||||||||
|
pdu3HumidityThLowerWarningmandatory
Lower warning threshold. Return value is divided by 10 to get %RH. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-1000 |
.1.3.6.1.4.1.232.165.11.4.3.1.6 |
||||||||||
|
pdu3HumidityThLowerCriticalmandatory
Lower critical threshold. Return value is divided by 10 to get %RH. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-1000 |
.1.3.6.1.4.1.232.165.11.4.3.1.7 |
||||||||||
|
pdu3HumidityThUpperWarningmandatory
Upper warning threshold. Return value is divided by 10 to get %RH. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-1000 |
.1.3.6.1.4.1.232.165.11.4.3.1.8 |
||||||||||
|
pdu3HumidityThUpperCriticalmandatory
Upper critical threshold. Return value is divided by 10 to get %RH. A negative value
indicates that this object is not available. |
Integer32 Constraints: range: -1-1000 |
.1.3.6.1.4.1.232.165.11.4.3.1.9 |
.1.3.6.1.4.1.232.165.11.4.4
·
1 row entry
·
4 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3ContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3ContactTable'
A list of contact sensors. The number of entries are given by number of pdu and pdu3ContactCount.
An entry for a contact sensor
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
pdu3ContactIndexmandatory
A unique value for each contact sensor. Its value ranges from 1 to
contactCount. |
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.232.165.11.4.4.1.1 |
||||||
|
pdu3ContactNamemandatory
A descriptive name for the contact sensor.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.11.4.4.1.2 |
||||||
|
pdu3ContactProbeStatusmandatory
Indicates whether a probe is connected or not.
Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be read. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.4.4.1.3 |
||||||
|
pdu3ContactStatemandatory
The state of the contact sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.4.4.1.4 |
.1.3.6.1.4.1.232.165.11.5.1
·
1 row entry
·
17 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3OutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3OutletTable'
Aggregate Object with number of entries equal to Number of PDU (pdu3IdentIndex) and Number of outlet per PDU (pdu3OutletIndex).
The Outlet table entry containing the type, voltage, current etc.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
pdu3OutletIndexmandatory
Index for each outlet, value from 1 to the number of outlets per PDU.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.232.165.11.5.1.1.1 |
||||||||||||||||||||||||||||||||
|
pdu3OutletNamemandatory
A descriptive name for the outlet.
|
OctetString Constraints: range: 1-31 |
.1.3.6.1.4.1.232.165.11.5.1.1.2 |
||||||||||||||||||||||||||||||||
|
pdu3OutletTypemandatory
Type of this outlet - C13, C19.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.5.1.1.3 |
||||||||||||||||||||||||||||||||
|
pdu3OutletCurrentRatingmandatory
Rated current capacity of this outlet. Return value is divided by 100 to get amps. A negative
value indicates that the hardware current capacity is unknown. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.5.1.1.4 |
||||||||||||||||||||||||||||||||
|
pdu3OutletCurrentmandatory
A outlet current measurement value. Return value is divided by 100 to get amps.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.5.1.1.5 |
||||||||||||||||||||||||||||||||
|
pdu3OutletActivePowerThStatusmandatory
Status of the measured outlet active power relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.5.1.1.6 |
||||||||||||||||||||||||||||||||
|
pdu3OutletActivePowerThLowerWarningmandatory
Lower warning threshold. Units are Watts(W). A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-10000 |
.1.3.6.1.4.1.232.165.11.5.1.1.7 |
||||||||||||||||||||||||||||||||
|
pdu3OutletActivePowerThLowerCriticalmandatory
Lower critical threshold. Units are Watts(W). A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-10000 |
.1.3.6.1.4.1.232.165.11.5.1.1.8 |
||||||||||||||||||||||||||||||||
|
pdu3OutletActivePowerThUpperWarningmandatory
Upper warning threshold. Units are Watts(W). A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-10000 |
.1.3.6.1.4.1.232.165.11.5.1.1.9 |
||||||||||||||||||||||||||||||||
|
pdu3OutletActivePowerThUpperCriticalmandatory
Upper critical threshold. Units are Watts(W). A negative value indicates
that this object is not available. |
Integer32 Constraints: range: -1-10000 |
.1.3.6.1.4.1.232.165.11.5.1.1.10 |
||||||||||||||||||||||||||||||||
|
pdu3OutletCurrentPercentLoadmandatory
Current percent load, based on the rated current capacity. Units are
percentage, for example 80.5% will be returned as 805. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.5.1.1.11 |
||||||||||||||||||||||||||||||||
|
pdu3OutletVAmandatory
A outlet power VA value. Units are VA. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.5.1.1.12 |
||||||||||||||||||||||||||||||||
|
pdu3OutletWattsmandatory
A outlet power in Watts value. Units are Watts. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.5.1.1.13 |
||||||||||||||||||||||||||||||||
|
pdu3OutletWhmandatory
An energy in kWatt-Hour value for each outlet. Units are kWh.
This object is writable so that it can be reset to 0. When it is written to, the pdu3OutletWhTimer will be reset updated as well A negative value indic… |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.5.1.1.14 |
||||||||||||||||||||||||||||||||
|
pdu3OutletWhTimermandatory
Timestamp (date and time) of outlet energy in kWh is reset.
|
OctetString Constraints: range: 0-22 |
.1.3.6.1.4.1.232.165.11.5.1.1.15 |
||||||||||||||||||||||||||||||||
|
pdu3OutletPowerFactormandatory
An outlet PF value. Return value is divided by 100, for example a power factor
of 0.95 would be returned as 95. A negative value indicates that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.5.1.1.16 |
||||||||||||||||||||||||||||||||
|
pdu3OutletVARmandatory
An outlet power reactive in VAR value. Units are VAR. A negative value indicates
that this object is not available. |
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.232.165.11.5.1.1.17 |
.1.3.6.1.4.1.232.165.11.5.2
·
1 row entry
·
9 columns
Uses the hp variant from
Command help
/opt/observium/mibs/hp.
Walk pdu3OutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPQPOWER-MIB' -M '/opt/observium/mibs/hp:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPQPOWER-MIB::pdu3OutletControlTable'
Aggregate Object with number of entries equal to Number of PDU (pdu3IdentIndex) and Number of outlets per PDU (pdu3OutletIndex).
The Outlet table entry containing the type, voltage, current etc.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
pdu3OutletControlStatusmandatory
current state of a control outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.5.2.1.1 |
||||||||
|
pdu3OutletControlOffCmdmandatory
When write, once issued, the outlet will turn Off immediately.
0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet Off command When read, returns -1 if no command is pending, or the curr… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.11.5.2.1.2 |
||||||||
|
pdu3OutletControlOnCmdmandatory
When write, once issued, the outlet will turn On immediately.
0-n: Time in seconds until the outlet command is issued -1: Cancel a pending outlet On command When read, returns -1 if no command is pending, or the curren… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.11.5.2.1.3 |
||||||||
|
pdu3OutletControlRebootCmdmandatory
When write, for outlets that are On prior to this Reboot command, they will
switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets tha… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.11.5.2.1.4 |
||||||||
|
pdu3OutletControlPowerOnStatemandatory
Determines the outlet state when power is applied to the unit.
1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequenceTime 3 : should take the state the outlet had when power was… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.5.2.1.5 |
||||||||
|
pdu3OutletControlSequenceDelaymandatory
Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on delay. Set to -1 to exclude this outlet from Global Sequence … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.11.5.2.1.6 |
||||||||
|
pdu3OutletControlRebootOffTimemandatory
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
|
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.11.5.2.1.7 |
||||||||
|
pdu3OutletControlSwitchablemandatory
Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled 2 : control On/Off disabled. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.232.165.11.5.2.1.8 |
||||||||
|
pdu3OutletControlShutoffDelaymandatory
Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first then write it to the command pdu3OutletControlOf… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.232.165.11.5.2.1.9 |