pduInputPhaseConfigOverloadRestriction
CPDU-MIB ·
.1.3.6.1.4.1.318.1.1.32.3.2.1.3
Object
column
mandatory
r/w
Enumeration
This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
Context
- MIB
- CPDU-MIB
- OID
.1.3.6.1.4.1.318.1.1.32.3.2.1.3- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- pduInputPhaseConfigEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alwaysAllowTurnOn |
2 | restrictOnUpperWarning |
3 | restrictOnUpperCritical |
4 | notSupported |