CPI-UNIFIED-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
26
Rows
26
Columns
219
cpiPduTable
table.1.3.6.1.4.1.30932.1.10.1.2.10
·
1 row entry
·
18 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduTable'
This table contains a list of PDU entries that are being monitored
by the PDU.
The table contains one, or many rows, depending upon the
number of PDUs being monitored. Each row in the table represents a PDU
in the daisy chain.
This table always contains at least one entry and a maximum of 32 entries.
The MAC address is used as an index on the table to allow data collectors
to ensure that information can be retrieved for a specific PDU.
This entry defines the columns to be populated in the
'cpiPduTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU MAC that is globally unique.
'cpiPduTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU MAC that is globally unique.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.1 |
||||||
|
Get the model number of the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.2 |
||||||
|
Set or get the user assigned name of the PDU.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.3 |
||||||
|
Set or get the user assigned description of the PDU.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.4 |
||||||
|
An indicator if the PDU supports monitoring voltage, and current on branches in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.5 |
||||||
|
An indicator if the PDU supports monitoring current on the individual outlets in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.6 |
||||||
|
An indicator if the PDU supports control (turn on/off) individual outlets in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.7 |
||||||
|
Get the number of branches (breakers) in the PDU.
|
Integer32 Constraints: range: 0-12 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.8 |
||||||
|
Get the number of outlets in the PDU.
|
Integer32 Constraints: range: 0-72 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.9 |
||||||
|
Set or get whether the PDU is in-service.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.10 |
||||||
|
Get the firmware version number of the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.11 |
||||||
|
An indicator if the PDU firmware is being upgraded.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.12 |
||||||
|
Get the role of the PDU in a daisy chain.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.2.10.1.13 |
||||||
|
Get IP address of the PDU.
|
SNMPv2-SMIIpAddress Type Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.14 |
||||||
|
Get the IPv6 address of the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.15 |
||||||
|
Get the power in volt-amps for the entire PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.16 |
||||||
|
Get/set the name of the cabinet the PDU is in.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.17 |
||||||
|
Get the serial number of the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.2.10.1.18 |
cpiPduLineTable
table.1.3.6.1.4.1.30932.1.10.1.3.10
·
1 row entry
·
3 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduLineTable'
This table contains a list of PDU line entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of input lines. Each row
in the table represents a PDU line in the daisy chain.
The table is indexed based on the corresponding Line Input ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'cpiPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.3.10.1.1 |
|
Get the ID of the input line on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.10.1.2 |
|
Get current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.10.1.3 |
cpiPduBranchTable
table.1.3.6.1.4.1.30932.1.10.1.3.110
·
1 row entry
·
9 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduBranchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduBranchTable'
This table contains a list of PDU branch entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduBranchTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'cpiPduBranchTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Get the MAC address of the PDU that owns the branch.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.1 |
||||||
|
Get the ID of the branch on the owning PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.2 |
||||||
|
Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.3 |
||||||
|
Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.4 |
||||||
|
Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.5 |
||||||
|
Get the power in volt-amps for the branch.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.6 |
||||||
|
Get the power factor for the branch.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.7 |
||||||
|
Get the alarm status of the branch.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.3.110.1.8 |
||||||
|
Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr.
|
SNMPv2-SMICounter64 Type Constraints: range: 0..18446744073709551615 |
.1.3.6.1.4.1.30932.1.10.1.3.110.1.9 |
cpiPduBranchAlertTable
table.1.3.6.1.4.1.30932.1.10.1.3.210
·
1 row entry
·
12 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduBranchAlertTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduBranchAlertTable'
This table contains a list of PDU branch alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and the
source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.1 |
|
Get the branch ID on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.2 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.3 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.4 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.5 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.6 |
|
Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.7 |
|
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.8 |
|
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.9 |
|
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.10 |
|
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.11 |
|
Index for branch alert.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.3.210.1.12 |
cpiPduOutletTable
table.1.3.6.1.4.1.30932.1.10.1.4.10
·
1 row entry
·
12 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduOutletTable'
This table contains a list of PDU outlet entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets on each PDU.
Each row in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
'cpiPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Get the MAC address of the source PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.1 |
||||||
|
Get the ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.2 |
||||||
|
Get the ID of the branch the outlet is associated with on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.3 |
||||||
|
Set or get the user supplied name of the outlet on the PDU.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.4 |
||||||
|
Set or get the user supplied description of the outlet on the PDU.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.5 |
||||||
|
Get the current draw in 1/100 amp of the outlet on the PDU. Convert
the value by dividing by 100. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.6 |
||||||
|
Get the voltage in 1/10 volts of the outlet on the PDU. Convert the
value by dividing by 10. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.7 |
||||||
|
The power in Volt-Amps of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.8 |
||||||
|
Get the alarm status of the outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.4.10.1.9 |
||||||
|
Get the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.
|
SNMPv2-SMICounter64 Type Constraints: range: 0..18446744073709551615 |
.1.3.6.1.4.1.30932.1.10.1.4.10.1.10 |
||||||
|
Set or get power control to the outlet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.4.10.1.11 |
||||||
|
Set or get reset power to the outlet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.4.10.1.12 |
cpiPduOutletConfigTable
table.1.3.6.1.4.1.30932.1.10.1.4.210
·
1 row entry
·
4 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduOutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduOutletConfigTable'
This table contains a list of PDU outlet configuration entries
that are being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
| Column | Syntax | OID |
|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.4.210.1.1 |
|
Get the ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.210.1.2 |
|
Set or get the outlet power-on delay in seconds.
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.30932.1.10.1.4.210.1.3 |
|
Set or get the outlet reset delay in seconds.
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.30932.1.10.1.4.210.1.4 |
cpiPduOutletAlertTable
table.1.3.6.1.4.1.30932.1.10.1.4.310
·
1 row entry
·
7 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduOutletAlertTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduOutletAlertTable'
This table contains a list of PDU outlet alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and the
source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'cpiPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
| Column | Syntax | OID |
|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.1 |
|
Get the outlet ID on the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.2 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.3 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.4 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.5 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.6 |
|
Set or get the critical current draw in 1/100 amp of the
outlet on the PDU. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.4.310.1.7 |
cpiPduProbeTable
table.1.3.6.1.4.1.30932.1.10.1.5.5
·
1 row entry
·
3 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduProbeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduProbeTable'
This table contains a list of PDU probes that are being monitored
by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of probes attached to the PDUs in
the daisy chain. Each row in the table represents a probe in the daisy chain.
The table is index based on the corresponding Probe ID and the source
PDU MAC.
This entry defines the columns to be populated in the
'cpiPduProbeTable'. Each column represents an attribute of a PDU probe.
This table is indexed by the PDU identifier that is unique
within the PDU and the probe ID.
'cpiPduProbeTable'. Each column represents an attribute of a PDU probe.
This table is indexed by the PDU identifier that is unique
within the PDU and the probe ID.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.5.5.1.1 |
|
Get the probe ID on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.5.1.2 |
|
Set or get the user defined name of the probe.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.5.5.1.3 |
cpiPduSensorTable
table.1.3.6.1.4.1.30932.1.10.1.5.10
·
1 row entry
·
5 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduSensorTable'
This table contains a list of PDU sensor entries that are being monitored
by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
The table is index based on the corresponding Sensor ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiPduSensorTable'.
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor …
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor …
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.5.10.1.1 |
||||
|
Get the sensor ID on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.10.1.2 |
||||
|
Set or get the user defined name of the sensor.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.5.10.1.3 |
||||
|
Get the type of sensor for the entry.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.5.10.1.4 |
||||
|
Get the value of the sensor. For temperature the value is in degrees
Fahrenheit and for humidity the value is percent humidity. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.10.1.5 |
cpiPduSensorAlertTable
table.1.3.6.1.4.1.30932.1.10.1.5.110
·
1 row entry
·
6 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiPduSensorAlertTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiPduSensorAlertTable'
This table contains a list of PDU sensor alert entries that are
being monitored by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
The table is index based on the corresponding Sonsor ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiPduSensorAlertTable'.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
| Column | Syntax | OID |
|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.1 |
|
Get the id of the sensor.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.2 |
|
Set or get the minimum warning value of the sensor.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.3 |
|
Set or get the maximum warning value of the sensor.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.4 |
|
Set or get the minimum alarm value of the sensor.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.5 |
|
Set or get the maximum alarm value of the sensor.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.5.110.1.6 |
cpiGroupTable
table.1.3.6.1.4.1.30932.1.10.1.6.10
·
1 row entry
·
2 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiGroupTable'
This table contains a list of PDU group entries that are being monitored
by the PDU.
The table contains one, or many rows, depending upon the number
of groups that have been configured. Each row in the table represents a
group.
This entry defines the columns to be populated in the
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
This is the index that indicates the row of the 'cpiPduTable'.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.6.10.1.1 |
|
Name for GROUP 1 of receptacles.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.6.10.1.2 |
cpiGroupOutletTable
table.1.3.6.1.4.1.30932.1.10.1.6.20
·
1 row entry
·
4 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiGroupOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiGroupOutletTable'
This table contains a list of PDU group entries. The table contains zero, one, or many rows, depending upon the number of groups that have been configured. Each row in the table represents a group.
This entry defines the columns to be populated in the
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
'cpiGroupTable'. This table is indexed by the group identifier that
is unique within the PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
This is the index that indicates the row of the 'cpiGroupOutletTable'.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.6.20.1.1 |
|
Name for GROUP 1 of receptacles.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.6.20.1.2 |
|
MAC of PDU the outlet is on.
|
SNMPv2-TCMacAddressr/w Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.6.20.1.3 |
|
The ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.6.20.1.4 |
cpiEasConfigTable
table.1.3.6.1.4.1.30932.1.10.1.7.90
·
1 row entry
·
6 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiEasConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiEasConfigTable'
This table contains a list of electronic locks that are connected to the PDU
and allows for the configuration of the various settings associated with the
EAS (electronic access system).
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.7.90.1.1 |
||||
|
Indicates whether the Electronic Access System (EAS) is available on the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.90.1.2 |
||||
|
Enables the front lock on the EAS.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.90.1.3 |
||||
|
Enables the rear lock on the EAS.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.90.1.4 |
||||
|
The length of time in seconds to hold open the lock after a successful card scan.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.7.90.1.5 |
||||
|
The length of time in minutes before alerting that the door is open.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.10.1.7.90.1.6 |
cpiEasTable
table.1.3.6.1.4.1.30932.1.10.1.7.100
·
1 row entry
·
11 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk cpiEasTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::cpiEasTable'
This table contains a list of electronic locks that are connected to the PDU
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.10.1.7.100.1.1 |
||||||
|
Get the lock ID on the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.2 |
||||||
|
Indicates if the Electronic Access Control system is ready, inactive, or in an error state.
If the status is Inactive, then the lock is not enabled on the PDU. If the status is Error, then the cpiEasError… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.3 |
||||||
|
Indicates if the door sensor is closed or open.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.4 |
||||||
|
Indicates if the lock is closed or open.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.5 |
||||||
|
Indicates if the cabinet was forced open by a command from the webUI or SNMP interfaces.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.6 |
||||||
|
Indicates if the cabinet is currently unlocked/opened without an authorization scan.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.7 |
||||||
|
Gets the error code associated for the electronic lock system. The possible error codes are:
196608 (0x00030000 ) - No error, the lock is working and ready. 167968771 (0x0a030003 ) - The lock is not enabl… |
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.10.1.7.100.1.8 |
||||||
|
Gets the version of the electronic lock control.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.7.100.1.9 |
||||||
|
Get the serial number of the electronic lock control.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.10.1.7.100.1.10 |
||||||
|
Tells the system to open the locks on the cabinet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.10.1.7.100.1.11 |
saIpv4Table
table.1.3.6.1.4.1.30932.1.20.5.5.11
·
1 row entry
·
11 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saIpv4Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saIpv4Table'
This table contains a list of PDU IPv4 entries that are attached through
the SecureArray connection.
The Row ID field is used as an index on the table. The Row ID is not
guaranteed to be the same PDU from one instance in time to another. It
is recommended to utilize the MAC address as a universally unique ID.
This entry defines the columns to be populated in the
'saIpv4Table'. Each column represents an attribute of a PDU.
'saIpv4Table'. Each column represents an attribute of a PDU.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
The Row ID of the PDU.
|
Integer32 Constraints: range: 1-48 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.1 |
||||
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.2 |
||||
|
Controls whether the IPv4 network interface is enabled.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.5.5.11.1.3 |
||||
|
Set or get the IPv4 address of the PDU.
|
SNMPv2-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.4 |
||||
|
Controls whether the IPv4 address is retrieved from a
DHCP server or is set statically. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.5.5.11.1.5 |
||||
|
Controls whether the DNS addresses are retrieved from
a DHCP server or are set statically. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.5.5.11.1.6 |
||||
|
The subnet mask associated with the IPv4 address of this
entry. The value of the mask is an IPv4 address with all the network bits set to 1 and all the hosts bits set to 0. |
SNMPv2-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.7 |
||||
|
Set or get the IPv4 address of the gateway router for the PDU.
|
SNMPv2-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.8 |
||||
|
Set or get the IPv4 address of the first DNS entry for the PDU.
|
SNMPv2-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.9 |
||||
|
Set or get the IPv4 address of the second DNS entry for the PDU.
|
SNMPv2-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.10 |
||||
|
Set or get the IPv4 address of the third DNS entry for the PDU.
|
SNMPv2-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.5.5.11.1.11 |
saPduTable
table.1.3.6.1.4.1.30932.1.20.10.11
·
1 row entry
·
19 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduTable'
This table contains a list of PDU entries that are attached through
the SecureArray connection.
The table contains one, or many rows, depending upon the
number of PDUs being monitored. Each row in the table represents a PDU
in the SecureArray.
This table always contains at least one entry and a maximum of 48 entries.
The Row ID field is used as an index on the table. The Row ID is not
guaranteed to be the same PDU from one instance in time to another. It
is recommended to utilize the MAC address as a universally unique ID.
This entry defines the columns to be populated in the
'saPduTable'. Each column represents an attribute of a PDU.
'saPduTable'. Each column represents an attribute of a PDU.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
The Row ID of the PDU.
|
Integer32 Constraints: range: 1-48 |
.1.3.6.1.4.1.30932.1.20.10.11.1.1 |
||||||
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.10.11.1.2 |
||||||
|
Get the model number of the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.10.11.1.3 |
||||||
|
Set or get the user assigned name of the PDU.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.10.11.1.4 |
||||||
|
Set or get the user assigned description of the PDU.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.10.11.1.5 |
||||||
|
An indicator if the PDU supports monitoring voltage, and current on branches in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.6 |
||||||
|
An indicator if the PDU supports monitoring current on the individual outlets in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.7 |
||||||
|
An indicator if the PDU supports control (turn on/off) individual outlets in the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.8 |
||||||
|
Get the number of branches (breakers) in the PDU.
|
Integer32 Constraints: range: 0-12 |
.1.3.6.1.4.1.30932.1.20.10.11.1.9 |
||||||
|
Get the number of outlets in the PDU.
|
Integer32 Constraints: range: 0-48 |
.1.3.6.1.4.1.30932.1.20.10.11.1.10 |
||||||
|
Set or get whether the PDU is in-service.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.11 |
||||||
|
Get the firmware version number of the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.10.11.1.12 |
||||||
|
An indicator if the PDU firmware is being upgraded.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.13 |
||||||
|
Get the role of the PDU in a SecureArray.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.10.11.1.14 |
||||||
|
Get IP address of the PDU.
|
SNMPv2-SMIIpAddress Type Constraints: range: 4 |
.1.3.6.1.4.1.30932.1.20.10.11.1.15 |
||||||
|
Get the IPv6 address of the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.10.11.1.16 |
||||||
|
Get the power in volt-amps for the entire PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.10.11.1.17 |
||||||
|
Get/set the name of the cabinet the PDU is in.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.10.11.1.18 |
||||||
|
Get the serial number of the PDU.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.10.11.1.19 |
saPduLineTable
table.1.3.6.1.4.1.30932.1.20.15.11
·
1 row entry
·
5 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduLineTable'
This table contains a list of PDU line entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of input lines. Each row
in the table represents a PDU line in the SecureArray.
The table is indexed based on the corresponding Line Row ID.
This entry defines the columns to be populated in the
'saPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'saPduLineTable'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Get the ID of the input line on the PDU.
|
Integer32 Constraints: range: 0-512 |
.1.3.6.1.4.1.30932.1.20.15.11.1.1 |
|
Get the ID of the input line on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.15.11.1.2 |
|
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.15.11.1.3 |
|
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.15.11.1.4 |
|
Get current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.15.11.1.5 |
saPduBranchTable
table.1.3.6.1.4.1.30932.1.20.20.11
·
1 row entry
·
11 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduBranchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduBranchTable'
This table contains a list of PDU branch entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'saPduBranchEntry'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'saPduBranchEntry'. Each column represents an attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Get the Row ID of the branch on the owning PDU.
|
Integer32 Constraints: range: 0-768 |
.1.3.6.1.4.1.30932.1.20.20.11.1.1 |
||||||
|
Get the ID of the branch on the owning PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.2 |
||||||
|
Get the MAC address of the PDU that owns the branch.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.20.11.1.3 |
||||||
|
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.20.11.1.4 |
||||||
|
Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.5 |
||||||
|
Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.6 |
||||||
|
Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.7 |
||||||
|
Get the power in volt-amps for the branch.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.8 |
||||||
|
Get the power factor for the branch.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.11.1.9 |
||||||
|
Get the alarm status of the branch.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.20.11.1.10 |
||||||
|
Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr.
|
SNMPv2-SMICounter64 Type Constraints: range: 0..18446744073709551615 |
.1.3.6.1.4.1.30932.1.20.20.11.1.11 |
saPduBranchAlertTable
table.1.3.6.1.4.1.30932.1.20.20.12
·
1 row entry
·
13 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduBranchAlertTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduBranchAlertTable'
This table contains a list of PDU branch alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of branches per PDU. Each row
in the table represents a PDU branch in the daisy chain.
The table is indexed based on the corresponding Branch ID and the
source PDU MAC.
This entry defines the columns to be populated in the
'saPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'saPduBranchAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Get the Row ID of the branch on the owning PDU.
|
Integer32 Constraints: range: 0-768 |
.1.3.6.1.4.1.30932.1.20.20.12.1.1 |
|
Get the MAC address of the PDU that owns the branch.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.20.12.1.2 |
|
Get the MAC address of the PDU that owns the input line.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.20.12.1.3 |
|
Get the branch of the owning PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.4 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.5 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.6 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.7 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.8 |
|
Set or get the critical current draw in 1/100 amp of the
branch on the PDU. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.9 |
|
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.10 |
|
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.11 |
|
Set or get the minimum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.12 |
|
Set or get the maximum voltage that the branch can reach
up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.20.12.1.13 |
saPduOutletTable
table.1.3.6.1.4.1.30932.1.20.25.11
·
1 row entry
·
13 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduOutletTable'
This table contains a list of PDU outlet entries that are being
monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets on each PDU.
Each row in the table represents a PDU outlet in the SecureArray.
This entry defines the columns to be populated in the
'saPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
'saPduOutletTable'. Each column represents an outlet of a PDU.
This table is indexed by the PDU Outlet identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Get the ID of the outlet on the PDU.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.30932.1.20.25.11.1.1 |
||||||
|
Get the MAC address of the source PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.25.11.1.2 |
||||||
|
Get the ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.3 |
||||||
|
Get the ID of the branch the outlet is associated with on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.4 |
||||||
|
Set or get the user supplied name of the outlet on the PDU.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.25.11.1.5 |
||||||
|
Set or get the user supplied description of the outlet on the PDU.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.25.11.1.6 |
||||||
|
Get the current draw in 1/100 amp of the outlet on the PDU. Convert
the value by dividing by 100. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.7 |
||||||
|
Get the voltage in 1/10 volts of the outlet on the PDU. Convert the
value by dividing by 10. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.8 |
||||||
|
The power in Volt-Amps of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.11.1.9 |
||||||
|
Get the alarm status of the outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.25.11.1.10 |
||||||
|
Get the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr.
|
SNMPv2-SMICounter64 Type Constraints: range: 0..18446744073709551615 |
.1.3.6.1.4.1.30932.1.20.25.11.1.11 |
||||||
|
Set or get power control to the outlet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.25.11.1.12 |
||||||
|
Set or get reset power to the outlet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.25.11.1.13 |
saPduOutletConfigTable
table.1.3.6.1.4.1.30932.1.20.25.20
·
1 row entry
·
5 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduOutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduOutletConfigTable'
This table contains a list of PDU outlet configuration entries
that are being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
The table is indexed based on the corresponding Outlet ID and
the source PDU MAC.
This entry defines the columns to be populated in the
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
'cpiPduOutletConfigTable'. Each column represents an
configurable attribute of an outlet in the PDU. This
table is indexed by the PDU Line identifier that is
uni…
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Get the ID of the outlet on the PDU.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.30932.1.20.25.20.1.1 |
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.25.20.1.2 |
|
Get the ID of the outlet on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.20.1.3 |
|
Set or get the outlet power-on delay in seconds.
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.30932.1.20.25.20.1.4 |
|
Set or get the outlet reset delay in seconds.
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.30932.1.20.25.20.1.5 |
saPduOutletAlertTable
table.1.3.6.1.4.1.30932.1.20.25.30
·
1 row entry
·
8 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduOutletAlertTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduOutletAlertTable'
This table contains a list of PDU outlet alert entries that are
being monitored by the PDU.
The table contains one, or many rows, depending upon the number
of PDUs being monitored and the number of outlets per PDU. Each row
in the table represents a PDU outlet in the daisy chain.
This entry defines the columns to be populated in the
'saPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
'saPduOutletAlertTable'. Each column represents an alert attribute of a PDU.
This table is indexed by the PDU Line identifier that is unique
within the PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Get the outlet ID on the PDU.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.30932.1.20.25.30.1.1 |
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.25.30.1.2 |
|
Get the outlet ID on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.3 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.4 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers a warning condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.5 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.6 |
|
Set or get the current draw in 1/100 amp of the branch on
the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.7 |
|
Set or get the critical current draw in 1/100 amp of the
outlet on the PDU. Convert the value by dividing by 100. |
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.25.30.1.8 |
saPduSensorTable
table.1.3.6.1.4.1.30932.1.20.30.10
·
1 row entry
·
6 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduSensorTable'
This table contains a list of PDU sensor entries that are being monitored
by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
This entry defines the columns to be populated in the 'saPduSensorTable'.
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor I…
Each column represents an attribute of a PDU sensor. This table is indexed
by the PDU identifier that is unique within the PDU and the sensor I…
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Get the sensor ID on the PDU.
|
Integer32 Constraints: range: 1-8192 |
.1.3.6.1.4.1.30932.1.20.30.10.1.1 |
||||
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.30.10.1.2 |
||||
|
Get the sensor ID on the PDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.10.1.3 |
||||
|
Set or get the user defined name of the sensor.
|
SNMPv2-TCDisplayStringr/w Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.30.10.1.4 |
||||
|
Get the type of sensor for the entry.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.30.10.1.5 |
||||
|
Get the value of the sensor. For temperature the value is in degrees
Fahrenheit and for humidity the value is percent humidity. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.10.1.6 |
saPduSensorAlertTable
table.1.3.6.1.4.1.30932.1.20.30.20
·
1 row entry
·
7 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saPduSensorAlertTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saPduSensorAlertTable'
This table contains a list of PDU sensor alert entries that are
being monitored by the PDU.
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of sensors attached to the PDUs in
the daisy chain. Each row in the table represents a sensor in the daisy chain.
This entry defines the columns to be populated in the 'cpiPduSensorAlertTable'.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Each column represents an attribute of a PDU sensor alert. This table
is indexed by the PDU identifier that is unique within the PDU.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Get the id of the sensor.
|
Integer32 Constraints: range: 1-4096 |
.1.3.6.1.4.1.30932.1.20.30.20.1.1 |
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.30.20.1.2 |
|
Get the id of the sensor.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.3 |
|
Set or get the minimum warning value of the sensor.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.4 |
|
Set or get the maximum warning value of the sensor.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.5 |
|
Set or get the minimum alarm value of the sensor.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.6 |
|
Set or get the maximum alarm value of the sensor.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.30.20.1.7 |
saEasConfigTable
table.1.3.6.1.4.1.30932.1.20.40.20
·
1 row entry
·
7 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saEasConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saEasConfigTable'
This table contains a list of electronic locks that are connected to the PDU
and allows for the configuration of the various settings associated with the
EAS (electronic access system).
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Get the MAC address of the PDU.
|
Integer32 Constraints: range: 1-128 |
.1.3.6.1.4.1.30932.1.20.40.20.1.1 |
||||
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.40.20.1.2 |
||||
|
Indicates whether the Electronic Access System (EAS) is available on the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.20.1.3 |
||||
|
Enables the front lock on the EAS.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.20.1.4 |
||||
|
Enables the rear lock on the EAS.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.20.1.5 |
||||
|
The length of time in seconds to hold open the lock after a successful card scan.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.40.20.1.6 |
||||
|
The length of time in minutes before alerting that the door is open.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.30932.1.20.40.20.1.7 |
saEasTable
table.1.3.6.1.4.1.30932.1.20.40.30
·
1 row entry
·
12 columns
Uses the chatsworth variant from
Command help
/opt/observium/mibs/chatsworth.
Walk saEasTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPI-UNIFIED-MIB' -M '/opt/observium/mibs/chatsworth:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPI-UNIFIED-MIB::saEasTable'
This table contains a list of electronic locks that are connected to the PDU
The table contains zero, one, or many rows, depending upon the number
of PDUs being monitored and the number of locks attached to the PDUs in
the daisy chain. Each row in the table represents a lock in the daisy chain.
The table is index based on the corresponding lock ID and the source
PDU MAC.
This entry defines the columns to be populated in the 'cpiEasTable'.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Each column represents an attribute of a PDU lock. This table is indexed
by the PDU identifier that is unique within the PDU and the lock ID.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Get the lock ID on the PDU.
|
Integer32 Constraints: range: 0-128 |
.1.3.6.1.4.1.30932.1.20.40.30.1.1 |
||||||
|
Get the MAC address of the PDU.
|
SNMPv2-TCMacAddress Type Constraints: range: 6Description: Represents an 802 MAC address represented in the `canonical' order defined by IEEE 802.1a, i.e., as if it were transmitted least significant bit first, even though 802.5 (in contrast to other 802.x protocols) requires M… |
.1.3.6.1.4.1.30932.1.20.40.30.1.2 |
||||||
|
Get the lock ID on the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.3 |
||||||
|
Indicates if the Electronic Access Control system is ready, inactive, or in an error state.
If the status is Inactive, then the lock is not enabled on the PDU. If the status is Error, then the cpiEasError… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.4 |
||||||
|
Indicates if the door sensor is closed or open.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.5 |
||||||
|
Indicates if the lock is closed or open.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.6 |
||||||
|
Indicates if the cabinet was forced open by a command from the webUI or SNMP interfaces.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.7 |
||||||
|
Indicates if the cabinet is currently unlocked/opened without an authorization scan.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.8 |
||||||
|
Gets the error code associated for the electronic lock system. The possible error codes are:
196608 (0x00030000 ) - No error, the lock is working and ready. 167968771 (0x0a030003 ) - The lock is not enabl… |
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.30932.1.20.40.30.1.9 |
||||||
|
Gets the version of the electronic lock control.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.40.30.1.10 |
||||||
|
Get the serial number of the electronic lock control.
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.30932.1.20.40.30.1.11 |
||||||
|
Tells the system to open the locks on the cabinet.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.30932.1.20.40.30.1.12 |