batteryAlarmHighCycleCount
BATTERY-MIB ·
.1.3.6.1.2.1.233.1.1.1.22
Object
This object provides the upper-threshold value for object
batteryChargingCycleCount. If the value of object
batteryChargingCycleCount rises above this threshold,
a battery aging alarm will be raised. The alarm procedure
may include generating a batteryAgingNotification.
A value of 0 indicates that no alarm will be raised for any
value of object batteryChargingCycleCount.
Context
- MIB
- BATTERY-MIB
- OID
.1.3.6.1.2.1.233.1.1.1.22- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- batteryEntry
- Groups
- 1
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BATTERY-MIB' -M '/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BATTERY-MIB::batteryAlarmHighCycleCount'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'BATTERY-MIB' -M '/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BATTERY-MIB::batteryAlarmHighCycleCount.<entPhysicalIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'BATTERY-MIB' -M '/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'BATTERY-MIB::batteryAlarmHighCycleCount'
Syntax
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Conformance
Member of
Compliance refinements
batteryCompliance
readonly
A compliant implementation is not required
to support set operations on this object.
to support set operations on this object.