xupsLoadShedSecsWithRestart
XUPS-MIB ·
.1.3.6.1.4.1.534.1.9.6
Object
scalar
r/w
seconds Integer32
Setting this value will cause the UPS output to turn off after the set number of seconds, then restart (after a UPS-defined 'down time') when the utility is again available. Unlike xupsControlOutputOffDelay, which might or might not, this object always maps to the XCP 0x8A Load Dump & Restart command, so the desired shutdown and restart behavior is guaranteed to happen. Once set, this command cannot be aborted. This is the preferred Control object to use when performing an On Battery OS Shutdown.
Context
- MIB
- XUPS-MIB
- OID
.1.3.6.1.4.1.534.1.9.6- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- seconds
- Parent
- xupsControl
- Siblings
- 6
Syntax
seconds Integer32
Values & Constraints
Object Constraints
range: 0-2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| xupsControlOutputOffDelay Setting this value to other than zero will cause the UPS
output to turn off after the number of seconds.
Setting it to 0 will cause an attempt to abort a pending
shutdown. | scalar | seconds Integer32 | .1.3.6.1.4.1.534.1.9.1 |
| xupsControlOutputOnDelay Setting this value to other than zero will cause the UPS
output to turn on after the number of seconds.
Setting it to 0 will cause an attempt to abort a pending
startup. | scalar | seconds Integer32 | .1.3.6.1.4.1.534.1.9.2 |
| xupsControlOutputOffTrapDelay When xupsControlOutputOffDelay reaches this value, a trap will
be sent. | scalar | seconds Integer32 | .1.3.6.1.4.1.534.1.9.3 |
| xupsControlOutputOnTrapDelay deprecated When xupsControlOutputOnDelay reaches this value, a
xupsOutputOff trap will be sent. | scalar | seconds Integer32 | .1.3.6.1.4.1.534.1.9.4 |
| xupsControlToBypassDelay Setting this value to other than zero will cause the UPS
output to go to Bypass after the number of seconds.
If the Bypass is unavailable, this may cause the UPS
to not supply pow… | scalar | seconds Integer32 | .1.3.6.1.4.1.534.1.9.5 |
| xupsSwitchable Parameter which indicates whether UPS commands received via any
communication path (aside from manual controls) are able (switchable)
or not able (notSwitchable) to control the … | scalar | Enumeration | .1.3.6.1.4.1.534.1.9.7 |