SCTE-HMS-HE-POWER-SUPPLY-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
2
Rows
2
Columns
8
hePsUnitTable
table.1.3.6.1.4.1.5591.1.11.2.2.1.1.1
·
1 row entry
·
4 columns
Uses the scte variant from
Command help
/opt/observium/mibs/scte.
Walk hePsUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCTE-HMS-HE-POWER-SUPPLY-MIB' -M '/opt/observium/mibs/scte:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCTE-HMS-HE-POWER-SUPPLY-MIB::hePsUnitTable'
A table containing information about headend (or indoor plant) power supplies. These power supplies could be, for example, plug-in modules for a chassis.
Information about each Power Supply in the subsystem. Each Power Supply
unit will have an entry in the Entity MIB supported for this agent.
unit will have an entry in the Entity MIB supported for this agent.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Scaled representation of the input current (AC or DC) for
this power supply. This is an RMS value for AC currents. This object must provide for the alarm management capabilities with a corresponding ent… |
milliamperesSCTE-HMS-HEADENDIDENT-MIBHeMilliAmp | .1.3.6.1.4.1.5591.1.11.2.2.1.1.1.1.1 |
|
Scaled representation of the input power (AC or DC) for
this power supply. This is an RMS value for AC powers. This object must provide for the alarm management capabilities with a corresponding entry i… |
hundredths of a wattSCTE-HMS-HEADENDIDENT-MIBHeHundredthWatts | .1.3.6.1.4.1.5591.1.11.2.2.1.1.1.1.2 |
|
This string will describe the model type of the Power Supply.
Examples are AC+110, AC+220, DC-48, DC+48. This model type should match the entry in the Entity mib for this object. |
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.5591.1.11.2.2.1.1.1.1.3 |
|
Scaled representation of the input voltage (AC or DC) for
this power supply. This is an RMS value for AC voltages. This object must provide for the alarm management capabilities with a corresponding ent… |
tenths of a voltSCTE-HMS-HEADENDIDENT-MIBHeTenthVolt | .1.3.6.1.4.1.5591.1.11.2.2.1.1.1.1.4 |
hePsOutputTable
table.1.3.6.1.4.1.5591.1.11.2.2.1.1.2
·
1 row entry
·
4 columns
Uses the scte variant from
Command help
/opt/observium/mibs/scte.
Walk hePsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCTE-HMS-HE-POWER-SUPPLY-MIB' -M '/opt/observium/mibs/scte:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCTE-HMS-HE-POWER-SUPPLY-MIB::hePsOutputTable'
A list of monitorable parameter entries for power supply outputs.
An entry containing management information applicable to
a particular power supplies outputs.
a particular power supplies outputs.
| Column | Syntax | OID |
|---|---|---|
|
An arbitrary value which uniquely identifies each entry.
|
SNMPv2-SMIUnsigned32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.5591.1.11.2.2.1.1.2.1.1 |
|
Scaled representation of the output voltage for this power supply output.
If a single PHYSICAL power supply provides multiple voltages, each voltage shall have its own entry in this table. … |
tenths of a voltSCTE-HMS-HEADENDIDENT-MIBHeTenthVolt | .1.3.6.1.4.1.5591.1.11.2.2.1.1.2.1.2 |
|
Scaled representation of the output current for this power supply output.
This object must provide for the alarm management capabilities with a corresponding entry in the propertyTable of SCTE-HMS-PROPE… |
milliamperesSCTE-HMS-HEADENDIDENT-MIBHeMilliAmp | .1.3.6.1.4.1.5591.1.11.2.2.1.1.2.1.3 |
|
Scaled representation of the output power for this power supply output.
This object must provide for the alarm management capabilities with a corresponding entry in the propertyTable of SCTE-HMS-PROPERT… |
hundredths of a wattSCTE-HMS-HEADENDIDENT-MIBHeHundredthWatts | .1.3.6.1.4.1.5591.1.11.2.2.1.1.2.1.4 |