ICT-DISTRIBUTION-PANEL-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
3
Rows
3
Columns
12

outputTable

table mandatory
.1.3.6.1.4.1.39145.10.8 · 1 row entry · 5 columns
Uses the ict variant from /opt/observium/mibs/ict.
Command help
Walk outputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ICT-DISTRIBUTION-PANEL-MIB' -M '/opt/observium/mibs/ict:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ICT-DISTRIBUTION-PANEL-MIB::outputTable'
Output Table
outputEntry row .1.3.6.1.4.1.39145.10.8.1
Indexes
No indexes recorded
Column Syntax OID
outputNumbermandatory
Output Number
Integer32 .1.3.6.1.4.1.39145.10.8.1.1
outputNamemandatory
Output Label
RFC1213-MIBDisplayString .1.3.6.1.4.1.39145.10.8.1.2
outputCurrentmandatory
Output Current (Amps)
RFC1213-MIBDisplayString .1.3.6.1.4.1.39145.10.8.1.3
Output Fuse Status ('1' indicates Fuse is OK, and '2' indicates Fuse is OPEN)
Enumeration .1.3.6.1.4.1.39145.10.8.1.4
outputEnablemandatory
Output Relay Enable ('1' indicates the Output is ENABLED, and '2' indicates the Output is DISABLED)
Enumerationr/w .1.3.6.1.4.1.39145.10.8.1.5

alarmTable

table mandatory
.1.3.6.1.4.1.39145.10.9 · 1 row entry · 3 columns
Uses the ict variant from /opt/observium/mibs/ict.
Command help
Walk alarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ICT-DISTRIBUTION-PANEL-MIB' -M '/opt/observium/mibs/ict:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ICT-DISTRIBUTION-PANEL-MIB::alarmTable'
Alarm Input Table
alarmEntry row .1.3.6.1.4.1.39145.10.9.1
Indexes
No indexes recorded
Column Syntax OID
alarmNumbermandatory
Alarm Input Number
Integer32 .1.3.6.1.4.1.39145.10.9.1.1
alarmNamemandatory
Alarm Input Name
RFC1213-MIBDisplayString .1.3.6.1.4.1.39145.10.9.1.2
alarmStatusmandatory
Alarm Input Status ('1' indicates Alarm is INACTIVE,'2' indicates Alarm is READY, and '3' indicates Alarm is in an ALARM condition)
Enumeration .1.3.6.1.4.1.39145.10.9.1.3

busTable

table mandatory
.1.3.6.1.4.1.39145.10.10 · 1 row entry · 4 columns
Uses the ict variant from /opt/observium/mibs/ict.
Command help
Walk busTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ICT-DISTRIBUTION-PANEL-MIB' -M '/opt/observium/mibs/ict:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ICT-DISTRIBUTION-PANEL-MIB::busTable'
Bus Table
busEntry row .1.3.6.1.4.1.39145.10.10.1
Indexes
No indexes recorded
Column Syntax OID
busNumbermandatory
Bus Number
Integer32 .1.3.6.1.4.1.39145.10.10.1.1
busNamemandatory
Bus Name
RFC1213-MIBDisplayString .1.3.6.1.4.1.39145.10.10.1.2
busVoltagemandatory
Bus Voltage (Volts)
RFC1213-MIBDisplayString .1.3.6.1.4.1.39145.10.10.1.3
busCurrentmandatory
Total Bus Current (Amps)
RFC1213-MIBDisplayString .1.3.6.1.4.1.39145.10.10.1.4