CPDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
26
Rows
26
Columns
224

pduNamePlateTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.1.2 · 1 row entry · 16 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduNamePlateTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduNamePlateTable'
A table of PDU nameplate data
pduNamePlateEntry row .1.3.6.1.4.1.318.1.1.32.1.2.1
Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize.
Column Syntax OID
The index of the PDU nameplate table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.1.2.1.1
A user-defined string identifying the PDU
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.2
A user-defined string identifying the location of PDU
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.3
The type of address format
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.1.2.1.4
The current IP address. A value of 0.0.0.0 indicates an error or an unset option
INET-ADDRESS-MIBInetAddress
Type Constraints:
range: 0..255
.1.3.6.1.4.1.318.1.1.32.1.2.1.5
The current netmask. A value of 0.0.0.0 indiates an error or an unset option
INET-ADDRESS-MIBInetAddress
Type Constraints:
range: 0..255
.1.3.6.1.4.1.318.1.1.32.1.2.1.6
The current gateway. A value of 0.0.0.0 indicates an error or an unset option
INET-ADDRESS-MIBInetAddress
Type Constraints:
range: 0..255
.1.3.6.1.4.1.318.1.1.32.1.2.1.7
The assigned MAC address for the PDU
SNMPv2-TCMacAddress
Type Constraints:
range: 6
Description:
Represents an 802 MAC address represented in the
`canonical' order defined by IEEE 802.1a, i.e., as if it
were transmitted least significant bit first, even though
802.5 (in contrast to other 802.x protocols) requires M…
.1.3.6.1.4.1.318.1.1.32.1.2.1.8
The difference in hours and minutes from Coordinated Universal
Time(UTC) for the time used in a particular time zone
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.9
The PDU model number
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.10
The PDU part number
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.11
The PDU serial number
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.12
The date the PDU was manufactured in mm/dd/yyyy format
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.13
The PDU firmware version
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.14
Timestamp of when the PDU firmware was last updated
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.1.2.1.15
The type of input
Enumeration
Enumerated Values:
1singlePhase
2delta
3wye
.1.3.6.1.4.1.318.1.1.32.1.2.1.16

pduUnitConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.2.2 · 1 row entry · 20 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduUnitConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduUnitConfigTable'
A table of PDU configuration data
pduUnitConfigEntry row .1.3.6.1.4.1.318.1.1.32.2.2.1
Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize
Column Syntax OID
The index of the PDU Unit Config Entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.2.2.1.1
A user-defined string identifying the PDU
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.2.2.1.2
A user-defined string identifying the location of the PDU
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.2.2.1.3
Indicates the intended physical orientation of the oLED display
displayNormal (1) indicates normal orientation.
displayReverse (2) indicates upside down orientation
NOTE:
This OID is compatible only with the two displa…
Enumerationr/w
Enumerated Values:
1displayNormal
2displayReverse
.1.3.6.1.4.1.318.1.1.32.2.2.1.4
Used to turn oled display On or Off
displayOff (1) to turn dispaly OFF.
displayOn (2) to turn dispaly ON
Enumerationr/w
Enumerated Values:
1displayOff
2displayOn
.1.3.6.1.4.1.318.1.1.32.2.2.1.5
The amount of time, specified in seconds, between when power
is provided to the PDU and when the PDU start providing basic master
power to the outlets
Unsigned32r/w
Constraints:
range: 0-3600
.1.3.6.1.4.1.318.1.1.32.2.2.1.6
The outlet state on device startup; applies to all outlets
unless overridden at the outlet level
Enumerationr/w
Enumerated Values:
0off
1on
2lastKnownState
.1.3.6.1.4.1.318.1.1.32.2.2.1.7
User-defined lower critical unit active power alarm threshold measured in Watts
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.2.2.1.8
User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.2.2.1.9
User-defined upper critical unit active power alarm threshold measured in Watts
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.2.2.1.10
User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.2.2.1.11
The hysteresis used for deassertions in Watts
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.2.2.1.12
The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive…
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.2.2.1.13
A bit string indicating which alarm thresholds are enabled
Bitsr/w
Enumerated Values:
0lowerCritical
1lowerWarning
2upperWarning
3upperCritical
.1.3.6.1.4.1.318.1.1.32.2.2.1.14
Setting this OID to reset (2) will cause the existing peak power value
to be replaced by the current load power value. Getting this OID will
do nothing and return the noOperation(1) value.
Enumerationr/w
Enumerated Values:
1noOperation
2reset
.1.3.6.1.4.1.318.1.1.32.2.2.1.15
Setting this OID to reset (2) will cause the device energy meter value
to be reset to zero. Getting this OID in models that support this
feature will do nothing and return the noOperation(1) value. Models
that do not…
Enumerationr/w
Enumerated Values:
1noOperation
2reset
3notSupported
.1.3.6.1.4.1.318.1.1.32.2.2.1.16
Setting this OID to reset (2) will cause the outlet peak power meter value
to be reset to zero. Getting this OID in models that support this
feature will do nothing and return the noOperation(1) value. Models
that do…
Enumerationr/w
Enumerated Values:
1noOperation
2reset
3notSupported
.1.3.6.1.4.1.318.1.1.32.2.2.1.17
Setting this OID to reset (2) will cause the outlet energy meter value
to be reset to zero. Getting this OID in models that support this
feature will do nothing and return the noOperation(1) value. Models
that do not…
Enumerationr/w
Enumerated Values:
1noOperation
2reset
3notSupported
.1.3.6.1.4.1.318.1.1.32.2.2.1.18
Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection.
Enumerationr/w
Enumerated Values:
0off
1on
.1.3.6.1.4.1.318.1.1.32.2.2.1.19
Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC.
Enumerationr/w
Enumerated Values:
0noOperation
1reset
.1.3.6.1.4.1.318.1.1.32.2.2.1.20

pduUnitPropertiesTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.2.3 · 1 row entry · 16 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduUnitPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduUnitPropertiesTable'
A table of PDU properties
pduUnitPropertiesEntry row .1.3.6.1.4.1.318.1.1.32.2.3.1
A unit properties entry containing objects for a particular unit.
Column Syntax OID
The index of the PDU properties table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.2.3.1.1
A user-defined string identifying the PDU
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.3.1.2
The total number of outlets on the PDU
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.2.3.1.3
The total number of switched outlets on the PDU
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.2.3.1.4
The total number of metered outlets on the PDU
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.2.3.1.5
The total number of phases on the PDU
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.2.3.1.6
The total number of circuit breaker on the PDU
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.2.3.1.7
The maximum number of external sensors that can be connected to the PDU
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.2.3.1.8
The current number of external sensors connected to the PDU
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.2.3.1.9
The PDU voltage rating in Volts
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.3.1.10
The PDU current rating in Amps
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.3.1.11
The PDU frequency rating in Hz
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.3.1.12
The PDU VA (VoltAmps) rating.
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.3.1.13
The PDU orientation
Enumeration
Enumerated Values:
1horizontal
2vertical
.1.3.6.1.4.1.318.1.1.32.2.3.1.14
The outlet layout for the PDU. Getting this OID will return outlet layout for the device.
seqPhaseToNeutral(1) indicates outlet layout as follows:
1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
seqPhaseToPhase(2) indicates outlet la…
Enumeration
Enumerated Values:
1seqPhaseToNuetral
2seqPhaseToPhase
3seqPhToNeu21PhToPh
4seqPhToPhGrouped
5seqPhToNGrouped
6seqPToN1516PToPGrouped
7seqPhToPh2xGrouped
8seqPhToN2xGrouped
9seqNotApplicable
.1.3.6.1.4.1.318.1.1.32.2.3.1.15
The cascading member type
Enumeration
Enumerated Values:
1standalone
2parent
3child
.1.3.6.1.4.1.318.1.1.32.2.3.1.16

pduUnitStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.2.4 · 1 row entry · 12 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduUnitStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduUnitStatusTable'
A table of PDU status information
pduUnitStatusEntry row .1.3.6.1.4.1.318.1.1.32.2.4.1
Status information from the PDU being queried
Column Syntax OID
The index of the PDU status table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.2.4.1.1
A user-defined string identifying the PDU
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.4.1.2
Returns the present load status of the PDU based on Active Power.
Enumeration
Enumerated Values:
1upperCritical
2upperWarning
3lowerWarning
4lowerCritical
5normal
.1.3.6.1.4.1.318.1.1.32.2.4.1.3
Returns power consumption, in Watts(W),
of the PDU being queried.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.2.4.1.4
Returns power consumption, in Volt-Amps(VA)
of the PDU load being queried.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.2.4.1.5
Returns peak power consumption, in Watts(W),
of the PDU being queried.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.2.4.1.6
Indicates the date and time that peak power consumption occurred
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.4.1.7
Indicates the date and time of the last device peak power reset
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.4.1.8
Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.2.4.1.9
A user resettable energy meter measuring PDU energy consumption
in tenths of kilowatt-hours(kWh).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.2.4.1.10
Indicates the date and time of the last device energy meter reset
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.4.1.11
Indicates the date and time of the last outlets energy meter reset
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.2.4.1.12

pduUnitPsTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.2.5 · 1 row entry · 4 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduUnitPsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduUnitPsTable'
Aggregate Object with number of entries equal to number of PDUs and Power share
pduUnitPsEntry row .1.3.6.1.4.1.318.1.1.32.2.5.1
The Power share entry containing the avaliable, input, output etc.
Indexes
Column Syntax OID
The index of the PDU Power share table entry
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.318.1.1.32.2.5.1.1
Power share support status on upstream PDU
Enumeration
Enumerated Values:
0notAvailable
1available
.1.3.6.1.4.1.318.1.1.32.2.5.1.2
Power share support status on downstream PDU
Enumeration
Enumerated Values:
0notAvailable
1available
.1.3.6.1.4.1.318.1.1.32.2.5.1.3
Operating power status.
Enumeration
Enumerated Values:
0backupPower
1mainPower
.1.3.6.1.4.1.318.1.1.32.2.5.1.4

pduInputPhaseConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.3.2 · 1 row entry · 17 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduInputPhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduInputPhaseConfigTable'
A table of PDU Input Phase configuration data
pduInputPhaseConfigEntry row .1.3.6.1.4.1.318.1.1.32.3.2.1
An input phase entry containing objects for a particular input phase.
Column Syntax OID
The index of the PDU Input Phase configuration table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.3.2.1.1
The total number of Input Phases
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.3.2.1.2
This OID controls the behavior of a Switched PDU Input Phase when an
overload condition is possible and additional outlets are requested
to be turned on. Setting this OID to alwaysAllowTurnON (1) will always
allow th…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnOn
2restrictOnUpperWarning
3restrictOnUpperCritical
4notSupported
.1.3.6.1.4.1.318.1.1.32.3.2.1.3
User-defined lower critical input phase current alarm threshold in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.4
User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.5
User-defined upper critical input phase current alarm threshold in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.6
User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.7
User-defined lower critical input phase voltage alarm threshold in Volts(V).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.8
User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.9
User-defined upper critical input phase voltage alarm threshold in Volts(V).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.10
User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.11
The hysteresis used for current alarm deassertions in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.12
The delay measured in samples before a current state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the assertion condition
must exist for n+1 …
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.3.2.1.13
A bit string indicating which current alarm thresholds are enabled.
Bitsr/w
Enumerated Values:
0lowerCritical
1lowerWarning
2upperWarning
3upperCritical
.1.3.6.1.4.1.318.1.1.32.3.2.1.14
The hysteresis used for voltage alarm deassertions in Volts(V).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.3.2.1.15
The delay measured in samples before a voltage state is asserted. If the
value is zero, then the state is asserted as soon as it is
detected; if it is non-zero, say n, then the assertion condition
must exist for n+1 …
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.3.2.1.16
A bit string indicating which voltage alarm thresholds are enabled.
Bitsr/w
Enumerated Values:
0lowerCritical
1lowerWarning
2upperWarning
3upperCritical
.1.3.6.1.4.1.318.1.1.32.3.2.1.17
.1.3.6.1.4.1.318.1.1.32.3.3 · 1 row entry · 2 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduInputPhasePropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduInputPhasePropertiesTable'
A table of PDU Input Phase properties
pduInputPhasePropertiesEntry row .1.3.6.1.4.1.318.1.1.32.3.3.1
An input phase properties entry containing objects for a particular input phase.
Column Syntax OID
The index of the PDU Input Phase status entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.3.3.1.1
The numeric Input Phase ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.3.3.1.2

pduInputPhaseStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.3.4 · 1 row entry · 9 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduInputPhaseStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduInputPhaseStatusTable'
A table of PDU Input Phase status data
pduInputPhaseStatusEntry row .1.3.6.1.4.1.318.1.1.32.3.4.1
An input phase status entry containing objects for a particular input phase.
Column Syntax OID
The index of the PDU Input Phase status entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.3.4.1.1
The numeric Input Phase ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.3.4.1.2
Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton.
Enumeration
Enumerated Values:
1upperCritical
2upperWarning
3lowerWarning
4lowerCritical
5normal
.1.3.6.1.4.1.318.1.1.32.3.4.1.3
Indicates the present voltage status of the PDU Input Phase being queried
Enumeration
Enumerated Values:
1upperCritical
2upperWarning
3lowerWarning
4lowerCritical
5normal
.1.3.6.1.4.1.318.1.1.32.3.4.1.4
Returns the current draw, in hundredths of Amps(A)
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.3.4.1.5
Returns the voltage, in Volts(V)
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.3.4.1.6
Returns power consumption, in Watts(W)
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.3.4.1.7
Returns power consumption, in Volt-Amps(VA)
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.3.4.1.8
Returns the ratio of active to apparent power of the PDU.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.3.4.1.9
.1.3.6.1.4.1.318.1.1.32.4.2 · 1 row entry · 11 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduCircuitBreakerConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduCircuitBreakerConfigTable'
A table of PDU Circuit Breaker configuration data
pduCircuitBreakerConfigEntry row .1.3.6.1.4.1.318.1.1.32.4.2.1
A circuit breaker configuration entry containing objects for a particular circuit breaker.
Column Syntax OID
The index of the PDU Circuit Breaker configuration table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.4.2.1.1
The number of circuit breakers on the PDU
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.4.2.1.2
The label of the circuit breaker
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.4.2.1.3
This OID controls the behavior of a Switched PDU Circuit
Breaker when an overload condition is possible and additional
outlets are requested to be turned on. Setting this OID to
alwaysAllowTurnON (1) will always allo…
Enumerationr/w
Enumerated Values:
1alwaysAllowTurnOn
2restrictOnUpperWarning
3restrictOnUpperCritical
4notSupported
.1.3.6.1.4.1.318.1.1.32.4.2.1.4
User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.4.2.1.5
User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.4.2.1.6
User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.4.2.1.7
User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.4.2.1.8
The hysteresis used for deassertions in hundredths of Amps(A).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.4.2.1.9
The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon
as it is detected; if it is non-zero, say n, then the
assertion condition must exist for n+1 consecut…
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.4.2.1.10
A bit string indicating which alarm thresholds are enabled.
Bitsr/w
Enumerated Values:
0lowerCritical
1lowerWarning
2upperWarning
3upperCritical
.1.3.6.1.4.1.318.1.1.32.4.2.1.11
.1.3.6.1.4.1.318.1.1.32.4.3 · 1 row entry · 4 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduCircuitBreakerPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduCircuitBreakerPropertiesTable'
A table of PDU circuit breaker properties
pduCircuitBreakerPropertiesEntry row .1.3.6.1.4.1.318.1.1.32.4.3.1
A circuit breaker properties entry containing objects for a particular circuit breaker.
Column Syntax OID
The index of the PDU Circuit Breaker properties table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.4.3.1.1
The number of Circuit Breakers
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.4.3.1.2
This OID describes the outlet phase connections on
the referenced bank as follows:
seqPhase1ToNeutral(1) indicates that outlets attached
to circuit breaker are connected from Phase 1 to Neutral.
seqPhase2ToNeutral(2…
Enumeration
Enumerated Values:
1seqPhase1ToNeutral
2seqPhase2ToNeutral
3seqPhase3ToNeutral
4seqPhase1ToPhase2
5seqPhase2ToPhase3
6seqPhase3ToPhase1
.1.3.6.1.4.1.318.1.1.32.4.3.1.3
The number of Circuit Breakers
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.4.3.1.4
.1.3.6.1.4.1.318.1.1.32.4.4 · 1 row entry · 5 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduCircuitBreakerStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduCircuitBreakerStatusTable'
A table of PDU circuit breaker status data
pduCircuitBreakerStatusEntry row .1.3.6.1.4.1.318.1.1.32.4.4.1
A circuit breaker status entry containing objects for a particular circuit breaker.
Column Syntax OID
The index of the PDU Circuit Breaker status table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.4.4.1.1
The number of Circuit Breakers
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.4.4.1.2
The label on the PDU identifying the circuit breaker
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.4.4.1.3
Indicates the present load status of the PDU Circuit
Breaker being queried
Enumeration
Enumerated Values:
1upperCritical
2upperWarning
3lowerWarning
4lowerCritical
5normal
6off
.1.3.6.1.4.1.318.1.1.32.4.4.1.4
Returns the current draw, in hundredths of Amps(A), of the load on
the PDU Circuit Breaker being queried.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.4.4.1.5
.1.3.6.1.4.1.318.1.1.32.5.2 · 1 row entry · 6 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduOutletSwitchedConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduOutletSwitchedConfigTable'
A table of PDU Switched Outlet configuration data
pduOutletSwitchedConfigEntry row .1.3.6.1.4.1.318.1.1.32.5.2.1
An outlet configuration entry containing objects for a particular outlet.
Column Syntax OID
The index of the PDU Switched Outlet configuration table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.2.1.1
The user-defined name for the Switched Outlet
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.5.2.1.2
The outlet state on device startup; overrides
the global value pduUnitConfigGlobalOutletStateOnStartup.
Enumerationr/w
Enumerated Values:
0off
1on
2lastKnownState
.1.3.6.1.4.1.318.1.1.32.5.2.1.3
The amount of delay, in seconds, between when power is
provided to outlets the outlet and when this outlet
starts providing power
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.2.1.4
The amount of time, in seconds, this outlet will delay
powering off
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.2.1.5
The amount of time, in seconds, this outlet will remain
in powered off state before returning to power on state
during a reboot action.
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.2.1.6
.1.3.6.1.4.1.318.1.1.32.5.3 · 1 row entry · 6 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduOutletSwitchedPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduOutletSwitchedPropertiesTable'
A table of PDU Switched Outlet properties
pduOutletSwitchedPropertiesEntry row .1.3.6.1.4.1.318.1.1.32.5.3.1
An outlet properties entry containing objects for a particular outlet.
Column Syntax OID
The index of the PDU Switched Outlet properties table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.3.1.1
The numeric Switched Outlet ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.3.1.2
The user-defined switched outlet ID string
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.5.3.1.3
This OID describes the outlet phase connections
on the referenced bank as follows:
seqPhase1ToNeutral(1) indicates that outlets
attached to Switched Outlet are connected from Phase 1 to Neutral.
seqPhase2ToNeutral(2…
Enumeration
Enumerated Values:
1seqPhase1ToNeutral
2seqPhase2ToNeutral
3seqPhase3ToNeutral
4seqPhase1ToPhase2
5seqPhase2ToPhase3
6seqPhase3ToPhase1
.1.3.6.1.4.1.318.1.1.32.5.3.1.4
The numeric Circuit Breaker ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.3.1.5
The current rating of outlet in hundreths of ampere
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.3.1.6
.1.3.6.1.4.1.318.1.1.32.5.4 · 1 row entry · 4 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduOutletSwitchedStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduOutletSwitchedStatusTable'
A table of PDU Switched Outlet status data
pduOutletSwitchedStatusEntry row .1.3.6.1.4.1.318.1.1.32.5.4.1
Status data from the PDU Switched Outlet being queried
Column Syntax OID
The index of the PDU Switched Outlet status table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.4.1.1
The numeric Switched Outlet ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.4.1.2
The user-defined switched outlet ID string
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.5.4.1.3
Indicates the present switch state of the
PDU switched outlet being queried
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.318.1.1.32.5.4.1.4
.1.3.6.1.4.1.318.1.1.32.5.5 · 1 row entry · 4 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduOutletSwitchedControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduOutletSwitchedControlTable'
A table of PDU Switched Outlet status data
pduOutletSwitchedControlEntry row .1.3.6.1.4.1.318.1.1.32.5.5.1
Status data from the PDU Switched Outlet
being queried
Column Syntax OID
The index to the PDU switched outlet
control data table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.5.1.1
The numeric Switched Outlet ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.5.1.2
The user-defined switched outlet ID string
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.5.5.1.3
Getting this variable will return the outlet state.
If the outlet is on, the immediateOn (2)
value will be returned. If the outlet is off,
the immediateOff (1) value will be returned.
If the state of the outlet canno…
Enumerationr/w
Enumerated Values:
1immediateOff
2immediateOn
3delayedOff
4delayedOn
5immediateReboot
6delayedReboot
7outletUnknown
.1.3.6.1.4.1.318.1.1.32.5.5.1.4

pduOutletMeteredConfigTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.5.7 · 1 row entry · 9 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduOutletMeteredConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduOutletMeteredConfigTable'
A table of PDU Metered Outlet configuration data
pduOutletMeteredConfigEntry row .1.3.6.1.4.1.318.1.1.32.5.7.1
An outlet configuration entry containing objects for a particular outlet.
Column Syntax OID
The index of the PDU Metered Outlet
configuration table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.7.1.1
The user-defined name for the Metered Outlet
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.5.7.1.2
User-defined lower critical outlet active power alarm threshold in Watts(W).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.5.7.1.3
User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.5.7.1.4
User-defined upper critical outlet active power alarm threshold in Watts(W).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.5.7.1.5
User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.5.7.1.6
The hysteresis used for deassertions in Watts(W).
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.5.7.1.7
The delay measured in samples before a state
is asserted. If the value is zero, then the state
is asserted as soon as it is detected; if it is
non-zero, say n, then the assertion condition must
exist for n+1 consecu…
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.5.7.1.8
A bit string indicating which alarm
thresholds are enabled.
Bitsr/w
Enumerated Values:
0lowerCritical
1lowerWarning
2upperWarning
3upperCritical
.1.3.6.1.4.1.318.1.1.32.5.7.1.9
.1.3.6.1.4.1.318.1.1.32.5.8 · 1 row entry · 7 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduOutletMeteredPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduOutletMeteredPropertiesTable'
A table of PDU Metered Outlet properties
pduOutletMeteredPropertiesEntry row .1.3.6.1.4.1.318.1.1.32.5.8.1
Configuration data from the PDU Metered
Outlet being queried
Column Syntax OID
The index of the PDU Metered Outlet
properties table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.8.1.1
The numeric Metered Outlet ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.8.1.2
The user-defined Metered outlet ID string
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.5.8.1.3
This OID describes the outlet phase connections
on the referenced bank as follows:
seqPhase1ToNeutral(1) indicates that outlets attached
to Metered Outlet are connected from Phase 1 to Neutral.
seqPhase2ToNeutral(2)…
Enumeration
Enumerated Values:
1seqPhase1ToNeutral
2seqPhase2ToNeutral
3seqPhase3ToNeutral
4seqPhase1ToPhase2
5seqPhase2ToPhase3
6seqPhase3ToPhase1
.1.3.6.1.4.1.318.1.1.32.5.8.1.4
The numeric Circuit Breaker ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.8.1.5
Maximum power rating of the PDU metered outlet
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.8.1.6
Metered outlet current rating in hundreths of ampere
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.8.1.7

pduOutletMeteredStatusTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.5.9 · 1 row entry · 11 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduOutletMeteredStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduOutletMeteredStatusTable'
A table of PDU Metered Outlet status data
pduOutletMeteredStatusEntry row .1.3.6.1.4.1.318.1.1.32.5.9.1
Status data from the PDU Metered Outlet being queried
Column Syntax OID
The index of the PDU Metered Outlet status table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.9.1.1
The numeric Metered Outlet ID
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.5.9.1.2
The user-defined Metered outlet ID string
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.5.9.1.3
Returns the present load status of the PDU metered outlet being queried.
Enumeration
Enumerated Values:
1upperCritical
2upperWarning
3lowerWarning
4lowerCritical
5normal
.1.3.6.1.4.1.318.1.1.32.5.9.1.4
Returns the current draw, in hundredths of Amps(A), of the load on the PDU
outlet being queried.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.9.1.5
Returns the power draw, in Watts(W), of the load
on the PDU outlet being queried.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.9.1.6
Returns the ratio of active to apparent power
of the PDU Outlet being queried
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.9.1.7
Returns peak power consumption, in Watts(W),
of the Rack PDU outlet being queried.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.9.1.8
Indicates the date and time that this metered
outlet's peak power consumption occurred
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.5.9.1.9
Indicates the start date and time that this metered
outlet began recording peak power observations
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.5.9.1.10
A user resettable energy meter measuring outlet load energy
consumption in tenths of Kilowatt-Hours(kWh).
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.5.9.1.11
.1.3.6.1.4.1.318.1.1.32.6.2 · 1 row entry · 8 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduExternalSensorNamePlateTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduExternalSensorNamePlateTable'
A table of PDU ExternalSensorNamePlate data
pduExternalSensorNamePlateEntry row .1.3.6.1.4.1.318.1.1.32.6.2.1
External Sensor Name Plate data from the external
sensor being queried. The number of entries equals
the value of pduExternalSensorNamePlateTableSize.
Column Syntax OID
The index of the PDU External Sensor status table entry
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.6.2.1.1
A user-defined string identifying the external sensor
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.6.2.1.2
A user-defined description of the external sensor
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.6.2.1.3
A user-defined string identifying the location of the PDU
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.6.2.1.4
The serial number of the external sensor being queried
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.6.2.1.5
The type of external sensor.
Enumeration
Enumerated Values:
1temperature
2humidity
3doorSwitch
4dryContact
5spotFluid
6ropeFluid
7smoke
8beacon
9airVelocity
17modbusAdapter
18hidAdapter
.1.3.6.1.4.1.318.1.1.32.6.2.1.6
The base units the external sensor is measured in.
This parameter does not apply to onOff, trip, vibration,
waterDetection, smokeDetection sensors.
Enumeration
Enumerated Values:
0logic
1degreeC
2degreeF
3percent
4mps
.1.3.6.1.4.1.318.1.1.32.6.2.1.7
Unique identifier of the external sensor.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.6.2.1.8
.1.3.6.1.4.1.318.1.1.32.6.3 · 1 row entry · 7 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduExternalSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduExternalSensorConfigTable'
A table of PDU External Sensor configuration data
pduExternalSensorConfigEntry row .1.3.6.1.4.1.318.1.1.32.6.3.1
Configuration data from the PDU External
Sensor being queried
Column Syntax OID
The index of the PDU External Sensor
configuration table entry
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.6.3.1.1
User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits.
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.6.3.1.2
User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits.
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.6.3.1.3
User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits.
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.6.3.1.4
User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits.
Unsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.318.1.1.32.6.3.1.5
A bit string indicating which alarm
thresholds are enabled.
Bitsr/w
Enumerated Values:
0lowerCritical
1lowerWarning
2upperWarning
3upperCritical
4binarySensorAlarm
.1.3.6.1.4.1.318.1.1.32.6.3.1.6
User defined alarm state of external sensor
Enumerationr/w
Enumerated Values:
0off
1on
.1.3.6.1.4.1.318.1.1.32.6.3.1.7
.1.3.6.1.4.1.318.1.1.32.6.4 · 1 row entry · 7 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduExternalSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduExternalSensorStatusTable'
A table of PDU External Sensor status data
pduExternalSensorStatusEntry row .1.3.6.1.4.1.318.1.1.32.6.4.1
Status data from the PDU External Sensor
being queried
Column Syntax OID
The index of the PDU External Sensor status table entry
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.318.1.1.32.6.4.1.1
The user-defined name for the External Sensor
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.6.4.1.2
The communications status of the sensor
Enumeration
Enumerated Values:
1notInstalled
2commsOk
3commsLost
.1.3.6.1.4.1.318.1.1.32.6.4.1.3
This OID reports the current state of the sensor.
A notPresent (0) response indicates that no sensor is attached.
An alarmed (1) response indicates that the sensor is present
and its measured reading indicates alarmed…
Enumeration
Enumerated Values:
0notPresent
1alarmed
2normal
3belowLowerCritical
4belowLowerWarning
5aboveUpperWarning
6aboveUpperCritical
.1.3.6.1.4.1.318.1.1.32.6.4.1.4
Sensor reading in pduExternalSensorConfigUnits value.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.6.4.1.5
The sensor reading timestamp.
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.6.4.1.6
Temperature sensor reading in tenths of pduExternalSensorConfigUnits value.
This OID is applied to temperature sensor only
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.6.4.1.7

pduUnitSmartCabinetTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.7.2 · 1 row entry · 5 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduUnitSmartCabinetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduUnitSmartCabinetTable'
A table of Smart Cabinet information
pduUnitSmartCabinetEntry row .1.3.6.1.4.1.318.1.1.32.7.2.1
Information of Smart Cabinet
Column Syntax OID
The index of the PDU Smart Cabinet table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.7.2.1.1
User name of ID card
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.7.2.1.2
Card ID.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.7.2.1.3
Indicates the date and time of information update
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.7.2.1.4
Aisle of Smart Cabinet.
Enumeration
Enumerated Values:
1hotAisle
2coldAisle
.1.3.6.1.4.1.318.1.1.32.7.2.1.5
.1.3.6.1.4.1.318.1.1.32.7.4 · 1 row entry · 5 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduUnitSmartCabinetLockStateTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduUnitSmartCabinetLockStateTable'
A table of Smart Cabinet aisle state control
pduUnitSmartCabinetLockStateEntry row .1.3.6.1.4.1.318.1.1.32.7.4.1
Information of Smart Cabinet Lock State
Column Syntax OID
The index of the PDU Smart Cabinet table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.7.4.1.1
Smart Cabinet ColdAisle lock state
Enumerationr/w
Enumerated Values:
0unlock
1lock
2notPresent
.1.3.6.1.4.1.318.1.1.32.7.4.1.2
Smart Cabinet HotAisle lock state
Enumerationr/w
Enumerated Values:
0unlock
1lock
2notPresent
.1.3.6.1.4.1.318.1.1.32.7.4.1.3
Label of cold aisle smartcabinet
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.7.4.1.4
Label of hot aisle smartcabinet
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.7.4.1.5

trapsInfoTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.8.1.1 · 1 row entry · 7 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk trapsInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::trapsInfoTable'
A list of Trap Information entries. The number of
entries are given by the value of pduUnitTableSize.
trapsInfoEntry row .1.3.6.1.4.1.318.1.1.32.8.1.1.1
An entry containing objects used in traps
Indexes
Column Syntax OID
The index of the traps table entry
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.318.1.1.32.8.1.1.1.1
userNamemandatory
The user currently logged in.
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.8.1.1.1.2
userUpdatedmandatory
The user added, deleted, or modified.
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.8.1.1.1.3
The version of Firmware.
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.8.1.1.1.4
roleUpdatedmandatory
The role added, deleted, or modified.
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.8.1.1.1.5
Comma separated list of SMTP recipients
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.8.1.1.1.6
smtpServermandatory
The IP address/host name of the SMTP server
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.8.1.1.1.7

pduEhandleTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.9.1 · 1 row entry · 13 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduEhandleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduEhandleTable'
A list of contact sensors.  The number of entries are
given by number of pdu and pduEhandleCount.
pduEhandleEntry row .1.3.6.1.4.1.318.1.1.32.9.1.1
An entry for a contact sensor
Indexes
Column Syntax OID
The index of the PDU HID table entry
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.318.1.1.32.9.1.1.1
Aisle of HID handle.
Enumeration
Enumerated Values:
1hot
2cold
.1.3.6.1.4.1.318.1.1.32.9.1.1.2
HID handle control opterations
Enumerationr/w
Enumerated Values:
1unlock
2lock
.1.3.6.1.4.1.318.1.1.32.9.1.1.3
The firmware revision level of the HID
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.9.1.1.4
HID Mechanical opterations
Enumeration
Enumerated Values:
1unlock
2lock
.1.3.6.1.4.1.318.1.1.32.9.1.1.5
The Serial Number of the HID
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.9.1.1.6
The hardware revision level of the HID
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.9.1.1.7
HID Electronic Latch Autolock Time in seconds, Value ranges (0-999)
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.9.1.1.8
HID Door Open Time in seconds, Value ranges (0-999)
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.9.1.1.9
HID Max Door Open Time in seconds, Value ranges (0-32400),
critical alarm will be raised if door is left open past this time
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.9.1.1.10
Rack Access User minimum PIN Length, value ranges(1-15)
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.318.1.1.32.9.1.1.11
Rack Access User PIN mode setting
Enumerationr/w
Enumerated Values:
1visible
2hidden
.1.3.6.1.4.1.318.1.1.32.9.1.1.12
Rack Access Aisle Control setting,
when set to standalone each aisle will controlled seprately,
when set to combined opposite aisle can be controlled with authenticated control action on either aisle
Enumerationr/w
Enumerated Values:
1combined
2standalone
.1.3.6.1.4.1.318.1.1.32.9.1.1.13

pduEhandleControlTable

table mandatory
.1.3.6.1.4.1.318.1.1.32.9.2 · 1 row entry · 9 columns
Uses the apc variant from /opt/observium/mibs/apc.
Command help
Walk pduEhandleControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'CPDU-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'CPDU-MIB::pduEhandleControlTable'
A list of smartcard.  The number of entries are
given by number of pdu and pduEhandleCount.
pduEhandleControlEntry row .1.3.6.1.4.1.318.1.1.32.9.2.1
The smart card table entry containing the usrname, cardid, cardaisle etc.
Column Syntax OID
The index of the PDU smartcard table entry
Integer32
Constraints:
range: 1-200
.1.3.6.1.4.1.318.1.1.32.9.2.1.1
User name of smartcard
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.9.2.1.2
smartcard ID.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.9.2.1.3
Indicates the date and time of accessing
RFC1213-MIBDisplayString .1.3.6.1.4.1.318.1.1.32.9.2.1.4
Aisle of authorized card
Enumerationr/w
Enumerated Values:
1hot
2cold
3both
.1.3.6.1.4.1.318.1.1.32.9.2.1.5
Indicates the start date and time Rack access user is given access
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.9.2.1.6
Indicates the date and time when the access of user card will expire, To set expire time first set user as temporary user
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.318.1.1.32.9.2.1.7
Indicates if the card user has temporary access
Enumerationr/w
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.318.1.1.32.9.2.1.8
Rack acess control entry keypad PIN