cpiPduOutletAlertWarnLoCurrent

CPI-UNIFIED-MIB · .1.3.6.1.4.1.30932.1.10.1.4.310.1.3

Object

column r/w SNMPv2-SMIInteger32
Set or get the current draw in 1/100 amp of the branch on 
the PDU that triggers a warning condition.  Convert the 
value by dividing by 100.

Context

MIB
CPI-UNIFIED-MIB
OID
.1.3.6.1.4.1.30932.1.10.1.4.310.1.3
Type
column
Access
readwrite
Status
current
Parent
cpiPduOutletAlertEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduOutletAlertWarnLoCurrent'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduOutletAlertWarnLoCurrent.<cpiPduOutletAlertOutletId>.<cpiPduOutletAlertMac>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'CPI-UNIFIED-MIB::cpiPduOutletAlertWarnLoCurrent'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647