bacsStringAlarm
OBS ✓
BACS2-MIB ·
.1.3.6.1.2.1.33.5.2.7.1.6
Object
column HEX flagsNonNegativeInteger
The BACS String Alarm Flags(0x0=No Alarm, 0x1=General Alarm, 0x2=System Failure, 0x4=Voltage High Alarm, 0x8=Voltage Low Alarm, 0x10=Temperature High Alarm, 0x20=Temperature Low Alarm, 0x40=Resistor High Alarm, 0x80=Resistor Low Alarm, 0x100=Equalizing Error Alarm, 0x200=Voltage High Warning, 0x400=Voltage Low Warning, 0x800=Temperature High Warning, 0x1000=Temperature Low Warning, 0x2000=Resistor High Warning, 0x4000=Resistor Low Warning, 0x8000=Incompatible Module Rev).
Observium directly uses this object
This object is referenced by an Observium discovery or polling workflow.
Used in:
Status
Explore Observium network monitoring
Context
- MIB
- BACS2-MIB
- OID
.1.3.6.1.2.1.33.5.2.7.1.6- Type
- column
- Access
- readonly
- Status
- current
- Units
- HEX flags
- Parent
- bacsStringEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACS2-MIB' -M '/opt/observium/mibs/generex:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACS2-MIB::bacsStringAlarm'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'BACS2-MIB' -M '/opt/observium/mibs/generex:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACS2-MIB::bacsStringAlarm.<bacsStringIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'BACS2-MIB' -M '/opt/observium/mibs/generex:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'BACS2-MIB::bacsStringAlarm'
Syntax
HEX flagsNonNegativeInteger
- Source
- NonNegativeInteger
- Base type
Integer32- Display format
d
Type Description
This data type is a non-negative value.
Values & Constraints
Type Constraints
range: 0..2147483647