batteryAlarmLowCharge
BATTERY-MIB ·
.1.3.6.1.2.1.233.1.1.1.19
Object
This object provides the lower-threshold value for object
batteryActualCharge. If the value of object
batteryActualCharge falls below this threshold,
a low-battery alarm will be raised. The alarm procedure may
include generating a batteryLowNotification.
This object should be set to a value such that when the
batteryLowNotification is generated, the battery is still
sufficiently charged to keep the device(s) that it powers
operational for a time long enough to take actions before
the powered device(s) enters a 'sleep' or 'off' state.
A value of 0 indicates that no alarm will be raised for any
value of object batteryActualVoltage.
Context
- MIB
- BATTERY-MIB
- OID
.1.3.6.1.2.1.233.1.1.1.19- Type
- column
- Access
- readwrite
- Status
- current
- Units
- milliampere hours
- Parent
- batteryEntry
- Groups
- 1
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BATTERY-MIB' -M '/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BATTERY-MIB::batteryAlarmLowCharge'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'BATTERY-MIB' -M '/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BATTERY-MIB::batteryAlarmLowCharge.<entPhysicalIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'BATTERY-MIB' -M '/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'BATTERY-MIB::batteryAlarmLowCharge'
Syntax
milliampere hoursSNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Conformance
Member of
Compliance refinements
batteryCompliance
readonly
A compliant implementation is not required
to support set operations on this object.
to support set operations on this object.