batteryAlarmLowTemperature
BATTERY-MIB ·
.1.3.6.1.2.1.233.1.1.1.24
Object
column
r/w
deci-degrees Celsius Integer32
This object provides the lower-threshold value for object
batteryTemperature. If the value of object
batteryTemperature falls below this threshold, a battery
low temperature alarm will be raised. The alarm procedure
may include generating a batteryTemperatureNotification.
A value of '7fffffff'H indicates that no alarm will be
raised for any value of object batteryTemperature.
Context
- MIB
- BATTERY-MIB
- OID
.1.3.6.1.2.1.233.1.1.1.24- Type
- column
- Access
- readwrite
- Status
- current
- Units
- deci-degrees Celsius
- Parent
- batteryEntry
Syntax
deci-degrees Celsius Integer32
Values & Constraints
No enumerated values or constraints recorded.