bacsModuleState

OBS ✓
BACS2-MIB · .1.3.6.1.2.1.33.5.2.5.1.6

Object

The module alarm flags(0x0=No Alarm, 0x1=General Alarm, 0x2=System Failure, 0x4=Voltage High Alarm, 0x8=Voltage Low Alarm, 0x10=Temperature High Alarm, 0x20=Temperature Low Alarm, 0x40=Resistor High Alarm, 0x80=Resistor Low Alarm, 0x100=Equalizing Error Alarm, 0x200=Voltage High Warning, 0x400=Voltage Low Warning, 0x800=Temperature High Warning, 0x1000=Temperature Low Warning, 0x2000=Resistor High Warning, 0x4000=Resistor Low Warning, 0x8000=Incompatible Module Rev).
Observium directly uses this object
This object is referenced by an Observium discovery or polling workflow.
Used in: Status
Explore Observium network monitoring

Context

MIB
BACS2-MIB
OID
.1.3.6.1.2.1.33.5.2.5.1.6
Type
column
Access
readonly
Status
current
Parent
bacsModuleEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'BACS2-MIB' -M '/opt/observium/mibs/generex:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACS2-MIB::bacsModuleState'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'BACS2-MIB' -M '/opt/observium/mibs/generex:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'BACS2-MIB::bacsModuleState.<bacsModuleIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'BACS2-MIB' -M '/opt/observium/mibs/generex:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'BACS2-MIB::bacsModuleState'

Syntax

Source
NonNegativeInteger
Base type
Integer32
Display format
d
Type Description
This data type is a non-negative value.

Values & Constraints

Type Constraints
range: 0..2147483647